14
3.2 WH-MXC12J9E8
Item
Unit
Refrigerant System
Performance Test Condition
EN 14511 / EN 14825
POS (EAN)
5025232910700
Cooling Capacity
Condition
(Ambient/Water)
A35W7
kW
12.00
BTU/h
41000
kcal/h
10320
Cooling EER
W/W
2.84
kcal/hW
2.44
Heating Capacity
Condition
(Ambient/Water)
A7W35
A2W35
kW
12.00
12.00
BTU/h
41000
41000
kcal/h
10320
10320
Heating COP
W/W
4.80
3.53
kcal/hW
4.13
3.04
Heating ErP
Low temperature Application (W35)
Warmer
Average
Colder
Application
Climate
Pdesign
kW
9.0
9.0
11.0
Tbivalent / TOL
°C
2 / 2
-10 / -10
-15 / -22
SCOP / ns
(W/W) / %
6.47 / 256
4.96 / 195
4.31 / 169
Annual Consumption
kWh
1859
3747
6289
Class
A+++
A+++
A++
Medium temperature Application (W55)
Warmer
Average
Colder
Application
Climate
Pdesign
kW
9.0
9.0
11.0
Tbivalent / TOL
°C
2 / 2
-10 / -10
-15 / -22
SCOP / ns
(W/W) / %
4.34 / 171
3.57 / 140
3.26 / 127
Annual Consumption
kWh
2772
5208
8327
Class
A+++
A++
A++
Air Flow
m³/min (ft³/min)
Cooling: 102.4 (3620)
Heating: 76.8 (2710)
Refrigerant Control Device
Expansion Valve
Refrigerant Oil
cm³
FW50S (1200)
Refrigerant (R32)
kg (oz)
1.60 (56.4)
F-GAS
GWP
675
CO2eq (ton) (Precharged / Maximum)
1.080 / -
Compressor
Type
Hermetic Motor
Motor Type
Brushless (4-poles)
Rated Output
kW
3.0