background image

5

Access to Internal Components 

 

WARNING

This section is for authorized and licensed electrician/water system 
installer only. Work behind the front plate secured by screws 
must only be carried out under supervision of qualifi ed contractor, 
installation engineer or service person.

 

CAUTION

Open or close the Front Plate carefully. 

The heavy Front Plate may injures the 

fi ngers.

* The remote control cable is connected 

to the front panel, so be careful when 
removing the panel.

Open and Close Front Plate 

h

1.  Remove the 2 mounting screws of Front Plate 

h

.

2.  Slide it upwards to unhook the Front Plate 

h

 hook.

3.  Reverse above steps 1~2 for close it.

Water Piping Installation

 

Please engage a licensed water circuit installer to install this 
water circuit.

 

This water circuit must comply with relevant European and national 
regulations (including EN61770), and local building regulation 
codes.

 

Ensure the components installed in the water circuit could withstand 
water pressure during operation.

 

Do not use worn out tube or detachable hose-set.

 

Do not apply excessive force to pipes that may damage the pipes.

 

Choose proper sealer which can withstand the pressures and 
temperatures of the system.

 

Make sure to use two spanners to tighten the connection. Further 
tighten the nuts with torque wrench in specifi ed torque as stated 
in the table.

 

Cover the pipe end to prevent dirt and dust when inserting it 
through a wall.

 

If non-brass metallic piping is used for installation, make sure to 
insulate the pipes to prevent galvanic corrosion.

 

Do not connect galvanised pipes, this will cause galvanic corrosion.

 

Use correct nut for all Tank Unit tube connections and clean 
all tubes with tap water before installation. See Tube Position 
Diagram for detail.

Tube Connector

Nut Size

Torque

a

 & 

b

RP 1¼"

117.6 N•m

c

 & 

d

RP ¾"

58.8 N•m

e

 & 

f

RP 1"

88.2 N•m

Torque wrench Spanner

Hook

2X (screw)

 

CAUTION

Do not overtighten, overtightening may cause water leakage.

 

Make sure to insulate the water circuit pipes to prevent reduction 
of heating capacity.

 

After installation, check the water leakage condition in connection 
area during test run.

 

Failure to connect the tube appropriately might cause the Tank 
Unit malfunction.

 

Protection From Frost:
If the Tank Unit is being exposed to frost while power supply failure 
or pump operating failure, drain the system. When water is idle 
inside the system, freezing up is very likely to happen which could 
damage the system. Make sure the power supply is turned off before 
draining. Heater Assembly 

0

 may be damaged under dry heating.

 

Corrosion Resistance:
Duplex stainless steel is naturally corrosion resistant to mains 
water supply. No specifi c maintenance is required to maintain this 
resistance. However, please note that Tank Unit is not guaranteed 
for use with a private water supply.

 

It is recommended to use a tray (fi eld supply) to collect water from 
the Tank Unit if water leakage occur.

Recommended piping installation sequence: 
(a) 

 (c) 

 (e) 

 (f) 

 (b) 

 (d)

(A) Space Heating/Cooling Pipework

 

Connect Tank Unit Tube Connector 

a

 to outlet connector of Zone 1 

Panel/Floor heater.

 

Connect Tank Unit Tube Connector 

b

 to inlet connector of Zone 1 

Panel/Floor heater.

 

Failure to connect the tube appropriately might cause the Tank 
Unit malfunction.

 

Refer below table for the rated fl ow rate of each particular 
Outdoor Unit.

Model

Rated Flow Rate (l/min)

Cool

Heat

WH-ADC0509L3E5, 
WH-ADC0509L3E5AN, 
WH-ADC0509L6E5, 
WH-ADC0509L6E5AN

WH-WDG05LE5*

14.3

14.3

WH-WDG07LE5*

20.1

20.1

WH-WDG09LE5*

23.5

25.8

* Do not install automatic air purge valves on indoor water pipes.

In the unlikely event that the R290 refrigerant leaks into the 
water circuit, there is a risk that the refrigerant will leak indoors.

(B) Circulating Pipework

 

Connect Tank unit Tube Connector 

f

 to outdoor unit inlet water 

socket.

 

Connect Tank Unit Tube Connector 

e

 to Outdoor unit outlet water 

socket.

 

Failure to connect results in an error stop the system.

Model

Water piping between outdoor unit and indoor unit

Inner 

diameter

Maximum 

length

Insulator 

thickness

Maximum 

Elevation

WH-WDG05LE5*

ø20

30 m

30 mm 

or more

10 m

WH-WDG07LE5*

ø25

WH-WDG09LE5*

Summary of Contents for WH-ADC0509L3E5

Page 1: ...cause these important contents are related to safety The meaning of each indication used is as below Incorrect installation due to ignorance or negligence of the instructions will cause harm or damage and the seriousness is classified by the following indications Please leave this installation manual with the unit after installation WARNING This indication shows the possibility of causing death or...

Page 2: ...on approval applicable to respective country that may require to notify the local authority before installation The Tank Unit must be shipped and stored in upright condition and dry environment It may laid on its back when being moved into the building Work done to the Tank Unit after remove the front plate cover that secured by screws must be carried out under the supervision of authorized dealer...

Page 3: ...ow Sensor g Water Pressure Sensor h Front Plate i Top Plate j Right Plate k Left Plate l Rear Plate m Tank Sensor Not Visible n Bushing 4 pieces o Safety Relief Valve p Network Adaptor Holder q Electric Anode Bar NotVisible Applicable only forWH ADC0509L3E5AN and WH ADC0509L6E5AN r Electric anode PCB NotVisible Applicable only forWH ADC0509L3E5AN and WH ADC0509L6E5AN Main Components Diagram Field ...

Page 4: ...Tank Unit A place where air circulation in the room is good A place where drainage can be easily done e g Utility room A place where Tank Unit s operation noise will not cause discomfort to the user A place where Tank Unit is far from door way A place where accessible for maintenance Ensure to keep minimum distance of spaces as illustrated below from wall ceiling or other obstacles A place where f...

Page 5: ...late the water circuit pipes to prevent reduction of heating capacity After installation check the water leakage condition in connection area during test run Failure to connect the tube appropriately might cause the Tank Unit malfunction Protection From Frost If the Tank Unit is being exposed to frost while power supply failure or pump operating failure drain the system When water is idle inside t...

Page 6: ...of this pipework must be in such a way so that the outlet is visible and can not cause any damage Keep away from electrical components It is recommended to fit a tundish into this g pipework Tundish should be visible and positioned away from frost environment and electrical components WARNING This section is for authorized and licensed electrician only Work behind the Control Board Cover 5 secured...

Page 7: ...ap g 2 Set all Tap Shower OPEN 3 Start filling water to the Domestic Hot Water Tank via Tube Connector i After 20 40min water should flow out from Tap Shower Else please contact your local authorized dealer 4 Check and make sure no water leaking at the tube connecting points 5 Set the Domestic Hot Water Tank Discharge Drain Tap g to OPEN for 10 seconds to release air from this pipeline Then set it...

Page 8: ...ed in the Outdoor Unit 1 Confirm that the pressure relief valve is working properly Pull the lever horizontal direction 2 Release the lever when water comes out of the drain pipe of the pressure relief valve While the air continues to come out of the drain pipe keep raising the lever to completely discharge the air 3 Confirm that the water from the drain pipe stops 4 If water is leaking pull the l...

Page 9: ...ove of the case 5 For embedded type Preparation Make 2 holes for screws using a driver Avoid the wire being caught Mount the top case Align the claws of the top case and then align the claws of the bottom case Screws field supply Bottom case Back side Top case Back side Remote controller terminal board Remove the coating Approx 6 mm Make sure the wiring connection is in the correct direction Mount...

Page 10: ...t water piping connections Has the heat insulation been carried out at water piping connection Is the Pressure Relief Valve operation normal Is water pressure higher than 0 5 bar Is the water drainage work properly done Is the power supply voltage within the rated voltage range Is the cables being fixed to RCCB ELCB and terminal board firmly Is the cables being clamped firmly by holder clamper Is ...

Page 11: ...roller Floor heating Indoor Connect floor heating or radiator directly to the Tank Unit Remove remote controller from Tank Unit and install it in the room where floor heating is installed This is an application that uses remote controller as Room Thermostat 3 External Room Thermostat Outdoor Room Thermostat Field supply Floor heating Indoor Connect floor heating or radiator directly to Tank Unit R...

Page 12: ...nk It requires connection setting of buffer tank and T temperature setting at heating operation separately This system requires Optional PCB CZ NS5P Note Buffer tank thermistor must be connected to main indoor PCB only Outdoor Radiator Thermistor 1 Thermistor 2 Buffer tank Pump 2 Pump 1 Mixing valve 1 Indoor Floor heating Connect floor heating or radiator to 2 circuits through buffer tank as shown...

Page 13: ...lected not display on remote controller Indoor Outdoor Simple 2 zone Floor heating Radiator Thermistor 2 Thermistor 1 Pump 2 Mixing valve Indoor Outdoor Radiator This is an example of simple 2 zone control without using buffer tank Built in pump from Tank Unit served as a pump in zone 1 Install mixing valve pump and thermistor specified by Panasonic on zone 2 circuit Please be sure to assign high ...

Page 14: ...it to compensate for insufficient capacity by operate boiler when outdoor temperature drops heat pump capacity is insufficient Boiler is connected parallel with heat pump against heating circuit Besides that an application that connects to the DHW tank s circuit to heat up tank s hot water is also possible Boiler output can be control by either SG ready input from optional PCB or Auto control by 3...

Page 15: ...wer Supply 1 cord Power Supply 2 cord Indoor Unit Outdoor Unit Connecting cable For connection to Optional PCB 7 1 By connecting Optional PCB 2 Zone temperature control can be achieved Please connect mixing valves water pumps and thermistors in zone 1 and zone 2 to each terminals in Optional PCB Temperature of each zone can be controlled independently by remote controller 2 Pump zone 1 and zone 2 ...

Page 16: ... cable Mixing valve zone 1 cable Mixing valve zone 2 cable 2 way valve cable Extra pump cable Boiler contact cable D 1 and D 2 Bushings are for External control cable Outdoor air sensor cable Remote controller cable Room sensor zone 1 cable Room sensor zone 2 cable Buffer tank sensor cable Pool sensor cable Water sensor zone 1 cable Water sensor zone 2 cable Demand signal cable Solar sensor cable ...

Page 17: ... Zone pump AC230V AC 230V 0 6 A max Thermistor inputs Zone room sensor PAW A2W TSRT Buffer tank sensor PAW A2W TSBU Pool water sensor PAW A2W TSHC Zone water sensor PAW A2W TSHC Solar sensor PAW A2W TSSO Recommended External Device Specification This section explains about the external devices optional recommended by Panasonic Please always ensure to use the correct external device during system i...

Page 18: ...cuit board Pull the cable out of the Tank Unit so that there is no pinching If an Optional PCB has been installed in the Tank Unit connect to the CN CNT connector of the Optional PCB 2 Insert a flat head screwdriver into the slot on the top of the adaptor and remove the cover Connect the other end of the CN CNT cable connector to the connector inside the adaptor Slot Connector 3 Pull the CN CNT ca...

Page 19: ...t direct water temp Set pool temp 4 Display Heat temp Display current heating temperature it is set temperature when enclosed by line 5 Display tank temp Display current tank temperature it is set temperature when enclosed by line 6 Outdoor temp Display outdoor temp 3 1 Remote Controller Outline The LCD display as shown in this manual are for instructional purpose only and may differ from the actu...

Page 20: ...ll be recognised as main remote controller Set language confirm Clock format 12 00am Mon 24h am pm Select Confirm When language is set setting screen of time display appears 24h am pm Set time display confirm Date time 12 00am Mon Year Month Day Hour Min 2015 01 01 12 00 Select Confirm YY MM DD Time setup screen appears Set YY MM DD Time confirm Front grille 12 00am Mon Is O D front grille fixed N...

Page 21: ...ction Yes No Tank setup Solar setup 12 Only when the selection for Optional PCB is Yes External Error signal Yes No 13 Only when the selection for Optional PCB is Yes Demand control Yes No 14 Only when the selection for Optional PCB is Yes SG ready Yes No Capacity setup 15 Only when the selection for Optional PCB is Yes External Compressor SW Yes No 16 Circulation liquid Water glycol 17 Only when ...

Page 22: ...Tank is Yes except for AIO 33 Outdoor temp for Cool to Heat Cool Heat change temp setup 34 Tank Floor operation time max Max operation time for Heat Cool mode setup 35 Tank heat up time max Max operation time for Tank mode setup 36 Tank re heat temp Tank re heat temp setup 37 Sterilization Sterilization day and temp and time setup 38 Service setup Pump maximum speed Pump maximum speed setup Air pu...

Page 23: ...ting Depend on model System setup 12 00am Mon Optional PCB connectivity Zone Sensor Heater capacity Anti freezing Select Confirm If there is built in Heater set the selectable heater capacity NOTE There are models which cannot select Heater capacity 4 Anti freezing Initial setting Yes System setup 12 00am Mon Optional PCB connectivity Zone Sensor Heater capacity Anti freezing Select Confirm Operat...

Page 24: ...YES After that please begin setting according to remote controller instruction Boiler icon will be displayed on remote controller top screen After Bivalent connection Set YES there is two option of control pattern to be select SG Ready Auto 1 SG ready Only available to set when optional PCB set to YES SG Ready input from optional PCB terminal control ON OFF of boiler and heat pump as below conditi...

Page 25: ...iler control characteristic in order to select the optimal setting for the system 3 Smart There are Energy price both electricity and boiler and Schedule to be set on remote controller Operation setting of Energy price and Schedule shall be responsible by installer Based on these settings system will calculate the final price for both electricity and boiler When final price of Electricity is lower...

Page 26: ...8 6 85 1 4 1 6 15 5 2 55 50 8 7 90 85 1 7 20 15 5 3 8 8 1 8 5 4 5 6 55 8 9 9 1 90 1 9 2 1 20 5 7 60 55 9 2 95 90 2 2 25 20 5 8 9 3 2 3 5 9 6 1 60 9 4 9 6 95 2 4 2 6 25 6 2 65 60 9 7 100 95 2 7 30 25 6 3 9 8 2 8 6 4 6 6 65 9 9 100 2 9 3 1 30 6 7 70 65 A minimum operating current is applied on each model for protection purpose 0 2 voltage hysteresis is provided The value of voltage after 2nd decimal...

Page 27: ...ter Initial setting Manual System setup 12 00am Mon External compressor SW Circulation liquid Heat Cool SW Force Heater Select Confirm Under manual mode user can turn on force heater through quick menu If selection is auto force heater mode will turn automatically if pop up error happen during operation Force heater will operate follow the latest mode selection mode selection is disable under forc...

Page 28: ...t cool meter and Tank meter Both systems can provide all generation data of heating cooling and DHW directly from external meter If Heat cool meter is set to Yes it will read from external meter for heat pump s energy generation data during heating cooling and DHW operation 1 If Heat cool meter is set to No it will base on unit s calculation for heat pump s energy generation data during heating co...

Page 29: ...tting range is 1 C 15 C 29 Heater ON OFF 0 C OFF ON a Outdoor temp for heater ON Initial setting 0 C Set outdoor temp when back up heater starts to operate Setting range is 20 C 15 C User shall set whether to use or not to use heater b Heater ON delay time Initial setting 30 minutes Set delay time from compressor ON for heater to turn ON if not achieve water set temperature Setting range is 10 min...

Page 30: ...utdoor temp for Cool to Heat Initial setting 10 C 10 C Heat Cool Outdoor temp dropping Set outdoor temp that switches from Cooling to Heating by Auto setting Setting range is 5 C 14 C Timing of judgement is every 1 hour Tank 34 Floor operation time max Initial setting 8h Heat Tank 30min 10h Set max operating hours of heating When max operation time is shortened it can boil the tank more frequently...

Page 31: ...ring room side operation 39 Dry concrete 30 C 1 2 3 4 5 6 35 C 35 C 40 C 40 C 45 C Stage Operate concrete curing operation Select Edit set temp for every stage 1 99 1 is for 1 day Setting range is 25 55 C When it is turned ON dry concrete starts When it is 2 zone it dries both zones 40 Service contact Contact 1 Bryan Adams ABC abc 0 9 Other A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a b c...

Page 32: ...r NOTE It is different from to use not to use backup heater set by client When this setting is used heater power on due to protection against frost will be disabled Please use this setting when it is required by utility company By using this setting it cannot defrost due to low Heating s setting temp and operation may stop H75 Please set under the responsibility of installer When it stops frequent...

Reviews: