Wire and cable specifications
Wiring run
Specifications
Max. length
Door station
«
Switching hub
Cat-5e or higher,
stranded, twisted pair,
straight
100 m
Power supply unit
«
Door station
0.65 mm (22 AWG)
approx. 10 m
2 mm (12 AWG)
approx. 20 m
Power supply unit
«
AC power source
1.2 mm (17 AWG)
No requirement
2 mm (12 AWG)
Door station
«
Relay box
0.5 mm (24 AWG)
According to
specification of
connected device.
1.2 mm (17 AWG)
Relay box
«
Electric lock
0.5 mm (24 AWG)
According to
specification of
connected device.
1.2 mm (17 AWG)
Note the following when selecting wiring
R
For all wiring (except network wiring), use 2-conductor (solid copper) wiring with a PE
(polyethylene)-insulated PVC jacket.
Mid-capacitance, non-shielded wiring is recommended.
R
A certified power supply wiring has to be used with this equipment. The relevant national installation
and/or equipment regulations shall be considered. A certified power supply wiring not lighter than
ordinary polyvinyl chloride flexible wiring according to IEC 60227 shall be used.
R
When connecting an electric lock, select a device that meets the following guidelines.
Electric lock connection terminal (Relay box: S1/S2):
– N/O dry closure contact
– 12 V AC/DC, less than 1 A
17
Installation