(Note1) This is the min. time for operation at the rated output current.
(This time may be longer depending on different types.)
(Note 2) This is the min. time. (The time may be longer with the increase of rated capacity.)
Even if the power failure time is relatively long (approx. 1 min), the inverter may restart after
the power is restored. So inverter, motor and loading equipments should be restarted after
the power is restored more than 4 minutes (wait time + 2 minutes).
[When voltage drop time is more than 15ms but less than 100ms]
Data setting value
"0" (No ride-through
restart function)
Data setting value
"1" (0Hz restart)
Data setting value
"2" (Pickup restart)
Output
frequency
Power
supply
Voltage drop time
LU level
Output
frequency
Output
frequency
Operate according to the start mode
setting details
Wait time
(parameter P026)
Current limit function
LU
trip
LU
trip
LU
trip
0
0
0
0
・
Wait time can be set with parameter P026.
Note
P026
:
Wait time
Used to set the wait time for the start mode, the ride-through restart and retry functions.
0.1 to 100.0
Data setting range(s)
78
P026
Related
parameters
P022
~
P025
Related
parameters