10. Custom mode
"Custom mode" can be used to freely select 10 function parameters frequently changed by the
customer among the 151 function parameters to make the data changing easier.
1~10 can be distributed to custom parameter No.. The distributed data will be written in non-volatile
memory inside the inverter and the data will be stored even if the power is turned off. (Max.
writing times of the non-volatile memory inside the inverter is 100,000 times. Note that function
parameter No. cannot be distributed too frequently. )
10-1. Method of distributing function parameter No. to custom parameter No.
[Setting example] Function parameter "P002" (1st deceleration time) is distributed to custom
parameter "U001".
Stop state or operation state (at 50.0Hz)
Press the MODE button.
Press the MODE button.
Press the MODE button.
Press the MODE button and select the "custom mode".
Press the SET button and confirm the current function
parameter No. to be distributed.
* When function parameter No. in the custom mode is
displayed, a dot following "P" is displayed. "P" changes
to "P.".
(If a password is set, it's necessary to input the password.
Refer to page 139.)
Press the UP button once to change parameter No.
to P.002.
Press the SET button to complete the distribution of
parameter No.
Hold down the SET button for 3 seconds and enter the
distribution setting state.
(Digital display will flicker.)
141
SET
SET
SET
MODE
MODE
MODE
MODE