P090
:
Output TR1 function select
P091
:
Output TR2 function select
Used to set functions of open-collector output 1 (control terminals No.10-12) and open-collector
output 2 (control terminals No.11-12).
・
Output frequency ratio or output current ratio of setting data "11" is set with parameter P097.
・
Retardation time of current detect signal set to "5" and "6" can be set with "P096: Retardation
time of current detect".
ON when timer operates one cycle (only output during wait time)
End of timer's
one cycle
operation
9
9
ON when timer's operation ends (when "tEnd" is displayed)
End of timer's
operation
10
10
ON when the inverter is in the fault trip state
Fault alarm (1)
7
7
ON when the inverter is in the normal state
(OFF when the inverter is in the fault trip state)
Fault alarm (2)
8
8
ON when output current is lower than detect current level
(parameter P095 setting )
Current
detect (2)
6
6
11
5
4
3
2
1
0
TR1
P090
-
5
4
3
2
1
0
TR2
P091
Output state
signal
Current
detect (1)
Frequency
detect
S
et
tin
g
da
ta
Overload
alarm
Arrival signal
Reverse
run signal
Run signal
Function
ON when output current is higher than
detect current level (parameter P095 setting)
ON when the inverter is running in reverse
ON when the output frequency is within the setting
frequency
±
2Hz
ON when the output current is 140% of the rated current or
higher or when the electronic thermal level is reached.
ON when output frequency is higher than detect frequency
(parameter P093 setting )
Usually output PWM signal that is in direct proportion to
output frequency or output current
ON when run signal is ON or during inverter output
Conditions for open-collector output to turn ON
Note
・
Setting data "11" can only be used to set open-collector output 1 (TR1).
・
Setting data "10" is used to output the time set with "P070: Continuous wait time of timer's
operation".
105
P070, P093
P095
~
P097
Related
parameters