MONITOR SELECT and LINE SPEED MULTIPLIER
(Parameter P60 and P61)
Used to select the details of the operation panel's main display.
[Parameter P60: Monitor details selection]
Data setting value
Details displayed on operation panel
0 Output
frequency
1 Line
speed
[Parameter P61: Line speed multiplier setting]
Used to set the multiplier with respect to the frequency when the line speed is displayed
on the operation panel's main display.
Data setting range
0.1 to 100 (can be set in 0.1 units)
[Example: Display line speed ]
⇒
Line speed (m/min) = F (Hz) × K (multiplier)
·
To display the line speed 25 (m/min) for 50Hz, set the multiplier (K) to "0.5".
Note)
A line speed exceeding "999" cannot be displayed.
(The 4-pole motor speed cannot be displayed.)
MAX. OUTPUT VOLTAGE (Parameter P62)
Used to set the max. output voltage.
Data setting range (V)
0 • 1 to 500
(When "0" is set, the power voltage value will be output.)
Note 1)
A voltage exceeding the power voltage
cannot be output.
Note 2)
This setting does not affect the DC
brake level.