PACD011001G2 / PACD011004G3
Appendix (Check Points in Installing UM Series)
Urban Multi Inverter “MX1” Series
85
8.2.2
Types of Refrigerant Piping
1. Match piping size to the connecting pipe of the outdoor unit when rigging a line between the outdoor unit
and Line branch pipes.
2. Match piping size to the connecting pipe of the indoor unit when rigging a line between the Line branch
pipes and indoor unit.
3. Header branch pipes and joint size vary with model. For details, refer to system reference materials.
Line and Header branch pipes
1. Line branch pipes
(Gas line and liquird line branch pipe)
If the selected building pipe differs form the branch pipe in size, cut the conneciton with a pipe cutter as
shown below.
Install the branch pipe either vertically or horizontally.
Insulate the branch pipe as described in the kit installation manual.
Outdoor unit
Total capacity of indoor units
Gas pipe size
Liquid pipe size
CU-5
Less than 100
φ
15.9
φ
9.5
CU-8·10
Less than 100
φ
15.9
φ
9.5
Addition required for small
capacity connection
100 or more
φ
19.1
φ
9.5
Less than 160
160 or more
φ
25.4
φ
12.7