PACD011001G2 / PACD011004G3
Installation 1
Urban Multi Inverter “MX1” Series
53
3.2.12
Additional Charge of Refrigerant
Operational steps
Important points
1. The results of all calculations must be recorded. (Make a list.)
2. The refrigerant will need to be additionally charged whenever the distance between the outdoor unit and
the most distant indoor unit is more than 10m.
3. The additional charging operation should be carried out by input of liquid into the liquid pipes from a
charging cylinder following completion of the vacuum drying operation.
4. When the additional charging operation cannot be satisfactorily completed use the action of the
compressor to complete the additional charging during the test run.
Use the length of the piping to
calculate the amount of
refrigerant required
Additional charge of
refrigerant
(V0995)