Installation 1
PACD011001G2 / PACD011004G3
44
Urban Multi Inverter “MX1” Series
Management of
available space
when placing
several units in
close proximity to
each other
When placing several units in close proximity to each other some thought should be given to the possibility
of short circuiting and also to the provision of adequate space for servicing. (For more detailed information
please refer to the system design materials.)
Note:
1. Height of walls in case of Patterns 1 and 2:
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
2. If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side
service spaces respectively as shown in the figure on the right.
3. When installing the units the most appropriate pattern should be selected from those shown above in
order to obtain the best fit in the space available always bearing in mind the need to leave enough room
for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take
account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work