Instalation 1
PACD011001G2 / PACD011004G3
56
Urban Multi Inverter “MX1” Series
Inverter Series (CU-8 · 10MX, CU-8 · 10MC)
h :
φ
6 . 4 × 2 0 m
i :
φ
6 . 4 × 2 0 m
j :
φ
6 . 4 × 3 0 m
Less than 100
100 or more to 160 (160 excluded)
160 or more
Gas pipe
φ
15.9×1.0
φ
19.1×1.0
φ
25.4×1.2
Liquid pipe
φ
9.5×0.8
φ
12.7×0.9
Actual pipe length
Equivalent length
Difference in height
Difference in height
Actual pipe length
EXAMPLE OF CONNECTION
(When 8 indoor units are connected)
Allowable length after the branch
Between outdoor and indoor
units
Between outdoor and indoor units
Between adjacent indoor units
Branch using Line branch pipes
Branch using Line branch pipes and Header branch pipes
Branch using Header branch pipes
Refrigerant branch kit selection
Outline of selecting pipe size
Outline of how to compute quantity of refrigerant to be charged
additionally.
Quantity of additional charge R (kg)
Example of downstream indoor units
R=
+
+
-2
×0.025
Total
length of
12.7mm
dia. liquid line
Total
length of
9.5mm
dia. liquid line
Total
length of
6.4mm
dia. liquid line
•Round off R to one decimal place.
•When R is zero or smaller, keep the unit in operation.
Pipe length between outdoor and indoor units 100m or less
(Example) 8 :a+ b+c+d+e+f+g+p
≤
100m
(Example) 8 :b+c+d+e+f+g+p
≤
40m
(Example) In case of Line branch pipes C
Indoor units 3 + 4 + 5 + 6 + 7 + 8 .
(Example) In the case of Line branch pipes B Indoor units 7 + 8 .
(Example) In the case of Header branch pipes
Indoor units 1 + 2 + 3 + 4 + 5 + 6 .
(Example) In the case of Header branch pipes
Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8 .
(Example) 1 :a+b+h
≤
100m, 7 :a+i+j
≤
100m
(Example) 6 :b+h
≤
40m, 7 :i+k
≤
40m
(Example) 8 :i
≤
40m
(Example) 8 :a+i
≤
100m
Equivalent pipe length between outdoor and indoor units 125m or less (Assume equivalent pipe length of Line branch pipes to be 0.5m, that of Header branch pipes to be 1m, computation purposes)
Difference in height between outdoor and indoor units (H1) 50m or less (40m or less when outdoor unit is located in a lower position)
Difference in height between adjacent indoor units (H2) 15m or less
Pipe length from first refrigerant branch kit (either Line branch pipes or Header branch pipes) to indoor unit 40m or less
Total capacity sum of indoor units
Less than 160
160 or more
Refrigerant branch kit No. to be used
KHRP26K18T
KHRP26K37T
How to select Line branch pipes
• When using Line branch pipes at the first branch counted from the outdoor unit side, use KHRP26K37T.
(Example: Line branch pipes A)
• In the case of Line branch pipes other than the first branch, select the proper branch kit model based on
the total capacity sum (for computation) of the indoor units installed after the first branch using the
following table. (For the total capacity, see the item 1 in the section under "COMBINATION" at the
beginning.)
Between outdoor unit and uppermost stream refrigerant branch kit
• Match the pipe size to that connected to outdoor unit.
Total capacity sum of indoor units
Less than 160
160 or more
Refrigerant branch kit No. to be used
KHRP26K18H (Up to 6 branches)
KHRP26K37H (Up to 8 branches)
How to select Header branch pipes
• Select the proper branch kit model based on the total capacity sum (for computation) of the indoor units
installed after the header using the following table. (For the total capacity, see the item 1 in the section
under "COMBINATION" at the beginning.)
• Branching is impossible between Header branch pipes and indoor unit.
Model name
CU-8MX, CU-8MC
CU-10MX, CU-10MC
Pipe size (Outer diameter × minimum wall thickness)
Gas pipe
φ
2 5 . 4 × 1 . 2
φ
2 8 . 6 × 1 . 2
Liquid pipe
φ
12.7× 0.9
a :
φ
1 2 . 7 × 3 0 m
b :
φ
1 2 . 7 × 5 m
c :
φ
1 2 . 7 × 5 m
d :
φ
1 2 . 7 × 5 m
e :
φ
9 . 5 × 3 m
f :
φ
9 . 5 × 2 m
g :
φ
9 . 5 × 5 m
h :
φ
9 . 5 × 5 m
i :
φ
6 . 4 × 5 m
j :
φ
6 . 4 × 5 m
k :
φ
6 . 4 × 5 m
l :
φ
9 . 5 × 5 m
m :
φ
6 . 4 × 5 m
n :
φ
6 . 4 × 5 m
o :
φ
6 . 4 × 5 m
Between two immediately adjacent refrigerant branch kits.
• Select the proper pipe size based on the total capacity sum (for computation) of the
indoor units connected downstream using the following table. (For the total capacity
see the item in the selection under "COMBINATION" at the beginning.)
Total capacity sum of
indoor units
Pipe size (Outer diameter × minimum wall thickness)
20 · 25 · 32 · 40
50 · 63 · 80
100 · 125
200
250
Gas Pipe
φ
12.7×0.9
φ
15.9×1.0
φ
19.1×1.0
φ
25.4×1.2
φ
28.6×1.2
Liquid pipe
φ
6.4×0.8
φ
9.5×0.8
φ
12.7×0.9
φ
12.7× 0.9
Between refrigerant branch kit and indoor unit
• Pipe size for direct connection to indoor unit must be the same as
the connection size of indoor unit.
Indoor unit capacity
sum of indoor units
Pipe size (Outer diameter × minimum wall thickness)
(Example)
a :
φ
1 2 . 7 × 3 0 m
b :
φ
1 2 . 7 × 1 0 m
c :
φ
9 . 5 × 1 0 m
d :
φ
6 . 4 × 1 0 m
e :
φ
6 . 4 × 1 0 m
f :
φ
6 . 4 × 1 0 m
g :
φ
6 . 4 × 1 0 m
h :
φ
6 . 4 × 2 0 m
i :
φ
9 . 5 × 1 0 m
j :
φ
9 . 5 × 1 0 m
k :
φ
6 . 4 × 9 m
(Example)
a :
φ
1 2 . 7 × 4 0 m
b :
φ
9 . 5 × 2 0 m
c :
φ
9 . 5 × 1 0 m
d :
φ
6 . 4 × 1 0 m
f :
φ
6 . 4 × 2 0 m
g :
φ
6 . 4 × 2 3 m
(Example)
R = 45×0.1 + 20×0.05 + 30×0.025 -2 = 4.25
4.3kg
↑
a+b+c+d
↑
e+f+g+h+i
↑
i+j+k+l+m+n+p
⇒
R= 40×0.1 + 30×0.05 + 69×0.025 -2 = 5.225
5.2kg
↑
a+b
↑
c+i+j
↑
d+e+f+g+h+k
⇒
R= 40×0.1 + 30×0.05 + 123×0.025 -2 = 6.575
6.6kg
↑
a
↑
b+c
↑
d+e+f+g+h+i
⇒
×0.1
×0.05
Maximum
allowable
length
Allowable
height
length
Pipe size connected to outdoor unit.
(Unit:mm)
(Unit:mm)
Connection pipe size of indoor unit
(Unit:mm)
(M009)