© Panasonic Industrial Devices SUNX Co., Ltd. 2014
61
Wiring
2-5-8 Wiring Configuration for Valid Muting Function (For SF4B-□CA-J05 only)
(Wiring Example of the Control Category 4)
<In case of using I/O circuit for PNP output with SF4B-□CA-J05>
Gray cable
with black line
Gray cable
K1
K2
*S2
*S2
*S2
K1
K2
*S1
Load
Load
24V DC
±10%
+
-
Receiver
Emitter
(Brown) +V
(Brown) +V
(Pale purple) Interlock setting input
(Pink) Emission halt input / Reset input
(Yellow) Override input
(Yellow-green / Black) Auxiliary output
(Shield) Output polarity setting wire
(Shield) Output polarity setting wire
(Blue) 0V
(Blue) 0V
(Orange) Synchroni
(Yellow-green) External device monitor input
(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)
(Orange) Synchroni
(Orange / Black) Synchronization -
(Orange / Black) Synchronization -
(Red) Muting auxiliary output
(Gray) NC
(Gray) NC
(Gray / Black) Large multi-purpose indicator input (Emitter side)
(Gray / Black) Large multi-purpose indicator input (Receiver side)
(Sky-blue / White) Muting input A
(Sky-blue / Black) Muting input B
Interlock function
Invalid (Auto-reset)
External device monitor function Valid
Auxiliary output
Can be used
The device output is selected depending on the connecting state of the output polarity setting wire
(shield). Incorrect wiring may cause the lockout state.
* Symbols
Switch S1
●
Emission halt input / Reset input
Vs to Vs - 2.5V (sink current 5mA or less): Emission (Note), Open: Emission halt
Switch S2
●
Muting input A / B, Override input
Vs to Vs - 2.5V (sink current 5mA or less): Valid (Note), Open: Invalid
K1, K2: External device (Forced guided relay or magnetic contactor)
Note: Vs is the applying supply voltage.
Ramco National
800-280-6933 | [email protected]
www.panasonicsensors.com