Wiring
<In case of using I/O circuit for PNP output with SF4B-□CA-J05>
Gray cable
with black line
Gray cable
K1
K2
*S1
Load
K1
K2
24V DC
±10%
+
-
Receiver
Emitter
(Brown) +V
(Brown) +V
(Pale purple) Interlock setting input
(Pink) Emission halt input / Reset input
(Yellow) Override input
(Yellow-green / Black) Auxiliary output
(Shield) Output polarity setting wire
(Shield) Output polarity setting wire
(Blue) 0V
(Blue) 0V
(Orange) Synchroni
(Yellow-green) External device monitor input
(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)
(Orange) Synchroni
(Orange / Black) Synchronization -
(Orange / Black) Synchronization -
(Red) Muting auxiliary output
(Gray) NC
(Gray) NC
(Gray / Black) Large multi-purpose indicator input (Emitter side)
(Gray / Black) Large multi-purpose indicator input (Receiver side)
(Sky-blue / White) Muting input A
(Sky-blue / Black) Muting input B
Interlock function
Valid (Manual reset)
External device monitor function Valid
Auxiliary output
Can be used
The device output is selected depending on the connecting state of the output polarity setting wire
(shield). Incorrect wiring may cause the lockout state.
* Symbols
Switch S1
Vs to Vs - 2.5V (sink current 5mA or less): Emission halt (Note 1), Open: Emission
K1, K2: External device (Forced guided relay or magnetic contactor)
Notes: 1) Vs is the applying supply voltage.
2) For resetting, refer to “
3-2 Interlock Function
.”