© Panasonic Industrial Devices SUNX Co., Ltd. 2014
64
Adjustment
<Reference>
The beam-axis alignment indicator indicates the reception status for each section of the device
which is divided into 4 sections.
Also, the A (D) of the beam-axis alignment indicates the light-receiving status of the device top
end (bottom end).
For example, when using a 12-beam channel device, there are 3 beam channels per section (i.e.,
12/4=3).
When the top end (bottom end) beam channel is received, the A (D) of the beam-axis alignment
indicator blinks in red.
(Example) 12 beam channels
Beam-axis
alignment indicator
A: Blinks
B to D: Turns OFF
Light received
Light blocked
Beam-axis
alignment indicator
A: Blinks
B to D: Turns OFF
Beam-axis
alignment indicator
A: Lights up
B to D: Turns OFF
Beam-axis
alignment indicator
All: Turns OFF
2 b e a m c h a n n e l s
including the top end
beam channel are
received
3 beam channels in top
section are received
Only top end beam
channel is received
2 b e a m c h a n n e l s
e x c l u d i n g t h e t o p
end beam channel
are received
All the 3 beam channels divided into each section are received, the beam-axis alignment indica-
tor lights up in red.
The indicators corresponding to the different sections light up in red, one by one, when the beam
channels of the respective sections are received. When all the beam channels are received and
the control output (OSSD 1 / 2) turns ON, all the four indicators of the beam-axis alignment indi-
cator turn into green.
Refer to “
2-6-3 Operation
" for details.
Step 5 After adjustment, tighten the four hexagon-socket head bolts [M3 (length: 6mm)] to se
-
cure the mounting bracket on this device.
The tightening torque should be 0.5N·m or less.
Step 6 Tighten the one intermediate supporting bracket [M3 (length: 6mm)].
The tightening torque should be 0.5N·m or less.
Verify that the beam-axis alignment indicator and incident light intensity indicator on the
display section of the emitter and receiver are green.
CAUTION
After the beam-axis alignment is finished, make sure to confirm that all the bolts are tightened by
the specified torque. For the tightening torque of each bolt, refer to “
2-4 Mounting
.”
Ramco National
800-280-6933 | [email protected]
www.panasonicsensors.com