background image

WARNING

 

Incorrect using of the muting control may cause an accident. Please 

understand the muting control fully, and use it. As for the muting 

control, the following international standards define the require

-

ments.

ISO 13849-1 (EN ISO 13849-1 / JIS B 9705-1) :

“Safety of machinery - Safety-related parts of control systems - Part 

1: General principles for design, Article 5.9 Muting”

IEC 61496-1 (UL 61496-1 / EN 61496-1 / JIS B 9704-1) :

“Safety of machinery - Electro sensitive protective equipment - Part 

1: General requirements and tests, Annex A, A.7 Muting”

IEC 60204-1 (JIS B 9960-1):

“Safety of machinery - Electrical equipment of machines - Part 1: 

General requirements, 9.2.4 Overriding safeguards”

EN 415-4:

“Safety of packaging machines - Part 4: Palletizers and depalletiz

-

ers, Annex A, A2.2 Muting”

ANSI B11.19-1990:

“for Machine Tools-Safeguarding When Referenced by the Other 
B11 Machine Tool Safety Standards-Performance Criteria for the 

Design, Construction, Care, and Operation” 4.2.3 Presence-Sensing 

Devices: Electro-Optical and Radio Frequency (R.F.)

ANSI/RIA R15.06-1999:

“for Industrial Robots and Robot Systems - Safety Requirements, 

10.4.5 Muting”

 

Use the muting control while the machine cycle is not in danger 
mode. Maintain safety with the other measures while the muting 
control is activating.

 

For the application that the muting control is activated when a work-

piece passes through the sensor, place the muting sensor so that 

the conditions for muting control cannot be satisfied by intrusion of 

personnel when the workpiece is passing through the sensor or the 
workpiece is not passing through it.

 

The muting lamp should be installed in a position where it can al-
ways be seen by operators who set or adjust the machine.

 

Be sure to check the operation of the muting function before its 

use. Furthermore, check the state of the muting lamp (cleanliness, 

brightness, etc.)

FUNCTIONS

11

 

Reset operation

WARNING

Design the system such that the reset switch can be operated from  

outside the dangerous area, and also where the operators can see the 

entire dangerous area.

The reset function corresponding to the respective safety outputs 1 / 
2 / 3 is incorporated.

X11, X12 and X13 terminal: Reset input terminal of safety output 1

When X11 and X12 terminals are used: Manual reset

When X11 and X13 terminals are used: Auto-reset

X21, X22 and X23 terminal: Reset input terminal of safety output 2

When X21 and X22 terminals are used: Manual reset

When X21 and X23 terminals are used: Auto-reset

X31 and X32 terminal: Reset input terminal of safety output 3

(Manual reset only).

However, if the muting function is valid, safety output 2 is not turned OFF.

 

Safety output 1

This is the output corresponding to light curtain in light received / 
light blocked status.

In light received status: ON, In light blocked status: OFF 

However, if the emergency stop is valid, safety output 1 is OFF.

 

Safety output 2

This is the output corresponding to the light curtain in light received / 
light blocked status including the muting state.

In light received status or if the muting function is valid: ON, 

In light blocked status and if the muting function is invalid: OFF

However, if the emergency stop is valid, the safety output 2 is OFF.

 

Safety output 3

This is the output corresponding to the external emergency stop switch.

When the emergency stop is invalid: ON

When the emergency stop is valid: OFF

However, if the emergency stop is valid, both safety outputs 1 / 2 are OFF.

Note:  When the safety output is ON, the output transistor goes OFF periodically to self-

diagnose the output circuit. (OFF pulse width: 100μs or less) When the OFF signal 

is fedback, it is judged that the circuit works properly. When the OFF signal is not 

fedback, it is judged that the output circuit or wiring is in error and the safety out

-

put is maintained in the OFF state.

WARNING

Please consider the input response time of the machine to which you 
connect this product so that no malfunction occurs due to this prod-
uct's OFF signal.

 

Emergency stop

Safety output 3 can be controlled by connecting an external emer-
gency stop switch or another interlock device.

*: Be sure to use a 2 NC type forcible dissociation type contact.

 

Test input

WARNING

Do not use the test input function for the purpose of stopping the ma

-

chine in which the light curtain is installed. Failure to do so could result 
in death or serious injury.

This function turns safety outputs 1 / 2 OFF forcibly. 

Open between T1 and T2 terminals: Forcibly OFF.

Short-circuit between T1 and T2 terminals: Normal operation

This is used when the override function is used as well. 

 

Muting function

This function turns the safety output 2 into invalid temporarily. This 
function is available for passing the workpieces through the sensing 
area of the light curtain without stopping the machine.
The muting function becomes valid when all the conditions listed be-

low are satisfied:

The safety output 2 is ON.

The incandescent lamp with 3.6 to 30W shall be connected to ei-

ther muting lamp output 1 or 2, or to both of the inputs.

The output of the muting sensors S3 and S4 shall be changed

from OFF (open) to ON. At this time, the time difference occurred

by changing the output of the muting sensors S3 and S4 into ON
status shall be 0 to 3 sec.

 

Muting sensor input
(Muting sensor is used in the “Dark-ON” state.)

This is used to connect the muting sensor. For following devices, 

photoelectric sensor with semiconductor output, inductive proximity 

sensor, position switch on NO (Normally Open) contacting point, etc. 

are available for applying to the muting sensor.     

S3 terminal (S3+, S3 and S3-): 3-wire PNP open-collector type sensor

S4 terminal (S4+, S4 and S4-): 3-wire NPN open-collector type sensor

 

Muting lamp

This lamp is used to show that the product is in muting state. Two 

lamps can be connected. Even if one of the two lamps breaks, the 

muting operation can be continued because of another lamp. The 
broken lamp can be replaced without suspending your work.

<Blown lamp output>

The diagram shows operation with safety outputs 1 / 2 in auto-reset 
mode.

 

● The lamps are monitored during muting state, and if either of them 

blows, auxiliary output 3 is turned OFF. If only one lamp blows, the 

muting state is maintained, however, if both lamps blow, the muting 

state is canceled immediately.

Light
received
Light
blocked

Light curtain

ON

OFF

ON

OFF

ON

OFF

Safety output 2
(34 and 44)

Muting sensor 1

ON

OFF

Auxiliary output 1
(Muting output)

ON

OFF

Auxiliary output 3
(Blown lamp output)

Muting lamp 
output 1

Blown
lamp

ON

OFF

Muting sensor 2

Muting lamp 
output 2

ON

OFF

Blown
lamp

Blown
lamp

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for SF-C14EX

Page 1: ... raceway This can cause malfunction due to induction CAUTIONS 2 OUTLINE 3 This is the application expansion unit which can control three differ ent safety outputs in combination with the light curtain It exhibits the following features 1 Either PNP or NPN output can be selected with the slide switch 2 It can be connected to the light curtain using the exclusive 8 core connection cable with connect...

Page 2: ...r cable length 10m SFB CCJ10D for receiver cable length 10m The following cables are recommended for power supply side con nector and other connector Power supply side connector A1 and A2 0 2 to 2 5mm2 AWG 24 to 12 Other connector 0 2 to 1 5mm2 AWG 24 to 16 Cable extension is possible up to 50m for each emitter receiver However 30m or less for each emitter receiver for two sets in series connectio...

Page 3: ...or 0V V OUT 0V V OUT 0V Muting sensor 1 PNP output type Muting sensor 2 NPN output type 1 1 Test input Override input Muting lamp output 1 3 6 to 30W Muting lamp output 2 3 6 to 30W 24V 3 Control circuit 24V DC Output polarity selection switch 2 Emergency stop switch 4 4 4 Wiring in auto reset setting broken line PLC etc TIMING CHART 10 Normal operation The diagram shows operation with safety outp...

Page 4: ...e output corresponding to the external emergency stop switch When the emergency stop is invalid ON When the emergency stop is valid OFF However if the emergency stop is valid both safety outputs 1 2 are OFF Note When the safety output is ON the output transistor goes OFF periodically to self diagnose the output circuit OFF pulse width 100μs or less When the OFF signal is fedback it is judged that ...

Page 5: ... display red When the muting function and the fixed blanking function the float ing blanking function are set the fixed blanking function the float ing blanking function are prioritized Fixed blanking function This function enables to protect the control output OSSD 1 2 from turning into OFF even though the specific beam channel is blocked The factory setting is set to be invalid for the fixed bla...

Page 6: ...esistance 3Ω or less Operation mode Output operation Safety output 1 When light curtain is in light received status ON When light curtain is in light blocked status OFF Note 2 Safety output 2 When light curtain is in light received status or the muting function is valid ON When light curtain is in light blocked status and the mut ing function is invalid OFF Note 2 Safety output 3 When the emergenc...

Page 7: ...inks The handy controller SFB HC has been connected Remove the handy controller SFB HC Only the power indicator green and the auxiliary output 1 2 and 3 indica tors orange light up All of the safety outputs 1 2 and 3 are OFF The product is in emergency stop state Wire the emergency stop input output terminals between S11 and S12 and S21 and S22 correctly Check if the emergency stop switch has been...

Reviews: