TROUBLESHOOTING

14

Symptom

Cause 

Remedy

“   ” lights up on the 
digital indicator (red)

Setting data error of 
the product 

• 

Check the noise state.

• 

In case the handy controller

SFB-HC

 (optional) is applied,

reset the function.

• If the error is not cleared, con

-

tact our office.

“   ” blinks on the 
digital indicator (red)

Emergency stop input 
error

• 

Wire the emergency stop input /
output wire correctly. 

“   ” blinks on the 
digital indicator (red)

The total number of 
sensors / total number 
of beam channels error

• 

Check the total number of sen-
sors / total number of beam
channels.

“   ” blinks on the 
digital indicator (red)

Reset input error

• 

Wire the reset input / output wire
correctly.

“   ” blinks on the 
digital indicator (red)

Safety output error
(Safety output circuit error)

• 

Wire the safety output wire cor-
rectly.

“   ” blinks on the 
digital indicator (red)

PNP / NPN setting 
error

• 

Change the setting after turning
the power OFF. 

“   ” blinks on the 
digital indicator (red)

Input voltage monitor 
error

• 

Check the supply voltage and
the voltage capacity.

“   ” blinks on the 
digital indicator (red)

Safety output error
(Safety output short-circuited)

• 

Wire the safety output wire cor-
rectly.

“   ” lights up on the 
digital indicator (red)

The blanking func-
tion is valid.

• 

The blanking function is valid.

(Normal operation)

“   ” lights up on the 
digital indicator (red)

Light curtain commu-
nication error

• 

Check if the light curtain is con-
nected correctly.

• 

Check the operation of the con-
nected light curtain.

“   ” blinks on the 
digital indicator (red)

Safety output circuit 
error

• 

Check the noise state.

“   ” blinks on the 
digital indicator (red)

Effect by noise, power, etc. 

or internal circuit failure

• 

Check the noise state.

“   ” blinks on the 
digital indicator (red)

Internal error of the 
product

• 

Check the noise state.

• Check the wiring, supply voltage 

and voltage capacity. 

• 

If the product does not work cor-

rectly, contact our office.

The test input indicator 
(yellow) lights up

The product is in test 
state.

• 

Wire the test input wire correctly.

The test input indicator 
(yellow) blinks

The handy controller 

SFB-HC

 has been 

connected.

• 

Remove the handy controller

SFB-HC

.

Only the power indicator 
(green) and the auxiliary 

output 1, 2 and 3 indica

-

tors (orange) light up.

All of the safety outputs 

1, 2 and 3 are OFF.

T h e   p r o d u c t   i s   i n 
emergency stop state.

• 

Wire the emergency stop input /
output terminals between S11 and 

S12, and S21 and S22 correctly.

• 

Check if the emergency stop
switch has been “pressed.”

The interlock indicator 
(yellow) lights up.

R e s e t   c a n n o t   b e 
canceled.

• 

Wire the reset input / output wire
correctly. 

• 

Change the relay having appro-
priate response time. 

• 

Replace the relay.

DIMENSIONS (Unit: mm)

16

10

130

67.3

35

4

54.1

40

6.5

80

(99)

25

34.1

13

31.1

11

23

18 18.4

38.4

46

Suitable for 35mm width DIN rail

Emitter side
connector

Receiver 
side
connector

MAINTENANCE

15

 

Be sure to do maintenance before use and 6 month periodic main-
tenance. Refer included instruction manual of light curtain for the 
inspection items.

 

● In case replacing this device to new this device, be sure special 

technician to exchange it. And do daily maintenance and periodic 
maintenance.

INTENDED PRODUCTS FOR CE MARKING

17

 

The model listed under “

SPECIFICATIONS

” comes with 

CE Marking.

As for all other models, please contact our office.

CE MARKING DECLARATION OF CONFORMITY

18

Itemized Essentials of EU Declaration of Conformity

Manufacturer’s Name:

 Panasonic Industrial Devices SUNX Co., Ltd.

Manufacturer’s Address:

 2431-1, Ushiyama-cho, Kasugai, Aichi

 

486-0901, Japan

EU Representative’s Name:

 

Panasonic Marketing Europe GmbH Panasonic Testing Center

EU Representative’s Address:

 

Winsbergring 15, 22525 Hamburg, Germany

Product:

 Exclusive Control Unit for Light Curtain

Model Name:

 

SF-C10

 Series

Trade Name:

 Panasonic

Application of Council Directive:

 

 

-

2006/42/EC Machinery Directive

 

-

2004/108/EC EMC Directive (Valid until April 19, 2016)

 

-

2014/30/EU EMC Directive (Valid from April 20, 2016)

 

-

2011/65/EU RoHS Directive

Harmonized standards:

 

-

EN 61496-1: 2013

 

-

EN ISO 13849-1: 2008

 

-

EN 55011: 2009+A1: 2010

 

-

EN 50581: 2012

Type Examination:

 Certified by TÜV SÜD Product Service GmbH

Ridlerstrasse 65 80339 München Germany

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for SF-C14EX

Page 1: ... raceway This can cause malfunction due to induction CAUTIONS 2 OUTLINE 3 This is the application expansion unit which can control three differ ent safety outputs in combination with the light curtain It exhibits the following features 1 Either PNP or NPN output can be selected with the slide switch 2 It can be connected to the light curtain using the exclusive 8 core connection cable with connect...

Page 2: ...r cable length 10m SFB CCJ10D for receiver cable length 10m The following cables are recommended for power supply side con nector and other connector Power supply side connector A1 and A2 0 2 to 2 5mm2 AWG 24 to 12 Other connector 0 2 to 1 5mm2 AWG 24 to 16 Cable extension is possible up to 50m for each emitter receiver However 30m or less for each emitter receiver for two sets in series connectio...

Page 3: ...or 0V V OUT 0V V OUT 0V Muting sensor 1 PNP output type Muting sensor 2 NPN output type 1 1 Test input Override input Muting lamp output 1 3 6 to 30W Muting lamp output 2 3 6 to 30W 24V 3 Control circuit 24V DC Output polarity selection switch 2 Emergency stop switch 4 4 4 Wiring in auto reset setting broken line PLC etc TIMING CHART 10 Normal operation The diagram shows operation with safety outp...

Page 4: ...e output corresponding to the external emergency stop switch When the emergency stop is invalid ON When the emergency stop is valid OFF However if the emergency stop is valid both safety outputs 1 2 are OFF Note When the safety output is ON the output transistor goes OFF periodically to self diagnose the output circuit OFF pulse width 100μs or less When the OFF signal is fedback it is judged that ...

Page 5: ... display red When the muting function and the fixed blanking function the float ing blanking function are set the fixed blanking function the float ing blanking function are prioritized Fixed blanking function This function enables to protect the control output OSSD 1 2 from turning into OFF even though the specific beam channel is blocked The factory setting is set to be invalid for the fixed bla...

Page 6: ...esistance 3Ω or less Operation mode Output operation Safety output 1 When light curtain is in light received status ON When light curtain is in light blocked status OFF Note 2 Safety output 2 When light curtain is in light received status or the muting function is valid ON When light curtain is in light blocked status and the mut ing function is invalid OFF Note 2 Safety output 3 When the emergenc...

Page 7: ...inks The handy controller SFB HC has been connected Remove the handy controller SFB HC Only the power indicator green and the auxiliary output 1 2 and 3 indica tors orange light up All of the safety outputs 1 2 and 3 are OFF The product is in emergency stop state Wire the emergency stop input output terminals between S11 and S12 and S21 and S22 correctly Check if the emergency stop switch has been...

Reviews: