background image

12

SPECIAL REMARKS

‘‘DRY’’ Operation

How it works

•  Once the room temperature reaches the level that was set, the unit repeats the cycle of

turning on and off automatically.

•  In order to prevent the humidity in the room from rising again, the indoor fan also turns off

when the unit stops operating.

•  The fan speed is set to ‘‘LO.’’ automatically, and cannot be adjusted.
•  ‘‘DRY’’ operation is not possible if the outdoor temperature is 15 °C or less.

Heating Operation

Heating performance

•  Because this appliance heats a room by utilizing the heat of the outside air (heat pump

system),  the heating effi ciency will fall off when the outdoor temperature is very low. If
suffi cient heat cannot be obtained with this heat pump, use another heating appliance in 
conjunction with this unit.

Defrosting

•  When the outdoor temperature is low, frost or ice may form on the outdoor heat exchanger

coil, reducing the heating performance. When this happens, a microcomputer-controlled 
defrosting system operates. At the same time, the fan on the indoor unit stops (or runs at
very low speed in some cases) and the ‘‘STANDBY’’ indicator appears on the display until 
defrosting is completed. Heating operation then restarts after several minutes. (This interval
will vary slightly depending upon the outdoor temperature and the way in which frost forms.)

 

(standby) on the 

display

•  For several minutes after the start of heating operation, the indoor fan will not start running

(or it will run at very low speed in some cases) until the indoor heat exchanger coil has
warmed up suffi ciently. This is because a cold draft prevention system is operating. During
this period, the ‘‘

’’ (standby) indicator remains displayed.

• ‘‘

’’ (standby) remains displayed during defrosting or when the compressor has been

turned off (or when the unit is running at very low speed) by the thermostat when the
system is in the heating mode.

•  Upon completion of defrosting and when the compressor is turned on again, ‘‘

’’

(standby) will turn off automatically as heating operation resumes.

NOTE

Should the power fail while the unit is running

If the power supply for this unit is temporarily cut off, the unit will automatically resume
operation (once the power is restored) using the same settings before the power was cut off.

CARE AND CLEANING

WARNING

1. For safety, be sure to turn the air conditioner off and also to disconnect the power 

before cleaning.

2. Do not pour water on the indoor unit to clean it. This will damage the internal 

components and cause an electric shock hazard.

CAUTION

1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe 

plastic parts using very hot water.

2. Some metal edges and the 

fi

 ns are sharp and may cause injury if handled

improperly; be especially careful when you clean these parts.

3. The internal coil and other components of the outdoor unit must be cleaned 

periodically. Consult your dealer or service center.

Air intake and outlet side 

(Indoor unit)

Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe
them with a clean, soft cloth.
If these parts are stained, use a clean cloth moistened with water. When cleaning the air outlet 
side, be careful not to force the vanes out of place.

Summary of Contents for S-22MK2E5A

Page 1: ...LE1H4 E U 12ME1H8 E S 45MY2E5A U 4LE1H7 E U 14ME1H8 E S 56MY2E5A U 5LE1H7 E U 16ME1H8 E U 6LE1H7 E U 18ME1H8 E U 20ME1H8 E Shows K2 type Wall Mounted ENGLISH ENGLISH Before operating the unit read the...

Page 2: ...numbers are on the nameplate on the bottom of the cabinet Model No _____________________________________ Serial No _______________________ Date of purchase ____________________________________________...

Page 3: ...n avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa ELECTRICAL REQUIREMENTS 1 All wiring must conform to the local electrical codes Co...

Page 4: ...cle or switch off the breaker or switch off the power disconnecting mean to isolate the air conditioner from the main power supply in case of emergency Do not insert your fingers or other objects into...

Page 5: ...l instructions Stop using the product when any abnormality failure occurs and disconnect the power plug Risk of smoke fire electric shock Examples of abnormality failure The product sometimes does not...

Page 6: ...to discard these items please contact your local authorities or dealer and ask for the correct method of disposal Pb Note for the battery symbol bottom two symbol examples This symbol might be used i...

Page 7: ...y hand Horizontal airflow direction louver Manually adjustable Receiver Emergency button K2 type WALL MOUNTED Wireless Remote Controller Optional parts NOTE Refer to the Operating Instructions attache...

Page 8: ...tically selects heating or cooling mode The automatic heating and cooling control for 2WAY and mini VRF system can be performed when all indoor units in the same refrigerant circuit are controlled in...

Page 9: ...ing operation Press the FLAP button to set the flap vertical airflow flap to the downward position and then press the FLAP button again This displays and the airflow automatically swings up and down H...

Page 10: ...ovement and to direct the air in the desired direction press the FLAP button again In the cool mode do not direct the flap down and move out of the cooling zone A otherwise condensation may drip on to...

Page 11: ...irflow direction for the indoor unit that is shown on the display Each time UNIT is pressed the indicator changes in the order shown below When nothing is displayed you can make the setting for all in...

Page 12: ...at exchanger coil has warmed up sufficiently This is because a cold draft prevention system is operating During this period the standby indicator remains displayed standby remains displayed during def...

Page 13: ...thoroughly under the shade away from fire or direct sunlight Replace any damage filter INDOOR UNIT Wipe the unit gently with a soft dry cloth FRONT PANEL Remove Front Panel Raise and pull to remove th...

Page 14: ...stops Fan rotating makes operation smoothly Fan may sometimes rotates because of drying heat exchanger due to settings Wind direction changes while operating Wind direction setting cannot be made Win...

Page 15: ...conditioner still does not work properly although you checked the points as described above first stop the operation and turn off the power switch Then contact your dealer and report the serial numbe...

Page 16: ...ada plat nama di bahagian bawah kabinet No Model _____________________________________ No Siri ________________________ Tarikh Pembelian ______________________________________________________________...

Page 17: ...ana air laut yang masin boleh merecik terus kepada unit atau dalam udara bersulfur berhampiran spa KEPERLUAN ELEKTRIK 1 Semua pendawaian perlu mematuhi kod elektrik tempatan Runding dengan pengedar at...

Page 18: ...dipanjangkan atau yang tiada aspek khusus untuk mencegah pemanasan dan kebakaran AMARAN Berhenti daripada menggunakan produk jika berlaku sebarang keganjilan kegagalan dan cabut palam kuasa atau mati...

Page 19: ...Berhenti daripada menggunakan produk jika berlaku sebarang keganjilan kegagalan dan cabut palam kuasa Risiko asap kebakaran kejutan elektrik Contoh keganjilan kegagalan Produk ini kadang kala tidak b...

Page 20: ...15 C DBT Maklumat untuk Pengguna tentang Pungutan dan Pelupusan Peralatan Lama dan Bateri terpakai Maklumat tentang Pelupusan di Negara lain di luar Kesatuan Eropah Simbol simbol ini hanya sah di Kes...

Page 21: ...an tangan Ram arah aliran udara mendatar Boleh diubah secara manual Penerima Butang kecemasan Jenis K2 PEMASANGAN DINDING Alat Kawalan Jauh Tanpa Wayar Alat pilihan NOTA Rujuk Arahan Operasi yang dile...

Page 22: ...ayunan auto atau arah udara kepada sudut tertentu Untuk butiran lihat seksyen Melaraskan Arah Aliran Udara 5 Butang tetapan suhu Mengubah tetapan suhu Tekan butang tetapan Suhu untuk mengubah tetapan...

Page 23: ...untuk menetapkan ram ram aliran udara menegak kepada kedudukan ke bawah dan kemudian tekan semula butang FLAP Ini memaparkan dan aliran udara secara automatik berayun ke atas dan ke bawah Pemanasan P...

Page 24: ...rgerakan ram dan mahu mengarahkan udara ke arah yang diinginkan tekan semula butang FLAP Dalam mod sejuk jangan arahkan ram ke bawah dan keluar daripada zon penyejukan A jika tidak pemeluwapan akan me...

Page 25: ...netapkan arah aliran udara untuk unit dalaman yang ditunjukkan pada paparan Setiap kali UNIT ditekan penunjuk berubah mengikut turutan di bawah Apabila tiada apa dipaparkan anda boleh membuat tetapan...

Page 26: ...gin sejuk sedang beroperasi Semasa tempoh ini penunjuk siap sedia kekal dipaparkan siap sedia kekal terpapar semasa penyahbekuan atau semasa pemampat dimatikan atau semasa unit beroperasi pada kelajua...

Page 27: ...a di bawah empat teduh jauhkan daripada api atau di cahaya matahari secara terus Gantikan sebarang penapis yang rosak UNIT DALAMAN Lap unit perlahan lahan dengan kain lembut dan kering PANEL DEPAN Ali...

Page 28: ...jalan lancar Kipas kadang kala mungkin berputar disebabkan penukar haba yang mengering disebabkan tetapan Arah angin berubah semasa operasi Tetapan arah angin tidak dapat dibuat Arah angin tidak dapat...

Page 29: ...inggi atau Strong Kuat Jika penyaman udara anda masih tidak berfungsi dengan betul walaupun anda telah memeriksa perkara yang dinyatakan di atas mula mula hentikan operasi dan matikan suis kuasa Kemud...

Page 30: ...____________________ ___________________________ ____________________________________________________________________________ ________________________________________________________________________ _...

Page 31: ...31 1 2 3 5 ON ON...

Page 32: ...32 ELCB ON OFF 1 5...

Page 33: ...33...

Page 34: ...34 DBT WBT LE1 14 C 25 C WBT 10 C 46 C DBT 16 C 30 C DBT 20 C 18 C WBT 20 C 24 C DBT 2WAY ME1 14 C 25 C WBT 10 C 46 C DBT 16 C 30 C DBT 25 C 15 C DBT Pb...

Page 35: ...35 OP EN CL OS E CL OS E OP EN Y2 4 60x60 K2...

Page 36: ...36 3 AUTO STRONG MEDIUM WEAK FAN AUTO 4 5 1 2 1 2 5 3 4 8 2WAY VRF HEAT DRY COOL FAN AUTO COOL HEAT...

Page 37: ...37 Y2 K2 FLAP FLAP FLAP FLAP FLAP...

Page 38: ...38 4 Y2 Y2 K2 FLAP FLAP A A A B...

Page 39: ...39 UNIT UNIT 1 1 1 2 1 3 1 8 1 1 1 2 1 3 2 4 1 4 2 1...

Page 40: ...40 DRY LO 15 C DRY STANDBY 1 2 1 2 3...

Page 41: ...41 pH7 40 C 1 2...

Page 42: ...42 3 30 3...

Page 43: ...43 ON OFF E F H L P...

Page 44: ...tte 60x60 Y2 type Model Name S 22MY2E5A S 28MY2E5A S 36MY2E5A S 45MY2E5A S 56MY2E5A Power Source 220 230 240 V single phase 50 60 Hz Cooling capacity kW 2 2 2 8 3 6 4 5 5 6 BTU h 7 500 9 600 12 300 15...

Page 45: ...2 55 Sound Power level C H dB A 68 70 69 71 70 73 Unit Dimensions H W D mm 1330 940 340 Net weight kg 104 104 104 Mini LE1 type 3 phase Model Name U 4LE1H7 E U 5LE1H7 E U 6LE1H7 E Power Source 300 400...

Page 46: ...930 Net weight kg 234 234 Model Name U 12ME1H8 E U 14ME1H8 E U 16ME1H8 E U 18ME1H8 E U 20ME1H8 E Power Source 380 400 415 V 3 phase 50 Hz Cooling capacity kW 33 5 40 0 45 0 50 0 56 0 BTU h 114 300 13...

Page 47: ...AY ME1 English B Malaysia Model Name Nama Model Power Source Sumber Kuasa Cooling Capacity Kapasiti penyejukan Heating Capacity Kapasiti pemanasan Sound Pressure Level High Medium Low Paras Tekanan Bu...

Page 48: ...Panasonic Corporation 2014 Unauthorized copying and distribution is a violation of law Printed in Malaysia FA0714 10914...

Reviews: