11.1.1 CAPACITY CORRECTION FACTOR CALCULATION METHOD
Calculation of Capacity Equivalent Length:
If the maximum extension equivalent length is over 90m or the main pipe maximum equivalent length is over 60m,
the diameter of the pipe between the outdoor unit and the first branch must be size-up in accordance to below table.
When size-up is applied, please include the Correction Factor for Capacity Equivalent Length calculation.
Pipe diameter between outdoor unit and first branch
Condition
Equivalent
Length
8HP 10HP
Correction
Factor
Outdoor unit to furthest indoor unit
≤
90 m
Total main pipe length
≤
60 m
9.52 mm (3/8”)
-
Outdoor unit to furthest indoor unit
> 90 m
Liquid Pipe
Total main pipe length
> 60 m
12.70 mm (1/2”)
0.5
Outdoor unit to furthest indoor unit
≤
90 m
Total main pipe length
≤
60 m
19.05 mm (3/4”)
22.22 mm (7/8”)
-
Outdoor unit to furthest indoor unit
> 90 m
Gas Pipe
Total main pipe length
> 60 m
22.22 mm (7/8”)
25.40 mm (1”)
0.5
Example
Equivalent Length = 80 m x 0.5 + 15 m = 55 m
According to result of Equivalent Length, retrieve the capacity correction from the corresponding figure.
Equivalent =
Length
Main Pipe
Equivalent Length x
Correction
Factor +
Sub Pipe
Equivalent Length
First branch
Main Pipe Equivalent
Length: 80 m
Sub Pipe Equivalent
Length: 15 m
Summary of Contents for S-22KA1E5S
Page 45: ...45 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5...
Page 47: ...47 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5...
Page 48: ...48 4 3 2 S 100UA1E5 S 125UA1E5...
Page 50: ...50 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5...
Page 51: ...51 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5...
Page 52: ...52 4 5 3 S 100MA1E5 S 125MA1E5...
Page 53: ...53 4 6 Outdoor Unit 4 6 1 U 8EA1E8 U 10EA1E5...
Page 54: ...54 5 Refrigeration Cycle Diagram...
Page 58: ...58 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Page 59: ...59 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Page 60: ...60 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Page 61: ...61 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Page 62: ...62 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Page 63: ...63 7 6 Outdoor Unit EA1E8 Series...
Page 64: ...64 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Page 65: ...65...
Page 66: ...66 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Page 67: ...67...
Page 68: ...68 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Page 69: ...69...
Page 70: ...70 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Page 71: ...71...
Page 72: ...72 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Page 73: ...73...
Page 74: ...74 8 6 Outdoor Unit EA1E8 Series...
Page 75: ...75...
Page 77: ...77 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE...
Page 82: ...82 9 6 2 Inverter PCB CN AC CN RY2 CN RY1 CN FM2 CN COM FG DCN CN FM1 DCP W V U...
Page 231: ...231 19 Operation Range...
Page 233: ...233 21 Outdoor Unit Cooling Heating Capacity and Power Input 21 1 U 8EA1E8...
Page 234: ...234...
Page 235: ...235 21 2 U 10EA1E8...
Page 236: ...236...
Page 302: ...302 27 8 Outdoor Unit U 10EA1E8...