background image

298 

27.6  Low Static Pressure Duct Type – MA1E5 Series 

 

10

20

30

40

50

60

70

80

63

125 250 500 1000 2000 4000 8000

Frequency(Hz)

O

c

tave

B

and

S

o

u

nd

P

re

ss

u

re

L

evel

(d

B

)(

O

d

B

=

0

.0

00

2

μ

b

a

r)

S-45MA1E5(230V)
Octave Band Central Frequency(Hz)

NC-40

NC-50

NC-30

NC-20

H ○━━○

M △━━△

L □━━□

H
M

L

NC-60

50Hz

Frequency

H

40 35

42

M L

39

40
44

46

Fan Speed

Back Ground Noise12dB

C-scale(dB)

A-scale(dB)
C-scale(dB)

10

20

30

40

50

60

70

80

63

125 250 500 1000 2000 4000 8000

Frequency(Hz)

O

c

ta

ve

Ba

nd

S

o

und

Pre

ss

u

re

L

e

ve

l(

d

B

)(

O

d

B

=0

.00

02μba

r)

S-56MA1E5(230V)
Octave Band Central Frequency(Hz)

NC-40

NC-60

NC-50

NC-30

NC-20

H ○━━○

M △━━△

L □━━□

H

M

L

Frequency

50Hz

Fan Speed

C-scale(dB)

Back Ground Noise12dB

H

35

42

M L

39

46

A-scale(dB)

44

40

10

20

30

40

50

60

70

80

63

125 250 500 1000 2000 4000 8000

Frequency(Hz)

O

c

tave

B

and

S

o

u

nd

P

re

ss

u

re

L

evel

(d

B

)(

O

d

B

=

0

.0

00

2

μ

b

a

r)

S-63MA1E5(230V)
Octave Band Central Frequency(Hz)

NC-40

NC-50

NC-30

NC-20

H ○━━○

M △━━△

L □━━□

H

M

L

NC-60

50Hz

Frequency

H

40 36

43

M L

40

41
45

47

Fan Speed

Back Ground Noise12dB

C-scale(dB)

A-scale(dB)
C-scale(dB)

10

20

30

40

50

60

70

80

63

125 250 500 1000 2000 4000 8000

Frequency(Hz)

O

c

ta

ve

Ban

d

S

o

un

d

P

re

ss

ure

L

ev

el

(d

B)(

O

dB=0

.000

2μba

r)

S-71MA1E5(230V)
Octave Band Central Frequency(Hz)

NC-40

NC-60

NC-50

NC-30

NC-20

H ○━━○

M △━━△

L □━━□

H
M

L

Frequency

50Hz

Fan Speed

C-scale(dB)

Back Ground Noise12dB

H

36

43

M L

40

47

A-scale(dB)

45

41

 

 
 
 
 

Summary of Contents for S-22KA1E5S

Page 1: ...E5 S 90MA1E5 S 100MA1E5 S 125MA1E5 Outdoor Unit U 8EA1E8 U 10EA1E8 PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite be assured of no refrigerant leakage during the installation or repairing o...

Page 2: ...5 x 95 Cassette Type Indoor Unit UA1E5 Series 68 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series 70 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series 72 8 6 Outdoor Unit EA1E8 Series 74...

Page 3: ...cal Setting Mode 195 17 3 Wired Remote Control Local Setting Mode 196 17 4 Wireless Remote Control Local Setting Mode 198 17 5 AC Reset Control 199 18 Troubleshooting Guide 200 18 1 Error Code Table 2...

Page 4: ...the installation instruction An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fi...

Page 5: ...ith temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high about 1100 F 600 C 7 Power supply connection to the air conditioner Connect the power...

Page 6: ...Pressure Hide away MA1E5 SERIES O O O O O O O Total freedom of choice Up to 35 different indoor unit models Allows you to choose the best option depending on architectural needs and interior design Wa...

Page 7: ...ver 2 The build in thermistor allows indoor temperature detection in accordance with indoor conditions by switching with indoor unit thermistor 3 Twin non polar wires make installation work easy 10m c...

Page 8: ...high external static pressure mode up to 60Pa by outdoor unit local setting mode Combination table The system attains maximum indoor unit connection capacity of up to 130 in the unit s connection ran...

Page 9: ...tact relay for integration DC24V 2mA wire length max 150m COM shorted with Max rated current LV1 70 LV2 40 LV3 0 Forced Stop o With the Forced Stop input it is possible to override the air conditionin...

Page 10: ...ed unit will in priority to operate heat mode only o Priority mode is indicated in wired remote If remote setting is not same mode with Priority Mode indoor unit will standby until priority mode cance...

Page 11: ...s for two remote controls are identical Last pressed button has priority main or slave is set at remote control Indoor units Remote side remote control Local side remote control Remote side Optional w...

Page 12: ...ax Input Power W 35 37 40 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Material ASG30K1 ASG30K1 ASG30K1 Motor type DC 8 Poles DC 8 Poles DC 8 Poles Input power W Output power W 30 30 30 Cool r p...

Page 13: ...Diameter mm 2 Thermostat Electronic Control Electronic Control Electronic Control Maximum C 32 32 32 Cool Minimum C 21 21 21 Maximum C 27 27 27 Indoor Operation Range Heat Minimum C 16 16 16 1 Coolin...

Page 14: ...ASG30K1 Motor type DC 8 Poles DC 8 Poles Input power W Output power W 30 30 Cool r p m 960 980 Lo Heat r p m 1040 1130 Cool r p m 1090 1120 Me Heat r p m 1170 1240 Cool r p m 1230 1260 Indoor Fan Spee...

Page 15: ...Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb...

Page 16: ...otor type DC 8 Poles DC 8 Poles Input power W Output power W 30 30 Cool r p m 1040 1080 Lo Heat r p m 1160 1200 Cool r p m 1200 1270 Me Heat r p m 1300 1360 Cool r p m 1360 1460 Indoor Fan Speed Hi He...

Page 17: ...ectronic Control Electronic Control Maximum C 32 32 Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bu...

Page 18: ...5 45 40 Type Turbo Fan Turbo Fan Turbo Fan Material ABS GF 10 ABS GF 10 ABS GF 10 Motor type DC 8 Poles DC 8 Poles DC 8 Poles Input power W Output power W 40 40 40 Cool r p m 430 430 440 Lo Heat r p m...

Page 19: ...tronic Control Electronic Control Electronic Control Maximum C 32 32 32 Cool Minimum C 21 21 21 Maximum C 27 27 27 Indoor Operation Range Heat Minimum C 16 16 16 1 Cooling capacities are based on indo...

Page 20: ...ABS GF 10 Motor type DC 8 Poles DC 8 Poles Input power W Output power W 40 40 Cool r p m 450 490 Lo Heat r p m 560 580 Cool r p m 540 580 Me Heat r p m 605 625 Cool r p m 620 660 Indoor Fan Speed Hi H...

Page 21: ...eat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24...

Page 22: ...71 Max Input Power W 110 120 130 121 131 141 121 131 141 Type Turbo Fan Turbo Fan Turbo Fan Material ABS GF 10 ABS GF 10 ABS GF 10 Motor type AC 3 Speeds 6 Poles AC 3 Speeds 6 Poles AC 3 Speeds 6 Pole...

Page 23: ...mm 2 Thermostat Electronic Control Electronic Control Electronic Control Maximum C 32 32 32 Cool Minimum C 21 21 21 Maximum C 27 27 27 Indoor Operation Range Heat Minimum C 16 16 16 1 Cooling capacit...

Page 24: ...1 10 1 16 1 21 Max Input Power W 220 226 231 220 226 231 Type Turbo Fan Turbo Fan Material ABS GF 10 ABS GF 10 Motor type AC 3 Speeds 6 Poles AC 3 Speeds 6 Poles Input power W Output power W 65 65 Coo...

Page 25: ...ntrol Maximum C 32 32 Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet...

Page 26: ...mmAq 0 0 29 3 0 0 29 3 Max Current A 0 39 0 44 0 49 0 44 0 49 0 54 Max Input Power W 77 82 87 83 88 93 Type Sirocco Sirocco Material PP PP Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input pow...

Page 27: ...nimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outd...

Page 28: ...29 3 0 0 29 3 Max Current A 0 44 0 49 0 54 0 44 0 49 0 54 Max Input Power W 88 93 98 88 93 98 Type Sirocco Sirocco Material PP PP Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W Outp...

Page 29: ...nimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outd...

Page 30: ...External Static Pressure Pa mmAq 0 0 29 3 Max Current A 0 50 0 55 0 61 Max Input Power W 99 105 110 Type Sirocco Material PP Motor type AC 4 Speeds 4 Poles Input power W Output power W 40 Cool r p m...

Page 31: ...um C 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 7...

Page 32: ...9 3 0 0 29 3 Max Current A 0 55 0 60 0 65 0 50 0 55 0 60 Max Input Power W 99 104 109 110 115 120 Type Sirocco Sirocco Material PP PP Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W O...

Page 33: ...nimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outd...

Page 34: ...ssure Pa mmAq 49 5 69 7 49 5 69 7 Max Current A 0 80 0 85 0 90 0 80 0 85 0 90 Max Input Power W 180 190 200 180 190 200 Type Sirocco Sirocco Material ABS ABS Motor type AC 4 Speeds 4 Poles AC 4 Speeds...

Page 35: ...Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb a...

Page 36: ...rnal Static Pressure Pa mmAq 49 5 69 7 49 5 69 7 Max Current A 0 80 0 85 0 90 0 80 0 85 0 90 Max Input Power W 180 190 200 180 190 200 Type Sirocco Sirocco Material ABS ABS Motor type AC 4 Speeds 4 Po...

Page 37: ...Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb a...

Page 38: ...tic Pressure Pa mmAq 49 5 69 7 Max Current A 1 10 1 15 1 20 Max Input Power W 245 260 275 Type Sirocco Material ABS Motor type AC 4 Speeds 4 Poles Input power W Output power W 154 Cool r p m 700 730 7...

Page 39: ...m C 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75...

Page 40: ...tic Pressure Pa mmAq 49 5 69 7 49 5 69 7 Max Current A 1 91 1 94 1 97 1 91 1 94 1 97 Max Input Power W 412 430 455 412 430 455 Type Sirocco Sirocco Material ABS ABS Motor type AC 4 Speeds 4 Poles AC 4...

Page 41: ...Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb...

Page 42: ...ting Noise level Power level dB H L 79 80 Cool A 15 0 14 8 14 3 17 5 17 3 16 6 Max Current Heat A 14 5 14 3 13 8 17 0 16 8 16 2 Cool W 9 2k 9 5k 9 5k 10 9k 11 2k 11 1k Max Input Power Heat W 8 9k 9 3k...

Page 43: ...iameter mm 2 Thermostat Electronic Control Electronic Control Protection Device Electronic Control Electronic Control Maximum C 43 43 Cool Minimum C 5 5 Maximum C 24 24 Outdoor Operation Range Heat Mi...

Page 44: ...44 4 Dimensions 4 1 Wall Mounted Type Indoor Unit 4 1 1 S 22KA1E5 S 28KA1E5 S 36KA1E5 S 45KA1E5 S 22KA1E5S S 28KA1E5S S 36KA1E5S S 45KA1E5S...

Page 45: ...45 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5...

Page 46: ...46 4 2 60 x 60 Cassette Type Indoor Unit 4 2 1 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5...

Page 47: ...47 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5...

Page 48: ...48 4 3 2 S 100UA1E5 S 125UA1E5...

Page 49: ...49 4 4 Slim Hide Away Type Indoor Unit 4 4 1 S 22NA1E5 S 28NA1E5 S 32NA1E5 S 36NA1E5 S 45NA1E5 S 56NA1E5...

Page 50: ...50 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5...

Page 51: ...51 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5...

Page 52: ...52 4 5 3 S 100MA1E5 S 125MA1E5...

Page 53: ...53 4 6 Outdoor Unit 4 6 1 U 8EA1E8 U 10EA1E5...

Page 54: ...54 5 Refrigeration Cycle Diagram...

Page 55: ...ted Type Indoor Unit KA1E5 Series ZNR100 FUSE100 L N U1 U2 AC220V 240V 50Hz SC M URBAN NET ZNR101 ZNR102 6 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ZNR1 SSR1 L N U1 U2 AC220 230 240V 50Hz SC M...

Page 56: ...SSR1 RY H RY M RY L L N U1 U2 SC M 1 M 1 ZNR1 CR1 CR2 CR3 ZNR2 ZNR3 FUSE101 AC220 230 240V 50Hz URBAN NET 6 4 Slim Hide Away Type Indoor Unit NA1E5 Series RY H RY M RY L L N U1 U2 SC M 1 ZNR1 CR1 CR2...

Page 57: ...57 6 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series RY H RY M RY L L N U1 U2 SC M 1 ZR1 CR1 CR2 CR3 ZR2 ZR3 FUSE101 AC220 230 240V 50Hz URBAN NET 6 6 Outdoor Unit EA1E8 Series...

Page 58: ...58 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series...

Page 59: ...59 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...

Page 60: ...60 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...

Page 61: ...61 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series...

Page 62: ...62 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...

Page 63: ...63 7 6 Outdoor Unit EA1E8 Series...

Page 64: ...64 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series...

Page 65: ...65...

Page 66: ...66 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...

Page 67: ...67...

Page 68: ...68 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...

Page 69: ...69...

Page 70: ...70 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series...

Page 71: ...71...

Page 72: ...72 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...

Page 73: ...73...

Page 74: ...74 8 6 Outdoor Unit EA1E8 Series...

Page 75: ...75...

Page 76: ...76 9 Printed Circuit Board 9 1 Wall Mounted Type Indoor Unit KA1E5 Series 9 1 1 Main PCB 9 1 2 Power PCB CN FM CN DCV...

Page 77: ...77 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE...

Page 78: ...78 9 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series 9 2 1 Main PCB CN FM CN STM2 CN EV LED CN DISP CN OPT3 CN UN CN TIMER CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS JEM A CN STM1...

Page 79: ...STM1 CN STM2 CN EV CN DISP CN OPT3 CN UN CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS CN TIMER 9 4 Slim Hide Away Type Indoor Unit NA1E5 Series 9 4 1 Main PCB CN STM1 CN STM2 CN EV CN DISP CN...

Page 80: ...80 9 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series 9 5 1 Main PCB CN STM1 CN STM2 CN EV CN DISP CN OPT3 CN UN CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS CN TIMER...

Page 81: ...CN UN CN OPT2 CN OPT3 CN EV1 CN EV2 CN EV3 CN TH1 CN TH4 CN TH3 CN TH2 CN AC2 CN COM HUNDRED TEN ONE OUTDOOR ADDRESS COMMUNICATION BUS POWER SUPPLY SWITCH CN SUB1 COOLING ONLY JUMPER ADDRESS RESET BU...

Page 82: ...82 9 6 2 Inverter PCB CN AC CN RY2 CN RY1 CN FM2 CN COM FG DCN CN FM1 DCP W V U...

Page 83: ...83 9 6 3 Noise Filter PCB L1 IN CN AC L2 IN L3 IN N IN FG 1 FG 2 CN SUB1 L1 OUT L2 OUT L3 OUT 9 6 4 Capacitor PCB RAT2 DCP W V U DCN RAT1...

Page 84: ...tion mode of AUTO HEAT FAN COOL or DRY TEMP UP DOWN button Use to select the desired temperature AIR SWING AUTO MANUAL button Not applicable for Hide Away models FILTER RESET button Press to reset the...

Page 85: ...ton System reset SET button Local setting function ADDRESS button Use to change the address setting of indoor unit RC RESET button Use to clear the remote control setting from memory TIMER CLOCK SET b...

Page 86: ...ng pipe length is shown in the figure below 1 In Local Setting Mode when equivalent pipe length setting is 101 60 m to 90 m 2 In Local Setting Mode when equivalent pipe length setting is 102 90 m to 1...

Page 87: ...rection Factor Outdoor unit to furthest indoor unit 90 m Total main pipe length 60 m 9 52 mm 3 8 Outdoor unit to furthest indoor unit 90 m Liquid Pipe Total main pipe length 60 m 12 70 mm 1 2 0 5 Outd...

Page 88: ...nit 16 unit 1 Use the above table to combine the number of indoor units with the appropriate capacity which matches the outdoor unit s cooling capacity rating Set the combined number of units to compl...

Page 89: ...will cause toxic gases to be generated Improper fixing of screw may cause leakage current and electrical shock Must not use other parts except original optional parts described in catalog and manual O...

Page 90: ...gas leaks A location that provides space for installation and service A location that allows the pipe and cable length fixture for internal and external connections 2 If installing at locations prone...

Page 91: ...l A Wall C no limit Wall D 1500 mm CAUTION When Wall B and Wall D exceeds the height limits as mentioned additional gap is required as shown in figure below Maximum wall height when top opened with 2...

Page 92: ...pass the fork of the forklift through the forklift holes on the lower portion of the unit 11 2 5 INSTALLATION OF THE OUTDOOR UNIT 1 In order to prevent damage of outside unit due to earthquake typhoo...

Page 93: ...rial C1220T 0 C1220T 1 2H For 19 05 if a thickness of greater than 2mm use of C1220T 0 is possible For 8HP CU 8EA gas suction side panel use 19 05 When connecting utilize included sockets when assembl...

Page 94: ...ss than 40 m LB LC LD LE LF La Allowable piping length Maximum indoor unit connection pipe length 3 Actual length Less than 30 m Less than 30 m La Lb Lc Ld Le Lf Lg Lh Lj L branch pipe inside maximum...

Page 95: ...st branch must be ranked up in accordance with the below table 3 The maximum length of the indoor unit connection pipe depends on the indoor unit capacity Please refer to the table below Indoor unit c...

Page 96: ...t area for anti rust protection Close the gap at the pipe connected area with putty or heat insulator locally supplied o If an insect or small animal enters the outdoor unit there is the risk of short...

Page 97: ...e following steps Step 1 Make sure that the closing valve is closed Step 2 Connect the charge hose to the service port to release gas in the sealing pipe if any Step 3 Cut off the sealing pipe at its...

Page 98: ...g to the instruction manual Furthermore ask the customer to keep this installation instructions and the instruction manual in a safe place for later reference Warning Ask the vendor or a qualified tec...

Page 99: ...cable to H05RN F or H07RN F which conforms to CENELEC HAR rating specifications or use the cables based on IEC standard 245IEC57 245IEC66 Diameter 0 5 mm2 The maximum wire cable length is 150 meters A...

Page 100: ...section on the terminal module Terminal module with optional connection on the outdoor unit s control panel To the next system outdoor unit Cooling Heating Selector Forced Stop Demand 1 Brown cord Co...

Page 101: ...e unit 6 Install the case Re install the case that was removed by securing it with the screws 7 Install the decorative panel Install the decorative panel by clipping it in There is a specific directio...

Page 102: ...ng 3 the wired remote control indicates priority to the fan operation 3 Choose either the cooling operation or the heating operation Choose SW 5 or 6 Choose 5 for the cooling operation and choose 6 fo...

Page 103: ...ant allowable pipe lengths and allowable elevation difference refer to the installation instructions provided with the indoor unit The diameter of the piping for the indoor and outdoor units differs d...

Page 104: ...15 11 4 2 3 Precautions at connecting points After removing any impurities at the mouth of the pipe or the connecting points be sure to clean the inside of the pipe with nitrogen gas nitrogen displac...

Page 105: ...side of the branch pipe 2 Wrap tape all around the areas where the insulating materials are joined in order to seal it Tape Local supply Thermal insulator Accessory Insulating material for refrigerant...

Page 106: ...e parts supplied in the header pipe set The content shows as shown in the table below Content Content Part No 1 Header pipe to gas side Part No 7 Reducer attached to P4HP2C2 Part No 2 Header pipe to l...

Page 107: ...t is not necessary to cut off the pipe if it is identical to the tip of the size NOTE Do not forcibly cut off the pipe to escape deformation If doing so connection pipe cannot be inserted When selecti...

Page 108: ...plied insulator for the insulation of the branch pipe When using other than that be sure to insulate it to tolerate the temperature of more than 120 C For the details refer to Installation Instruction...

Page 109: ...an bears the weight of this unit sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon...

Page 110: ...may still occur even if the separation distance is more than 1 meter 11 6 1 ACCESSORIES PACKED IN THE INDOOR UNIT CONTAINER Name Q ty Appearance Purpose Plate 1 Screw 5 Installation plate fixing scre...

Page 111: ...generated 5 Avoid places near high frequency generators 11 6 3 INSTALLATION OF INDOOR UNIT HOW TO FIX INSTALLATION PLATE The mounting wall shall be strong and solid enough to prevent it from the vibra...

Page 112: ...sert the piping sleeve to the hole 2 Fix the bushing to the sleeve 3 Cut the sleeve until it extrudes about 15 mm from the wall When the wall is hollow please be sure to use the sleeve for tube assemb...

Page 113: ...unit Right and Right Bottom piping Cover for the bottom piping Tape it with piping in a position as mentioned in Fig below Cover for the right piping Piping Drain hose Right Rear piping Cover for the...

Page 114: ...idized scale in copper pipe 2 When there is a lot of brazings for long piping install a strainer midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface f...

Page 115: ...itch board designed for this purpose the switch should disconnected all poles with a contact separation of at least 3 mm 3 Always ground the air conditioner with a grounding wire and screw to meet the...

Page 116: ...ake up to 1 minute once power is supplied do not operate the remote control during this time Once the wires are connected to 1 Remote Control group control and power is supplied to the indoor unit the...

Page 117: ...eceiving sound can be change over by the following steps a Press AUTO switch continuously for more than 26 sec to below 31 sec A pep pep pep pep pep pep sound will occur at the twenty sixth sec b Pres...

Page 118: ...ient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead...

Page 119: ...ning the heat insulator Flat washer for M10 8 For fixing the hanging bolts Screw M5 4 Set screw for paper model and panel fixing Installation Instruction 1 This manual 11 7 2 SELECTING THE LOCATION FO...

Page 120: ...ecially in factories etc 3 Avoid places where inflammable gas is generated flows in contaminated or leaked 4 Avoid places where sulphurous acid gas or corrosive gas can be generated 5 Avoid places nea...

Page 121: ...midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface free from mist and dust Blow nitrogen gas or air to blow off dust in the pipe before connection 4...

Page 122: ...leave it provisionally until the test comes to an end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain up motor for normal operating and noise when ele...

Page 123: ...rom a dedicated electrical circuit All electric work must be carried out by a qualified technician according to proper technical standards for electrical work and according to installation instruction...

Page 124: ...pply cables 1 Length m Leakage current breaker A Switch A Fuse A 2 Control Cable Remote Controller Cable Indoor unit 220V 240V 2 mm 2 100 15A 15A 15A 0 75 mm 2 0 5 2 mm 2 1 The maximum length shows a...

Page 125: ...cient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead...

Page 126: ...insulating refrigerant pipe joint Band 4 For fastening the heat insulator Flat washer for M10 8 For fixing the hanging bolts Screw M5 4 Set screw for paper model and panel fixing Installation Instruct...

Page 127: ...xist especially in factories etc 3 Avoid places where inflammable gas is generated flows in contaminated or leaked 4 Avoid places where sulphurous acid gas or corrosive gas can be generated 5 Avoid pl...

Page 128: ...piping install a strainer midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface free from mist and dust Blow nitrogen gas or air to blow off dust in the...

Page 129: ...leave it provisionally until the test comes to an end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain up motor for normal operating and noise when ele...

Page 130: ...rom a dedicated electrical circuit All electric work must be carried out by a qualified technician according to proper technical standards for electrical work and according to installation instruction...

Page 131: ...Power supply cable Circuit breaker Minimum capacity Model name Power supply Minimum power cable supply cables 1 Length m Leakage current breaker A Switch A Fuse A 2 Control Cable Remote Controller Ca...

Page 132: ...hod However if the wall type indoor unit is connected then manual setting is not possible Automatic setting By switching ON the indoor unit s power supply with the DIP switch where the A C No is set t...

Page 133: ...pieces of the decorative panel to the indoor unit There is direction information at decorative panel PIPING SIDE indication meaning the direction of piping side 4 Adjust between decorative panel fixin...

Page 134: ...ween control board and control board cover 9 After complete install back removed part follow opposite procedure Warning Be sure to hook the air inlet grill string to prevent grill from falling and cau...

Page 135: ...m fluorescent lights Refer to the illustration below If using an inverter type fluorescent light keep the receiver at least 1 meter away from the light otherwise the remote control operation may not w...

Page 136: ...does not stick out 2 Remove the control box cover by removing the two screws and connect joint cord for wiring to the P C B connector CN DISP in the control box Note When securing the decorative pane...

Page 137: ...n Again press the AUTO switch for 5 seconds or more it will beep twice to start the heating operation The setting of the fan speed and louver control will be fixed as shown by the table below While th...

Page 138: ...it sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in ins...

Page 139: ...at insulator 2 For insulating refrigerant pipe joint Band 4 For fastening the heat insulator Flat washer for M10 8 For fixing the hanging bolts Installation Instruction 1 This manual 11 10 2 SELECTING...

Page 140: ...llection hood with suf cient capacity Unit mm 2 Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially in factories etc 3 Avoid places where...

Page 141: ...outing Avoid bending and bending back the same piping point more than three times This will result in hardening of the pipe 5 After deforming the pipe align centers of the union fitting of the indoor...

Page 142: ...may be required to take off this part for checking or servicing the drain up motor Please do not glue Make sure that there is no clearance here 2 Precautions in high humidity circumstance This air co...

Page 143: ...fer to the terminal connection section Imperfect connection and fixing leads to fire etc 1 Select a power source that is capable of supplying the current required by the air conditioner 2 Feed the pow...

Page 144: ...n the event that 1 remote control group control is not used do not set up the group control address A C No The wired remote control will not display when the settings for the A C No are set to a value...

Page 145: ...e manual setting is performed using each indoor unit s printed circuit board DIP switch Refer to the diagram below Set the DIP switch once the power supply for each indoor unit is switched OFF When th...

Page 146: ...s to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead to accidents arise...

Page 147: ...erant pipe 2 2 Hose clip for thermal insulator 5 3 M10 Flat waher 8 4 Thermal insulator for drainage hole 1 5 Duct flange R 1 6 Duct flange L 1 7 Screws 4 8 Flexible pipe 1 5 and 6 should be installed...

Page 148: ...o install the air conditioner in such place where it may not suck in oily steam Air conditioner Cooking table Ensure ample distance 2 Avoid installing the air conditioner in such circumstances where c...

Page 149: ...l charging etc 1 Brazing for piping a Execute brazing before tightening the flare nut b Brazing must be executed while blowing nitrogen gas This prevents generation of oxidized scale in copper pipe 2...

Page 150: ...or unit Band Accessory Heat insulator for piping Local supply Heat insulator Accessory Hose clip Accessory Heat insulator Local supply The thickness must be at least 8 mm Flexible hose with heat insul...

Page 151: ...cks may result Warning Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not transfer to the terminal connection section Imperfec...

Page 152: ...ontrol and power is supplied to the indoor unit the A C No is automatically set To stop group control use follow the directions below and clear the A C No that was automatically set after disconnectin...

Page 153: ...called To change the setting of the A C No turn OFF the power supply before resetting the DIP switch Ensure that there is no redundancy in the A C No Any redundancy can cause faulty control Ensure to...

Page 154: ...tion below If using an inverter type fluorescent light keep the receiver at least 1 meter away from the light otherwise the remote control operation may not work properly Fluorescent light 300 mm or m...

Page 155: ...box cover Control cable Control box Screw Remove the control box cover by removing the screws and connect the joint cord for wiring to the P C B connector CN DISP in the control box Connect joint cor...

Page 156: ...ooling operation Again press the AUTO switch for 5 seconds or more it will beep twice to start the heating operation The setting of the fan speed and louver control will be fixed as shown by the table...

Page 157: ...oor units at a maximum range of 8 meters from directly in front of the indoor unit If the remote control is at an angle to the receptor unit the operating range may become shortened If using a single...

Page 158: ...ting switch with a ballpoint pen or similar object to change the address setting as shown in the illustration to the right The address number displayed on the LCD changes in the order ADDRESS 1 ADDRES...

Page 159: ...block Terminal block Infrared receiver LOCAL SETTING Press the SET switch 2 to operate the Local setting mode Use the switches TEMP to choose the Mode No Use the switches TIMER to choose the Setting v...

Page 160: ...or 003 for the Setting value Press the SELECT switch and use the switches TIMER to set the night time low noise end time Press the SET switch 1 to confirm After the end time is set the display proceed...

Page 161: ...REMOTE CONTROL SET UP LOCATION Select a place where the remote control can be operated easily after obtaining approval from the customer Install in a place which is away from direct sunlight and as fr...

Page 162: ...unit and the remote control as shown in the illustration below The remote control cable is non polar At the time of shipment from the factory the connector cable used to connect the terminal block an...

Page 163: ...te control cable exposed use nippers to cut a notch into the upper case The feeding out direction can be either up or to the left or right Strip the end of the remote control cable which is to be conn...

Page 164: ...sh the upper case until it snaps shut onto the lower case tab while being careful not to clamp the remote control cable and the connector cord Upper case Lower case If remote control cable is embedded...

Page 165: ...thermistor Connect the remote controls Connect both remote controls to terminals and on the indoor unit terminal block non polar Indoor unit Terminal block GROUP CONTROL Up to a maximum of 16 indoor u...

Page 166: ...it address 5 Once the indoor unit address is fixed with the SET switch and it will return to the check display screen for the indoor unit address It is possible to choose a different air conditioner N...

Page 167: ...door units can be connected at the time of group control Do not connect the heat pump unit with the cooling only unit There are 2 methods for setting the group control address A C No an automatic and...

Page 168: ...e the CHECK switch is pressed Further details of the problem can be displayed by pressing the SET switch while the general problem details are being displayed Example of current problem display Press...

Page 169: ...ils of the problem can be displayed by pressing the SET switch Problem details Problem display The display can be switched between the previous problem and the one before that by pressing the UP DOWN...

Page 170: ...170 12 Testing and Commissioning 12 1 OUTDOOR UNIT 12 1 1 PRECAUTIONS REGARDING TEST RUN The process flow shows the start of the test run...

Page 171: ...rent is running can cause damage to the control board Once the power supply is turned OFF be sure to wait 5 minutes or more before starting to work on it Follow the indoor and outdoor units instructio...

Page 172: ...set on shipping When Enter button is pressed the third column right of 7 SEG display is displayed and local setting is done When Select and Enter buttons are pressed simultaneously over 5 seconds 7 S...

Page 173: ...EG light off 12 1 3 CHECKS AFTER INSTALLATION HAVE COMPLETED Check the following items after completing installation 12 1 4 REGARDING DELIVERY TO THE CUSTOMER Request the customer to review the instru...

Page 174: ...ntrol will change to normal operation after 30 minutes NOTE 5 Use the outdoor unit to cancel the outdoor unit test run and the wired remote control to cancel the wired remote control test run For the...

Page 175: ...s after completion of deice control 13 2 Outdoor Expansion Valve Control Expansion Valve is a VDC12 solenoid valve that controls the amount of refrigerant flow Operation Power Up Comp Start Up Normal...

Page 176: ...le after accumulation time for heating Compressor ON under low outdoor ambient environment as stated in table below Outdoor Air Temperature C Heat exchanger temperature C Acc Time minutes 5 to 7 75 3...

Page 177: ...ontrol is used to prevent condensation of refrigerant inside compressor and keep the temperature of compressor oil at the suitable level Crank case heater will ON if below conditions are all fulfilled...

Page 178: ...conditions happened o During Cool Mode Outdoor heat exchanger temp 58 C for 10 seconds o During Heat Mode Outdoor heat exchanger temp 30 C when outdoor ambient 5 C Outdoor heat exchanger temp 35 C whe...

Page 179: ...l compressor cannot restart and gas bypass valve is ON 14 7 Outdoor Residual Heat Removal Control When compressor OFF outdoor fan operate for 1 minute to remove the remaining heat 14 8 Compressor Stop...

Page 180: ...60 x 60 Cassette YA1 series 95 x 95 Cassette UA1 series Slim Hide away NA1 series 4 5 5 6kW 6 3 7 1 9 0 kW Indoor fan speed Me 2 0 C 2 0 C 1 5 C 2 0 C 1 0 C 2 0 C Thermostat OFF Point D COOL Mode Ind...

Page 181: ...dry Softdry thermostat OFF point Thermostat OFF continues for 3 minutes if the Intake Air Temperature Internal Setting Temperature Thermostat OFF point The Thermostat OFF point can be altering using R...

Page 182: ...setting Figure 15 Heating thermostat OFF characteristic Thermostat OFF continues for 3 minutes if the Intake Air Temperature Internal Setting Temperature Thermostat OFF point 1 0 C The Thermostat OFF...

Page 183: ...Cool Mode to Heat Mode 15 6 Indoor Fan Motor Operation Type of indoor fan motor are shown in below table Wall Mounted Type KA1E5 Series 60 x 60 Cassette Type MA1E5 Series DC Fan Motor 95 x 95 Cassette...

Page 184: ...indoor heat exchanger temperature and air swing setting Automatic air swing Manual air swing Stop Reduced Min Me 57oC 55oC for cassette 53oC 34oC 29oC 26oC 33oC Remote control setting Stop Min Me 39oC...

Page 185: ...ng during thermostat OFF compressor ON and temperature between indoor intake temperature and setting temperature is below 30 C Thermostat ON Sampling signal from outdoor unit Indoor fan Compressor ON...

Page 186: ...een indoor intake temperature and setting temperature is above 30 C Thermostat ON Sampling signal from outdoor unit Indoor fan Compressor ON OFF OFF ON Remote controller fan speed setting DC fan motor...

Page 187: ...eat removal control 144 Heat Thermostat OFF 20 32 50 68 20 Normal 20 26 32 45 20 45 Dew control 26 26 32 45 26 45 Cool Fan Thermostat OFF 20 26 32 45 20 45 Normal 20 26 32 45 20 45 Dew control 26 26 3...

Page 188: ...p 0 Air swing direction setting Automatic Mode Condition Zone A 70 70 70 Zone B 20 70 20 53 42 70 Indoor heat exchanger temperature Zone C 20 20 20 Deice 10 Hot start 10 Heat removal control 20 Heat T...

Page 189: ...on stop 0 Air swing direction setting Automatic Mode Condition Zone A 70 70 70 Zone B 20 70 20 50 40 70 Indoor heat exchanger temperature Zone C 20 20 20 Deice 10 Hot start 10 Heat removal control 20...

Page 190: ...SLo SSLo OFF SSLo OFF SSLo SLo SSLo OFF Softdry Auto SSLo OFF SSLo OFF SSLo Auto SSLo OFF Cool Thermostat Compressor Indoor fan ON OFF 40 sec 50 sec 20 sec 120 sec 20 sec 40 sec 50 sec Thermostat Comp...

Page 191: ...Control This control activates to increase the output capacity when the indoor unit ON and the temperature difference between indoor intake temperature and remote control setting temperature is more t...

Page 192: ...o Indoor fan speed is Lo or AUTO Indoor fan speed changed from SLo to Lo and air swing angle follows dew prevention angle When received dew prevention signal from indoor unit compressor frequency red...

Page 193: ...Dry or OFF o Indoor Thermostat ON before Heat mode changes During this control o DC motor fan speed is fixed at Lo and airflow direction is fixed o AC motor fan speed is fixed at Lo and airflow direc...

Page 194: ...ptor s AUTO switch for more than 5s till one beep is heard Force Heating Mode 1 Press and hold the receptor s AUTO switch for more than 8s till two beeps is heard 2 Press AC RESET button on the wirele...

Page 195: ...ight Test OFF ON Standby 21 Refrigeration Collection OFF ON Standby 22 Vacuuming OFF ON Standby 23 Defrost operation OFF ON HEAT Mode 24 Pump Down OFF ON Prohibited after installation 2 CCL RESET 17 2...

Page 196: ...0 Default control 001 10 seconds fan sampling operation 03 Thermostat OFF indoor fan control 002 Fixed fan speed operation I 000 default Thermostat OFF point D 001 Cool D 2 C Heat D 2 C 002 Cool D 4 C...

Page 197: ...Night Time Low Noise ON and OFF timer by pressing Timer SET button o Press TEST RUN button to exit LOCAL SETTING MODE 17 3 3 Thermostat OFF Indoor Fan Control During thermostat OFF and compressor OFF...

Page 198: ...4 C 000 Clear address 06 Outdoor unit address 001 199 Address 1 Address 199 Note 1 Mark in the column of the Individual setting shows a setting item individually made for each connected indoor unit N...

Page 199: ...Motor Speed Lo DC Fan Motor Speed Lo 17 4 3 Thermostat OFF Point Adjustment The default thermostat OFF point might not be accurate depends on indoor unit installation condition thermostat OFF point a...

Page 200: ...B Outdoor unit main PCB Inverter PCB F35 02 Outdoor DC fan motor error Outdoor unit Inverter PCB Outdoor DC fan motor outdoor unit Inverter PCB connectors CN FM1 CN FM2 F40 01 Outdoor temperature sens...

Page 201: ...indoor unit main PCB connector CN TH1 F22 01 Indoor gas pipe temperature sensor error Indoor gas pipe temperature sensor lead wire indoor unit main PCB connector CN TH1 F25 01 Indoor address double re...

Page 202: ...sion Conditions During operation of cooling and heating the signal received from drain level float switch in indoor unit is checked whether it is normal Malfunction Caused Faulty connector connection...

Page 203: ...rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operation stops due to breaking of fan mo...

Page 204: ...ooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty indoor...

Page 205: ...ng and heating the temperatures detected by the wired remote control thermistor are used to determine sensor errors Malfunction Caused Faulty wired remote controller Faulty indoor unit PCB main Abnorm...

Page 206: ...g startup and operation of cooling and heating the temperatures detected by the indoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty...

Page 207: ...g startup and operation of cooling and heating the temperatures detected by the indoor gas temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty...

Page 208: ...1 Malfunction Decision Conditions During standby startup and operation of cooling and heating the indoor unit detects the same address as that of its own Malfunction Caused Wrong indoor unit address s...

Page 209: ...ring standby startup and operation of cooling and heating normal transmission between remote control and indoor unit does not continue for 3 minutes Malfunction Caused Faulty connector connection Impr...

Page 210: ...outdoor unit is checked whether it is normal Malfunction Caused Indoor outdoor power supply is OFF Indoor outdoor signal transmission error due to breaking of U1 U2 Indoor outdoor signal transmission...

Page 211: ...e used to determine abnormal system connectivity Malfunction Caused No power supply to indoor unit Wrong total number max min of connected indoor unit Wrong total capacity max min of connected indoor...

Page 212: ...on Caused Clogged air filter of indoor unit Dust accumulation on the indoor outdoor unit heat exchanger Air short circuit at indoor outdoor unit 3 way valve closed Faulty outdoor unit fan motor Refrig...

Page 213: ...nction Caused Clogged air filter of indoor unit Dust accumulation on the indoor outdoor unit heat exchanger Air short circuit at indoor outdoor unit 3 way valve closed Faulty outdoor unit fan motor Ex...

Page 214: ...perature of thermostat ON indoor unit 5 C During cooling operation when the indoor pipe temperature of thermostat ON indoor unit 45 C Malfunction Caused Faulty sensor Faulty connector connection Fault...

Page 215: ...ooling and when outdoor unit receive indoor unit freezing abnormal signal indoor pipe temperature 0 C from thermostat OFF standby indoor unit Malfunction Caused Faulty sensor Faulty indoor unit expans...

Page 216: ...eration of cooling and heating when IPM temperature data 95 C is detected by the IPM temperature sensor Malfunction Caused Air short circuit at outdoor unit Faulty outdoor unit fan motor Faulty outdoo...

Page 217: ...ons During operation of cooling and heating when an input over current is detected by the current transformer CT in the outdoor unit PCB Malfunction Caused Excess refrigerant Faulty outdoor unit PCB m...

Page 218: ...temperature data 110 C is detected by the compressor discharge temperature sensor Malfunction Caused Faulty compressor discharge temperature sensor 3 way valve closed Refrigerant shortage refrigerant...

Page 219: ...verter DC Peak sensing circuitry in the outdoor unit PCB inverter Malfunction Caused Faulty outdoor unit PCB inverter Faulty compressor Abnormality Judgment Continue for 7 times within 30 minutes DC p...

Page 220: ...ilure is detected by checking the compressor running condition through the position detection circuitry in the outdoor unit PCB nverter Malfunction Caused Compressor terminal disconnect Faulty outdoor...

Page 221: ...or feedback of rotation 2550rpm or 20rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operation sto...

Page 222: ...ng startup and operation of cooling and heating the temperatures detected by the outdoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connectio...

Page 223: ...ng startup and operation of cooling and heating the temperatures detected by the compressor suction temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connectio...

Page 224: ...g startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Fault...

Page 225: ...ng startup and operation of cooling and heating the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection F...

Page 226: ...ng startup and operation of cooling and heating the temperatures detected by the compressor discharge temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connect...

Page 227: ...ty F41 02 Malfunction Decision Conditions During compressor stop when the outdoor unit high pressure switch is open for 1 minute Malfunction Caused Faulty connector connection Faulty outdoor unit high...

Page 228: ...ditions A current transformer CT open circuit is detected by checking the compressor running frequency 50Hz and CT detected input current 1 6A for continuously 60 seconds Malfunction Caused CT defecti...

Page 229: ...cision Conditions During startup and operation of cooling and heating the temperatures detected by the IPM temperature sensor are used to determine sensor errors Malfunction Caused Faulty indoor unit...

Page 230: ...onditions During standby startup and operation of cooling and heating the outdoor unit detects the same address as that of its own on any other outdoor unit of same urban network Malfunction Caused Wr...

Page 231: ...231 19 Operation Range...

Page 232: ...0 301 2 651 Suction Saturation temp C 26 2 43 82 1 Outdoor temp Lower limit 20 C Heating mode off 2 Outdoor temp Upper limit 43 C Cooling mode off Cooling Low Pressure 0 80 0 85 0 90 0 95 1 00 5 0 5 1...

Page 233: ...233 21 Outdoor Unit Cooling Heating Capacity and Power Input 21 1 U 8EA1E8...

Page 234: ...234...

Page 235: ...235 21 2 U 10EA1E8...

Page 236: ...236...

Page 237: ...rated cooling capacity 5 6kW Cooling capacity 22 4kW 5 53kW Total indoor rated cooling capacity 22 7kW Indoor Unit Cooling Capacity kW Indoor unit 0 8HP 1 0HP 1 25HP 1 5HP 1 65HP 1 75HP 2 0HP 2 5HP 3...

Page 238: ...8HP 1 0HP 1 25HP 1 5HP 1 65HP 1 75HP 2 0HP 2 5HP 3 0HP 3 5HP 4 0HP 5 0HP Cooling capacity 2 5kW 3 2kW 3 6kW 4 2kW 4 5kW 5 1kW 6 4kW 7 1kW 8 0kW 10 0kW 11 2kW 14 0kW Wall mounted Mini cassette Big cas...

Page 239: ...5 6 99 40 19 70 5 74 21 52 6 30 23 35 6 87 24 38 7 08 25 41 7 30 43 19 70 6 33 20 79 6 68 21 89 7 03 22 98 7 26 24 08 7 49 Combination 120 Capacity index kW 26 9 TC Total Capacity kW PI Power Input kW...

Page 240: ...6 42 25 34 6 62 40 18 66 5 43 20 39 5 97 22 12 6 51 23 10 6 71 24 08 6 91 43 18 66 6 00 19 70 6 33 20 74 6 66 21 77 6 88 22 81 7 10 Combination 100 Capacity index kW 22 4 TC Total Capacity kW PI Power...

Page 241: ...17 81 5 16 19 44 5 64 20 51 5 89 21 58 6 15 43 16 18 5 17 17 27 5 52 18 37 5 86 19 48 6 14 20 60 6 42 Combination 80 Capacity index kW 17 9 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Te...

Page 242: ...47 13 78 3 87 15 32 4 27 16 63 4 64 17 93 5 00 43 12 24 3 87 13 51 4 24 14 78 4 62 16 11 5 03 17 44 5 45 Combination 60 Capacity index kW 13 4 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air...

Page 243: ...07 5 7 4 1 48 8 7 1 61 10 0 1 74 11 5 1 91 12 9 2 07 10 7 4 1 50 8 7 1 62 10 0 1 74 11 5 1 91 12 9 2 07 15 7 4 1 50 8 7 1 63 10 0 1 75 11 5 1 92 12 9 2 09 20 8 3 1 69 9 8 1 84 11 2 1 99 12 7 2 16 14 3...

Page 244: ...7 88 26 90 8 65 29 18 9 43 30 48 9 72 31 77 10 02 43 24 62 8 69 25 99 9 17 27 36 9 66 28 73 9 97 30 10 10 29 Combination 120 Capacity index kW 33 6 TC Total Capacity kW PI Power Input kW Outdoor Indo...

Page 245: ...8 82 31 68 9 09 40 23 33 7 46 25 49 8 20 27 65 8 93 28 87 9 21 30 10 9 49 43 23 33 8 23 24 62 8 69 25 92 9 15 27 22 9 45 28 51 9 75 Combination 100 Capacity index kW 28 0 TC Total Capacity kW PI Power...

Page 246: ...22 26 7 07 24 30 7 76 25 64 8 11 26 98 8 47 43 20 22 7 03 21 59 7 51 22 96 8 00 24 35 8 38 25 75 8 75 Combination 80 Capacity index kW 22 4 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Te...

Page 247: ...17 22 5 27 19 15 5 90 20 78 6 43 22 41 6 95 43 15 30 5 08 16 89 5 65 18 48 6 21 20 14 6 76 21 80 7 31 Combination 60 Capacity index kW 16 8 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Te...

Page 248: ...3 1 69 10 9 1 88 12 5 2 08 14 3 2 30 16 1 2 51 10 9 3 1 69 10 9 1 89 12 5 2 09 14 3 2 32 16 1 2 54 15 9 3 1 71 10 9 1 92 12 5 2 12 14 3 2 34 16 1 2 56 20 9 3 1 73 10 9 1 95 12 5 2 17 14 3 2 38 16 1 2...

Page 249: ...3 5 09 10 29 87 6 67 27 81 6 15 25 75 5 62 23 69 5 21 21 63 4 80 15 29 87 6 45 27 81 5 85 25 75 5 26 23 69 4 84 21 63 4 43 Combination 120 Capacity index kW 30 0 TC Total Capacity kW PI Power Input kW...

Page 250: ...62 21 21 5 19 10 29 29 6 81 27 27 6 27 25 25 5 74 23 23 5 32 21 21 4 89 15 29 29 6 58 27 27 5 97 25 25 5 37 23 23 4 94 21 21 4 52 Combination 100 Capacity index kW 25 0 TC Total Capacity kW PI Power I...

Page 251: ...24 26 5 61 22 50 5 16 20 74 4 79 18 98 4 43 15 26 03 5 86 24 26 5 35 22 50 4 84 20 74 4 48 18 98 4 12 Combination 80 Capacity index kW 20 0 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Te...

Page 252: ...18 78 4 15 17 50 3 88 16 22 3 64 14 93 3 42 15 20 10 4 27 18 78 3 97 17 50 3 67 16 22 3 44 14 93 3 22 Combination 60 Capacity index kW 15 0 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air T...

Page 253: ...89 3 20 10 14 17 3 69 13 31 3 54 12 50 3 36 11 69 3 20 10 89 3 03 5 14 17 3 40 13 31 3 27 12 50 3 12 11 69 2 98 10 89 2 83 1 14 17 3 25 13 31 3 11 12 50 2 96 11 69 2 83 10 89 2 70 0 14 17 3 16 13 31 3...

Page 254: ...64 8 60 35 04 7 92 32 45 7 25 29 85 6 71 27 25 6 18 15 37 64 8 31 35 04 7 54 32 45 6 78 29 85 6 24 27 25 5 71 Combination 120 Capacity index kW 37 8 TC Total Capacity kW PI Power Input kW Outdoor Indo...

Page 255: ...4 26 72 6 69 10 36 91 8 77 34 36 8 09 31 82 7 40 29 27 6 85 26 72 6 31 15 36 91 8 48 34 36 7 70 31 82 6 91 29 27 6 37 26 72 5 83 Combination 100 Capacity index kW 31 50 TC Total Capacity kW PI Power I...

Page 256: ...30 57 7 23 28 35 6 65 26 13 6 18 23 91 5 71 15 32 80 7 55 30 57 6 89 28 35 6 23 26 13 5 77 23 91 5 30 Combination 80 Capacity index kW 25 2 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Te...

Page 257: ...23 67 5 34 22 05 4 99 20 43 4 69 18 82 4 40 15 25 33 5 51 23 67 5 12 22 05 4 73 20 43 4 44 18 82 4 14 Combination 60 Capacity index kW 18 9 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air T...

Page 258: ...72 4 13 10 17 85 4 76 16 77 4 55 15 75 4 33 14 74 4 13 13 72 3 91 5 17 85 4 38 16 77 4 21 15 75 4 02 14 74 3 84 13 72 3 65 1 17 85 4 18 16 77 4 00 15 75 3 82 14 74 3 65 13 72 3 48 0 17 85 4 08 16 77 3...

Page 259: ...5 18 1 15 23 20 3 16 53 22 4 16 92 23 7 16 52 25 0 16 21 40 18 1 15 23 20 3 16 53 22 4 16 92 23 7 16 52 25 0 16 21 43 18 1 15 23 20 3 16 53 22 4 16 92 23 7 16 52 25 0 16 21 Combination 50 TC Total Cap...

Page 260: ...0 65 31 3 20 26 40 22 7 19 04 25 3 20 67 28 0 21 15 29 6 20 65 31 3 20 26 43 22 7 19 04 25 3 20 67 28 0 21 15 29 6 20 65 31 3 20 26 Combination 50 TC Total Capacity kW SH Power Input kW Outdoor Indoor...

Page 261: ...0 Heating Lo m3 min 8 4 8 4 8 8 9 1 13 4 S 63KA1E5 S 71KA1E5 Hi m3 min 16 0 17 4 Me m3 min 13 7 14 7 Cooling Lo m3 min 11 4 12 0 Hi m3 min 17 1 18 3 Me m3 min 15 1 16 0 Heating Lo m3 min 13 1 13 7 26...

Page 262: ...Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Cooling...

Page 263: ...sec 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance Height 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0 0...

Page 264: ...1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Cooling...

Page 265: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 266: ...1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Coolin...

Page 267: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 268: ...1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Cooling...

Page 269: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 270: ...1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Cooling...

Page 271: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 272: ...rection 20 1 Cooling Hi 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2...

Page 273: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 274: ...1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Cooling...

Page 275: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 276: ...1m sec 0 0 5m sec Air velocity distribution 2 Cooling Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Cooling...

Page 277: ...c 0 0 5m sec Air velocity distribution 2 Heating Me 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec Air velocity distribution 3 Heating Lo 0...

Page 278: ...H eigh t m 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m Reaching distance m 1m sec over 0 5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6...

Page 279: ...5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m H eight m 1m sec over 0 5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m H eigh...

Page 280: ...H eight m 1m sec over 0 5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m H eight m 1m sec over 0 5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Re...

Page 281: ...ht m 1m sec over 0 5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m H eight m 1m sec over 0 5 1m sec 0 0 5m sec 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reachin...

Page 282: ...20 30 40 50 60 70 80 90 100 10 11 12 13 14 15 16 17 18 19 20 Air flow volume m3 min External static pressure Pa 5mmAq 49Pa 7mmAq 69Pa S 56MA1E5 5mmAq 49Pa Q P Q P Q P 15 0 49 0 13 0 32 1 11 0 25 6 13...

Page 283: ...1 12 13 14 15 16 17 18 19 20 Air flow volume m3 min External static pressure Pa 5mmAq 49Pa 7mmAq 69Pa S 71MA1E5 5mmAq 49Pa Q P Q P Q P 17 0 49 0 14 0 35 8 12 0 26 6 15 3 77 4 13 0 59 2 11 2 49 8 17 0...

Page 284: ...0 69 0 17 0 57 0 14 0 41 0 20 9 37 2 18 4 27 1 14 8 16 1 H M L H M L Standard air flow volume 19 17 14m3 min 0 10 20 30 40 50 60 70 80 90 100 12 13 14 15 16 17 18 19 20 21 22 Air flow volume m3 min E...

Page 285: ...285 S 125MA1E5 Standard air flow volume 34 0 30 4 26 3m 3 min 0 10 20 30 40 50 60 70 80 90 100 23 25 27 29 31 33 35 37 39 Air flow volume m3 min External static pressure Pa 5mmAq 49Pa 7mmAq 69Pa...

Page 286: ...in 0 5 10 15 20 25 30 35 40 45 50 6 7 8 9 10 11 12 Air flow volume m3 min External static pressure Pa 0mmAq 0Pa 3mmAq 29Pa S 28NA1E5 3mmAq 29Pa Q P Q P Q P 11 0 29 4 10 0 20 6 8 0 14 7 9 9 43 7 9 2 32...

Page 287: ...40 45 50 6 7 8 9 10 11 12 13 Air flow volume m3 min External static pressure Pa 0mmAq 0Pa 3mmAq 29Pa S 36NA1E5 3mmAq 29Pa Q P Q P Q P 11 0 29 4 9 0 20 6 7 0 14 7 9 9 43 8 8 2 32 1 6 3 26 6 11 0 29 4...

Page 288: ...0 29 4 10 0 20 6 8 0 14 7 10 8 43 8 9 2 32 1 7 3 26 7 12 0 29 4 10 0 20 6 8 0 14 7 13 2 11 3 10 8 5 6 8 5 2 8 0mmAq 0Pa Q P Q P Q P 12 0 0 0 10 0 0 0 8 0 0 0 10 8 23 2 9 2 17 2 7 3 16 2 12 0 0 0 10 0...

Page 289: ...air flow volume 12 5 10 5 8 5m3 min 0 5 10 15 20 25 30 35 40 45 50 7 8 9 10 11 12 13 14 Air flow volume m3 min External static pressure Pa 0mmAq 0Pa 3mmAq 29Pa 26 5 1 Outdoor Units U 8EA1E8 U 10EA1E8...

Page 290: ...125MA1E5 47 43 47 44 47 43 47 44 1 5m microphone outlet duct 2 inlet duct 1 indoor unit S 22YA1E5 36 33 36 33 S 28YA1E5 37 33 37 33 S 36YA1E5 38 34 38 34 S 45YA1E5 39 35 39 35 60 x 60 Cassette Type S...

Page 291: ...291 27 2 Outdoor Unit Measurement Specification dB A Cooling Heating 220 230 240V 50Hz microphone position U 8EA1E8 58 59 U 10EA1E8 59 60...

Page 292: ...60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 33 39 M L 38 44 A scale dB 41 36 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Oc...

Page 293: ...4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002 bar S 63KA1E5 Octave Band Central Frequency Hz NC 40 NC 60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back...

Page 294: ...C 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 33 37 M L 38 42 A scale dB 40 35 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave...

Page 295: ...000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002 bar S 56YA1E5 Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 36 40 M L 41 38 43 44 Fan S...

Page 296: ...NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 36 42 M L 42 47 A scale dB 45 40 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Ban...

Page 297: ...00 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002 bar S 125UA1E5 Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 Frequency H 4 4 M L 4 4 5 5 Fan Speed...

Page 298: ...60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 35 42 M L 39 46 A scale dB 44 40 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Oc...

Page 299: ...500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002 bar S 100MA1E5 Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 Frequency Fan Speed A scal...

Page 300: ...3 3 4 3 3 Back Ground Noise 12dB Frequency Fan Speed A scale dB C scale dB 50Hz H M L 3 3 3 4 3 3 Back Ground Noise 12dB 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave...

Page 301: ...V Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002 bar...

Page 302: ...302 27 8 Outdoor Unit U 10EA1E8...

Page 303: ...S S 45KA1E5 S 45KA1E5S 19 18 16 10 13 14 22 21 17 15 12 20 42 33 25 26 29 28 34 27 30 23 41 40 37 38 36 7 1 24 43 39 2 3 4 48 5 9 8 50 45 46 I I 47 O I O I CWH55025J CWH55051AJ 44 31 49 Note The above...

Page 304: ...RILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28...

Page 305: ...RILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28...

Page 306: ...RILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28...

Page 307: ...RILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28...

Page 308: ...8 9 50 3 5 4 49 16 26 28 21 22 17 25 24 30 31 27 29 42 32 23 33 34 36 37 38 41 40 CWH55025J CWH55051AJ 44 45 46 I I 47 O I O I 48 Note The above exploded view is for the purpose of parts disassembly a...

Page 309: ...RONT COVER 1 CWH13C1212 CWH13C1212 CWH13C1212 23 DISCHARGE GRILLE COMPLETE 1 CWE20C3008 CWE20C3008 CWE20C3008 24 BACK COVER CHASSIS 1 CWD933031 CWD933031 CWD933031 25 FULCRUM 2 CWH621103 CWH621103 CWH...

Page 310: ...IL COMPLETE 1 CWA43C2371 CWA43C2371 CWA43C2371 50 DRAIN PAN 1 CWH401062 CWH401062 CWH401062 Note All parts are supplied from PHAAM Malaysia Vendor Code 00029488 O marked parts are recommended to be ke...

Page 311: ...1 3 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5 42 20 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service...

Page 312: ...312 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Page 313: ...VAPORATOR SUPPORTER 3 CWD911529A CWD911529A CWD911529A 26 DRAIN PUMP COMPLETE 1 CWB53C1038 CWB53C1038 CWB53C1038 27 PANEL DRAIN PUMP ASS Y 1 CWD93K1021 CWD93K1021 CWD93K1021 28 DRAIN PUMP 1 CWB532093...

Page 314: ...4 EVAPORATOR SUPPORTER 3 CWD911529A CWD911529A 26 DRAIN PUMP COMPLETE 1 CWB53C1038 CWB53C1038 27 PANEL DRAIN PUMP ASS Y 1 CWD93K1021 CWD93K1021 28 DRAIN PUMP 1 CWB532093 CWB532093 29 ANTI VIBRATION BU...

Page 315: ...315 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Page 316: ...081007 10 BEARING 6 CWH641008 12 PLATE COVER FOR A S MOTOR 1 CWD911459 13 PLATE COVER FOR CONNECTING SHAFT 2 CWD911460 14 PLATE COVER FOR END SHAFT 1 CWD911461 21 ELECTRONIC CONT RECEIVER INDICATOR 1...

Page 317: ...8 1 4 S 63UA1E5 S 71UA1E5 S 90UA1E5 S 100UA1E5 S 125UA1E5 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service p...

Page 318: ...318 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Page 319: ...UMP COMPLETE 1 CWB53C1023 CWB53C1023 CWB53C1023 27 PANEL DRAIN PUMP ASS Y 1 CWD93K1016 CWD93K1016 CWD93K1016 28 DRAIN PUMP 1 CWB532065 CWB532065 CWB532065 29 ANTI VIBRATION BUSHING 3 CWH501097 CWH5010...

Page 320: ...388 CWA43C2388 CWA43C2388 100 CORD HOLDER 1 CWD741022 CWD741022 CWD741022 55 OPERATING INSTRUCTION 1 CWF567158 CWF567158 CWF567158 56 OPERATING INSTRUCTION 1 CWF567159 CWF567159 CWF567159 57 INSTALLAT...

Page 321: ...PUMP COMPLETE 1 CWB53C1023 CWB53C1023 27 PANEL DRAIN PUMP ASS Y 1 CWD93K1016 CWD93K1016 28 DRAIN PUMP 1 CWB532065 CWB532065 29 ANTI VIBRATION BUSHING 3 CWH501097 CWH501097 30 FLOAT SWITCH DRAIN PUMP 1...

Page 322: ...V COIL COMPLETE 1 CWA43C2387 CWA43C2387 100 CORD HOLDER 1 CWD741022 CWD741022 55 OPERATING INSTRUCTION 1 CWF567760 CWF567760 56 OPERATING INSTRUCTION 1 57 INSTALLATION INSTRUCTION 1 CWF614582 CWF61458...

Page 323: ...56NA1E5 1 1 1 2 2 3 1 23 25 24 26 28 30 9 2 33 8 11 15 14 12 13 16 10 18 21 20 19 7 22 34 35 36 37 32 31 17 16 5 3 4 6 29 27 Note The above exploded view is for the purpose of parts disassembly and r...

Page 324: ...O 18 DRAIN PAN COMPLETE 1 CWH40C1063 CWH40C1063 CWH40C1063 19 BOTTOM PLATE DRAIN SIDE 1 CWE051025 CWE051025 CWE051025 20 BOTTOM PLATE MIDDLE 1 CWE051026 CWE051026 CWE051026 21 BOTTOM PLATE FAN SIDE 1...

Page 325: ...AKYF00010 O 18 DRAIN PAN COMPLETE 1 CWH40C1063 CWH40C1063 19 BOTTOM PLATE DRAIN SIDE 1 CWE051025 CWE051025 20 BOTTOM PLATE MIDDLE 1 CWE051026 CWE051026 21 BOTTOM PLATE FAN SIDE 1 CWE051011 CWE051011 2...

Page 326: ...ALYF00005 O 18 DRAIN PAN COMPLETE 1 CWH40C1063 CWH40C1063 19 BOTTOM PLATE DRAIN SIDE 1 CWE051025 CWE051025 20 BOTTOM PLATE MIDDLE 1 CWE051026 CWE051026 21 BOTTOM PLATE FAN SIDE 1 CWE051011 CWE051011 2...

Page 327: ...MA1E5 5 24 25 26 6 9 16 14 34 15 35 12 23 10 22 21 20 33 36 18 11 19 13 7 8 4 27 28 32 2 3 1 31 30 29 17 37 Note The above exploded view is for the purpose of parts disassembly and replacement The non...

Page 328: ...ER RELAY BOX P06 T05830 1 1 18 HEADER PIPE ASSY P45 T07850 1 1 19 MULTIBENT TUBE P05 T14780 1 1 20 MAINFOLD TUBE ASSY P45 T09110 1 1 21 STRAINER B111033 1 1 22 SILENCER B121017 1 1 23 L SHAPED TUBE P0...

Page 329: ...RELAY BOX P06 T05830 1 1 1 18 HEADER PIPE ASSY P45 T09390 1 P45 T08820 1 1 19 MULTIBENT TUBE P05 T15240 1 P05 T14320 1 1 20 MAINFOLD TUBE ASSY P45 T08840 1 1 1 21 STRAINER B111033 1 1 1 22 SILENCER B1...

Page 330: ...1 25 17 18 19 20 37 38 16 24 15 22 23 14 30 34 31 32 28 29 33 9 40 28 A 35 7 3 39 36 27 26 8 6 5 A V IE W Note The above exploded view is for the purpose of parts disassembly and replacement The non n...

Page 331: ...LER P05 T14380 3 3 19 BEARING H64C1001 1 1 20 BEARING COVER P05 T12770R 1 1 21 BEARING SUPPORTER P05 T13770R 1 1 22 CONNECT SHAFT H08C025R 1 1 23 SHAFT P05 T11110R 1 1 24 STAY FAN MOTOR P06 T04990R 1...

Page 332: ...16 17 18 19 20 21 22 31 9 10 7 13 2 52 53 51 1 63 15 6 5 4 14 B 68 67 G A 23 24 25 26 27 28 29 57 BLUE CN TH1 A WHITE B Note The above exploded view is for the purpose of parts disassembly and replace...

Page 333: ...E 55 54 37 48 49 50 62 61 36 35 34 D 41 42 64 65 38 45 43 46 44 C 33 32 C YELLOW D GREEN E OUTDOOR TEMP G F Note The above exploded view is for the purpose of parts disassembly and replacement The non...

Page 334: ...ASS Y COMPRESSOR 1 CWA28K1086 CWA28K1086 22 CONTROL BOARD COVER 1 CWH131443 CWH131443 23 PTC THERMISTOR 1 D4DDG1010001 D4DDG1010001 24 MAGNETIC RELAY SMALL 1 K6C2AGA00002 K6C2AGA00002 25 MAGNETIC RELA...

Page 335: ...04 58 SENSOR COMPLETE CN TH2 1 CWA50C2705 CWA50C2705 59 SENSOR COMPLETE CN TH3 1 CWA50C2707 CWA50C2707 60 SENSOR COMPLETE CN TH4 1 CWA50C2706 CWA50C2706 61 HEATER COMPRESSOR 2 CWA341063 CWA341063 62 H...

Reviews: