132
11.8.8 SETTINGS
The automatic system settings can take up to 1 minute once power is supplied; do not operate the remote control
during this time.
In the event that 1 remote control group control is not used, do not set up the group control address (A/C No.).
The wired remote control will not display when the settings for the A/C No. are set to a value other than “01”.
Once the wires are connected to 1 remote control group control and power is supplied to the indoor unit, the A/C
No. is automatically set. To stop group control use, follow the directions below and clear the A/C No. that was
automatically set after disconnecting the wires for group control. If it is not cleared then the wired remote control
will not show any display.
•
Instructions on clearing the A/C No. after automatic setup
Turn OFF the indoor unit power supply
→
Using the DIP switch set the A/C No. to “16”
→
Turn ON the power
supply of the indoor unit
→
After approximately 1 minute, turn OFF the power supply to the indoor unit
→
Set
the DIP switch for the A/C No. to “01”.
(The next time the power supply is turned ON, the A/C No. will be cleared.)
Setting for 1 remote control group control
•
A maximum of 16 indoor units can be connected at the time of group control. (Do not connect the heat pump unit
with the cooling only unit.)
•
There are 2 methods for setting the group control address (A/C No.); an automatic and a manual setting method.
•
The A/C No. setting cannot be confirmed when using the automatic method.
•
To set each indoor unit’s A/C No., use the manual setting method.
However, if the wall type indoor unit is connected, then manual setting is not possible.
■
Automatic setting
•
By switching ON the indoor unit’s power supply with the DIP switch where the A/C No. is set to “01” (factory
setting), the A/C No. will be automatically set. (After activating the power for all indoor units, the automatic
setting takes approximately one minute.)
•
Once the A/C No. is automatically set, even when the power supply is switched OFF, the setting is stored.
To reset the A/C No. setting, follow the instructions for the “group control automatic address reset”. Refer to
the item “Local setting” in the installation instruction manual that comes with the wired remote control for the
“group control automatic address reset” method.
* If the indoor unit’s A/C No. DIP switch is not set to “01”, the automatic setting cannot be reset.
■
Manual setting
•
The manual setting is performed using each indoor unit’s printed circuit board DIP switch. (Refer to the
diagram below)
•
Set the DIP switch once the power supply for each indoor unit is switched OFF. When the power supply is
turned ON, the stored A/C No. is recalled.
•
To change the setting of the A/C No., turn OFF the power supply before resetting the DIP switch.
* Ensure that there is no redundancy in the A/C No. Any redundancy can cause faulty control.
* Ensure to set the A/C No. to “01” for 1 indoor unit.
A/C No.
01
02
03
04
05
06
07
08
Indoor unit
printed circuit
board DIP switch
(SW2)
Unnecessary
operation
1-ON
2-ON
1,2-ON
3-ON
1,3-ON
2,3-ON
1,2,3-ON
A/C No.
09
10
11
12
13
14
15
16
Indoor unit printed
circuit board DIP
switch (SW2)
4-ON
1,4-ON
2,4-ON
1,2,4-ON
3,4-ON
1,3,4-ON
2,3,4-ON
1,2,3,4-ON
(Refer to the remote control’s installation instruction manual for the remote control settings.)
Summary of Contents for S-22KA1E5S
Page 45: ...45 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5...
Page 47: ...47 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5...
Page 48: ...48 4 3 2 S 100UA1E5 S 125UA1E5...
Page 50: ...50 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5...
Page 51: ...51 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5...
Page 52: ...52 4 5 3 S 100MA1E5 S 125MA1E5...
Page 53: ...53 4 6 Outdoor Unit 4 6 1 U 8EA1E8 U 10EA1E5...
Page 54: ...54 5 Refrigeration Cycle Diagram...
Page 58: ...58 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Page 59: ...59 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Page 60: ...60 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Page 61: ...61 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Page 62: ...62 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Page 63: ...63 7 6 Outdoor Unit EA1E8 Series...
Page 64: ...64 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Page 65: ...65...
Page 66: ...66 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Page 67: ...67...
Page 68: ...68 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Page 69: ...69...
Page 70: ...70 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Page 71: ...71...
Page 72: ...72 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Page 73: ...73...
Page 74: ...74 8 6 Outdoor Unit EA1E8 Series...
Page 75: ...75...
Page 77: ...77 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE...
Page 82: ...82 9 6 2 Inverter PCB CN AC CN RY2 CN RY1 CN FM2 CN COM FG DCN CN FM1 DCP W V U...
Page 231: ...231 19 Operation Range...
Page 233: ...233 21 Outdoor Unit Cooling Heating Capacity and Power Input 21 1 U 8EA1E8...
Page 234: ...234...
Page 235: ...235 21 2 U 10EA1E8...
Page 236: ...236...
Page 302: ...302 27 8 Outdoor Unit U 10EA1E8...