Table 10-4 Setting the external static pressure
Indoor unit type
Item code
15, 22, 28, 36,
45, 56, 60, 73
90, 106
112, 140,
160
B0
External static pressure of the rated
airflow volume (Pa)
150
150
150
0010
140
140
140
0009
130
130
130
0008
120
120
120
0007
110
110
110
0006
90
90
90
0005
70
70
70
0004
50
40 *
50 *
0003
30 *
30
30
0002
10
10
10
0001
No auto airflow volume setting
-001
Auto airflow volume setting
-002
* Airflow volume setting at shipment
NOTE:
Failure to set this parameter may result in decreased airflow and condensation.
6. If the
button is pressed under the display Step 3, the
following display (Detailed setting-end screen) appears.
Then select “YES” by pressing the
or
button and press
the
button.
Auto External Static Pressure Setting Operation
7. Keep pressing the
,
and
buttons simultaneously for
4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
8. Press the
or
button to see each menu.
Select “Test run” on the LCD display and press the
button.
The “Test run” screen appears on the LCD display.
Change the display from “OFF” to “ON” by pressing the
or
button.
Then press the
button.
Detailed settings
[
]
[
]
Unit no.
Code no.
1-1
10
Set data
0001
0001
Exit detailed
settings
and restart?
YES
NO
Maintenance func
XX / XX
[
]
[
]
ECONAVI
nanoeX
RC. setting mode
Maintenance func
XX / XX
[
]
[
]
Test run
Sensor info.
Service check
Test run
Confrm
[
]
[
]
OFF
Test run
Confrm
[
]
[
]
ON