10-2. Operating the High-spec Wired Remote Controller (CZ-RTC5B)
20:30 (THU)
START
[
]
How to set the external static pressure
1. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel.
Page [
] Confirm
20:30 (THU)
2. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “8. Detailed settings” on the LCD display and press
the
button.
The “Detailed settings” screen appears on the LCD display.
3. Select the “Unit no.” by pressing the
or
button
for changes.
4. Select the “Code no.” by pressing the
or
button.
Change the “Code no.” to “B0” by pressing the
or
button (or keeping it pressed).
5. Select the “Set data” by pressing the
or
button.
Select one of the “Set data” among “0001” – “0010”
according to the desired external static pressure setting by
pressing the
or
button.
Then press the
button.
(See Table 10-2.)
When setting to auto airflow volume control:
Select the setting data to “-002”.
Then press the
button.
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no.
Code no.
Set data
10
1-1
0005
Sel.
Next
20:30 (THU)
Detailed settings
Unit no.
Code no.
Set data
1-1
-001
Sel.
Next
20:30 (THU)
B0
Detailed settings
Unit no.
Code no.
Set data
1-1
Sel.
20:30 (THU)
B0
0001
[
] Confirm
Detailed settings
Unit no.
Code no.
Set data
1-1
Sel.
20:30 (THU)
B0
-002
[
] Confirm