Safety Instructions
Check of Density Limit
U-100PZH2E5
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the
requirements for installation space of appliance are determined according to the refrigerant
charge amount [mc] used in the appliance.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows,
in case it is installed in a living area:
PAW-VP200LDHW, PAW-VP500LDHW must be calculated as wall mounted.
1.22
3.50
3.88
2.0
1.5
1.0
0.5
0.03
3.0
4.0
2.53
3.5
5.0
4.5
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
22.5
25.0
32.5
35.0
27.5
30.0
0.0
[Amin] :
minimum indoor floor space (
m
2
)
[m
c
] : the refrigerant
charge amount (kg)
Can not be installed
Can be installed
* U-100PZ2E5, U-100PZ2E8
Can not be installed
[m
c
]: the refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge
amount in the field)
[m
max
]: maximum refrigerant charge amount
U-100PZH2E5
U-100PZH2E8
(m
max
)³
3,50 kg
Can be installed
Can not be installed
* U-100PZH2E5, U-100PZH2E8
Can not be installed
[mc]: the refrigerant
charge amount (kg)
[Amin]: minimum indoor floor space (m²)
Summary of Contents for PAW-VP1000LDHW
Page 2: ......
Page 122: ...122 PAW VP LDHW Technical Manual 2019 11 Appendix A A 2 Spare parts Tanks ...
Page 123: ...123 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Page 124: ...124 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Page 125: ...125 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Page 126: ...126 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Page 132: ......
Page 133: ......
Page 134: ...Polar Energi AS Postboks 117 9450 Hamnvik Norway www polarenergi com ...