28
Fig. 3.5: Print preview
When entering the system diagram number (e.g. “58133” in the above example) into
the HPM during its initial start-up phase, the controller will automatically configure
its input and output terminals and parameters in accordance with the documentation
offered by the HPM tool.
The appendix of this manual contains a selection of the most frequently used system
diagrams (in case no Internet connection is available).
The graphical display of the web server integrated in the HPM unit is automatically
adjusted to the selected system diagram. The overview picture in the web server
corresponds to that of the selected diagram in HPM tool.
3.2 Loading the system diagram
When the system diagram is being loaded, the HPM will perform an automatic
configuration of its parameters according to the selected system diagram:
x
All input and output terminals will be assigned and configured according to
the system diagram.
x
All important functions are activated and their parameters are adjusted.
Afterwards, the controller is ready to operate!
NOTE: The operating mode switches in the HPM and in the heat pump will be
put in the “OFF” position. These have to be moved into the “AUTO” position for
the system to start working.