LC2H

Cautions for use

1. Non-voltage input type
For both panel mounting and PC 
board mounting types

1) Never apply voltage to the non-voltage 
input type. This will damage the internal 
elements. Also, since there is a possibility 
of erroneous operation, do not connect in 
parallel the inputs of a non-voltage input 
type and another counter from a single 
input signal.
2) Since the current flow is very small 
from the count input and reset input 
terminals (

1

 and 

3

 on the panel 

mounting type and terminals 

e

 to 

t

 and 

S

 to 

F

 on the PC board mounting type) 

please use relays and switches with high 
contact reliability.
3) When inputting with an open collector 
of a transistor, use a transistor for small 
signals in which ICBO is 1 µA or less and 
always input with no voltage.
4) When wiring, try to keep all the input 
lines to the count and reset inputs as 
short as possible and avoid running them 
together with high voltage and power 
transmission lines or in a power conduit. 
Also, malfunctions might occur if the 
floating capacitance of these wires 
exceeds 500 pF (10 m 

32.808 ft.

 for 

parallel wires of 2 mm

2

). When using 2 

kHz mode, use with a wiring floating 
capacitance of 120 pF (3 m 

9.843 ft.

 for 

parallel wires of 2 mm

2

). In particular, 

when using shielded wiring, be careful of 
the capacitance between wires.

PC board mounting type

1) For external power supply use 
manganese dioxide or lithium batteries 
(CR type: 3V).
2) Always reset after external power is 
applied and confirm that the display 
reads “0”.
3) Make the wiring from the battery to the 
counter unit as short as absolutely 
possible. Also, be careful of polarity.
4) Calculate battery life with the following 
formula.
t = A/I
    t: battery life [h]
    I: LC2H current consumption [mA]
    A: battery capacity until minimum 
        operation voltage is reached [mAh]
5) Hand solder to the lead terminal. Do 
not dip solder. With the tip of the 
soldering iron at 300°C 

572°F

 perform 

soldering within 3 seconds (for 30 to 60 
W soldering iron).

2. Voltage input type

1) Be aware that applying more than 30 V 
DC to count input terminals 

1

 and 

2

and reset input terminals 

3

 and 

4

 will 

cause damage to the internal elements.

2) For external resetting use H level 
(application of 4.5 to 30 V DC) between 
reset terminals 

3

 and 

4

 of the rear 

terminals. In this case, c to 
terminal 

3

 and – to terminal 

4

. This is 

the valid polarity; therefore, the counter 
will not work if reversed.
3) When wiring, try to keep all the input 
lines to the count and reset inputs as 
short as possible and avoid running them 
together with high voltage and power 
transmission lines or in a power conduit. 
Also, malfunctions might occur if the 
floating capacitance of these wires 
exceeds 500 pF (10 m 

32.808 ft.

 for 

parallel wires of 2 mm

2

). 

3. Free voltage input type

1) Use count input terminals 

1

 and 

2

 for 

free voltage input and reset terminals 

3

 

and 

4

 for non-voltage input.

2) Be aware that the application of 
voltage that exceeds the voltage range of 
the H level to the count input terminal, 
and the application of voltage to the reset 
input terminal, can cause damage to the 
internal elements.
3) Since the current flow is very small 
from reset input terminal 

3

, please use 

relays and switches with high contact 
reliability.
4) When inputting a reset with an open 
collector of a transistor, use a transistor 
for small signals in which ICBO is 1 µA or 
less and always input with no voltage.
5) To reset externally, short reset input 
terminals 

3

 and 

4

 on the rear.

6) Input uses a high impedance circuit; 
therefore, erroneous operation may occur 
if the influence of induction voltage is 
present. If you plan to use wiring for the 
input signal that is 10 m or longer (wire 
capacitance 120 pF/m at normal 
temperature), we recommend the use of 
a CR filter or the connection of a bleeder 
resistor. 

4. How to reset multiple panel 
mounting type counters all at once 
(input is the same for count)
Non-voltage input type

Notes) 1. Use the following as a guide for choosing 

transistors used for input (Tr).
Leakage current < 1 µA

2. Use as small a diode (D) as possible in the 

forward voltage so that the voltage between 
terminals 3 and 4 during reset input meets 
the standard value (0.5 V).
( At IF = 20 µA, forward voltage 0.1 and 
higher.)

Voltage input type

Note) Make sure that H (reset ON) level is at least 4.5 

V.

5. Backlight luminance

To prevent varying luminance among 
backlights when using multiple Backlight 
types, please use the same backlight 
power supply.

6. Environment for use

1) Ambient conditions
• Overvoltage category II, pollution level 2
• Indoor use
• Acceptable temperature and humidity 
range: –10 to +55°C, 35 to 85%RH (with 
no condensation at 20°C)
• Under 2000 m elevation 
2) Use the main unit in a location that 
matches the following conditions.
• There is minimal dust and no corrosive 
gas.
• There is no combustible or explosive 
gas.
• There is no mechanical vibration or 
impacts.
• There is no exposure to direct sunlight.
• Located away from large-volume 
electromagnetic switches and power 
lines with large electrical currents.
3) Connect a breaker that conforms to 
EN60947-1 or EN60947-3 to the voltage 
input section.
4) Applied voltage should be protected 
with an overcurrent protection device 
(example: T 1A, 250 V AC time lag fuse) 
that conforms to the EN/IEC standards. 
(Free voltage input type)

3

or

D

Tr

4

3 4

3 4

D

D

3

or

+V

+V

R
Tr

4

3 4

3 4

3 4

2

2

5

2

Green

Red

5

6

2

6

24V DC

24V DC

All Rights Reserved © C

OPYRIGHT

 Matsushita Electric Works, Ltd.

Summary of Contents for LC4H-PS-R6-AC240V

Page 1: ...at uses the bracket on the timer counter Choose a method that suits the application 5 Battery Replacement Easy on Environment To replace battery simply remove body for the one touch installation type and remove battery lid for the installation frame type 6 Screw Terminals Designed for Safety Built in finger protection 7 Panel Covers Replacable Standard color is ash gray Change the panel design by ...

Page 2: ... Switchable by switch 30 Hz Note 2 Count input Min input signal width ON OFF 1 1 0 25 ms 16 7 ms Switchable by switch 16 7 ms Input method signal Non voltage input using contacts or open collector connection High level 4 5 to 30 V DC Low level 0 to 2 V DC High level 24 to 240 V AC DC Low level 0 to 2 4 V AC DC Input impedance When shorted Max 10 kΩ When open Max 750 kΩ Approx 4 7 kΩ Residual volta...

Page 3: ... 1 1 0 25 ms 16 7 ms Input method Non voltage input using contacts or open collector connection Input impedance When shorted Max 10 kΩ When open Max 750 kΩ Residual voltage Max 0 5 V Reset input Min input signal width 10 ms Input method Non voltage input using contacts or open collector connection Input impedance When shorted Max 10 kΩ When open Max 750 kΩ Residual power Max 0 5 V Break down volta...

Page 4: ...nput Lock switch Unit display 1 Count speed switch Unit display 2 Count speed switch Lock switch RESET COUNTER LC2H Front reset button Terminal block side LCD side OFF ON Terminal block side LCD side 2k Hz 30Hz Fixed at 30 Hz Dimensions 1 Panel mounting type External dimensions 1 One touch installation type mm inch General tolerance 1 0 039 Panel installation diagram Note When installing to a 4 5 ...

Page 5: ...the mounting frame ATH3803 and the rubber packing ATH3804 Only installation frame type For connected installation sealed installation Only installation frame type Notes 1 Suitable installation panel thickness is 1 to 4 5 mm 039 to 177 inch 2 Waterproofing will be lost when installing repeatedly sealed installation 45 1 772 0 5 0 020 0 22 2 874 0 5 0 020 0 60 min 2 362 min 22 2 874 0 5 0 020 0 A 48...

Page 6: ... type Contact input Transistor input NPN transistor PNP transistor 2 PC board mounting type External dimensions Terminal layout and wiring diagrams General tolerance 1 0 039 mm inch PC board pattern BOTTOM VIEW General tolerance 0 1 004 Note The AXS212811K is recommended as a compatible connection socket LC2H COUNTER 33 02 0 3 1 300 012 43 4 1 709 17 3 681 DIP switch 8 19 748 15 24 0 3 600 012 3 3...

Page 7: ...unt input 1 2 3 4 5 6 0V 0V Reset input Count input 1 2 3 4 V V 5 6 1 2 3 4 5 6 Reset input Count input V V 1 2 3 4 Green Red 24V DC 24V DC 5 6 1 2 3 4 5 6 1 Counting takes place when the count input signal is ON 2 Counting resumes again when the count value reaches 99999999 full scale value and then returns to 0 with a new count input 3 No measurement takes place when a reset is input 1 When rese...

Page 8: ...ctions might occur if the floating capacitance of these wires exceeds 500 pF 10 m 32 808 ft for parallel wires of 2 mm2 3 Free voltage input type 1 Use count input terminals 1 and 2 for free voltage input and reset terminals 3 and 4 for non voltage input 2 Be aware that the application of voltage that exceeds the voltage range of the H level to the count input terminal and the application of volta...

Reviews: