Specifications
82
KW2M-A/X User's Manual
Chapter 11 Specifications
11.1 General specifications ( main unit and expansion unit)
Supply voltage range
100 to 240V AC
Rated frequency
50/60Hz
Nominal power consumption
Approx. 15V A (240V AC at 25°C)
Inrush current
Max. 30A
(240V AC/DC at 25°C)
Allowable momentary power-off
time
10ms
Ambient temperature
Operation
-10 to + 50°C
Storage
-25 to + 70°C
Ambient humidity
30 to 85%RH (at 20°C) non-condensing
Breakdown voltage (initial)
Between the isolated circuits: 2,000V/1min
a) enclosure
⇔
all terminals
b) primary insulated circuits
⇔
secondary insulated circuits
(Double insulation)
・
power supply terminals
⇔
other terminals
・
voltage input terminals
⇔
other terminals
Insulation resistance (initial)
Between the isolated circuits: min.
100MΩ
Vibration resistance
10 to 150Hz (7.5 minutes/cycle)
Single amplitude: 0.075mm (1h on 3 axes)
10 to 55Hz (1 minute/cycle)
Single amplitude: 0.375mm (1h on 3 axes)
Shock resistance
Min. 294m/s
2
(5 times on 3 axes)
Display method
LCD with backlight
Display updated cycle
500, 1000, 2000, 3000ms (set in setting mode)
Power failure memory method
(when power is off)
Internal memory
Usable altitude
Max. 2,000m above sea level
Overvoltage category
III
Pollution degree
2
Dimensions W/H/D
Main unit
Expansion unit
85 x 140 x 65mm
85 x 70 x 65mm
Weight
Main unit
Expansion unit
Approx. 450g