Settings
46
KW2M-A/X User's Manual
[Alarm]
The alarm is output when the condition next to a checked (activated) box is true.
Item
Description
1
Select CH *
Select channel to set.
2
Output type
Select pulse output type.
< List >
Integral power pulse, Alarm, General output
(initial: Integral power pulse)
3
Stand-by power
Select phase to monitor and set the threshold to use for output.
<List & Range>
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
Threshold: 0.1 to 100.0% (initial: 0.1%)
Elapsed: 0 to 9999min (initial: 0)
4
Active power
Select phase to monitor and set the threshold to use for output.
*Select
‘
Total
’
when measuring 3P3W.
<List & Range>
Target phase: Phase1, Phase2, Phase3, ALL, Total
(initial: Total)
OFF threshold: 0.00 to 9999999999.99 (initial: 9999999999.99)
ON threshold: 0.00 to 9999999999.99 (initial: 9999999999.99)
5
Reactive power
6
Apparent power
7
Over current
Select phase to monitor.
*The threshold is the ratio that is set at
‘
Setting for Power
Measurement
’
.
< List >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
8
Under current
9
Power interruption