FP2 Serial Data Unit
Parts and Functions
2
−
4
2.1
Parts and Functions
2.1.2
Operation Status Display LEDs
The operation status display shows status conditions such as the communication status
of the unit and errors/alarms.
Display
Operation
Alarm (red)
Lighted: Unit error (Lights on watchdog timer error)
Not lighted: Goes out when there is no error
COM.1
Sent data monitoring
SD (g ee )
Blinks during sending
SD (green)
Goes out when there is no sent data
Received data monitoring
RD (g ee )
Blinks during reception
RD (green)
Goes out when there is no reception data
Communication error
ERR ( ed)
Lights when communication error occurs
ERR (red)
Goes out when normal frame is received
COM.2
Sent data monitoring
SD (g ee )
Blinks during sending
SD (green)
Goes out when there is no sent data
Received data monitoring
RD (g ee )
Blinks during reception
RD (green)
Goes out when there is no reception data
Communication error
ERR ( ed)
Lights when communication error occurs
ERR (red)
Goes out when normal frame is received
LED status (
: on
: blink
: off)
Note
The ERROR LED for communication error lights if a parity,
framing, overrun, or BCC error occurs.
Summary of Contents for FP2 Series
Page 1: ......
Page 6: ...FP2 Serial Data Unit Table of Contents iv ...
Page 18: ...FP2 Serial Data Unit Functions of Serial Data Unit 1 2 ...
Page 22: ...FP2 Serial Data Unit Functions of Serial Data Unit 1 6 1 3 Restrictions on Units Combination ...
Page 24: ...FP2 Serial Data Unit Parts and Functions 2 2 ...
Page 30: ...FP2 Serial Data Unit Confirming the Unit Settings and Design Contents 3 2 ...
Page 44: ...FP2 Serial Data Unit Communication with External Devices 4 2 ...
Page 66: ...FP2 Serial Data Unit Precautions Regarding Serial Data Unit Operation and Programs 5 2 ...
Page 72: ...FP2 Serial Data Unit Operation If an Error Occurs 6 2 ...
Page 78: ...FP2 Serial Data Unit Specifications 7 2 ...
Page 86: ...FP2 Serial Data Unit Specifications 7 10 7 4 Transmission Format ...
Page 88: ...FP2 Serial Data Unit Sample Programs 8 2 ...
Page 98: ...FP2 Serial Data Unit Sample Programs 8 12 8 2 Table of ASCII Codes ...
Page 100: ...Record of changes FP2 Serial Data Unit R 2 ...
Page 101: ......
Page 102: ......