Specifications
AC OUTPUT TO LOAD
WITH GRID ABSENT
WITH GRID PRESENT
Output Power (Continuous)
@ 25°C
5500W
7000W
Overload 40/20/5/1sec
@ 25°C & 240V
5500/--/6500/7500W
--/9600/--/--W
Overload 40/5/1sec
@ 25°C & 120V
2750/3250/3750W
--
Rated Output Current
(RMS)
23A (120V and 240V)
29A (@120V and 240V)
Output Frequency
(Selectable)
50/60Hz
Output Voltage
and Accuracy
L-N: 120V ± 3%; L-L: 240V ± 3%
Output Voltage Limits
L-L: 180 to 280V (240V Nominal)
Total harmonic distortion
(THD) at rated power
< 5%
Power Factor
>99%
AC INPUT FROM GRID (GRID SUPPORT)
Automatic Transfer Power Rating
/ Typical Transfer Time
7000W / 20ms
Input Voltage Range
L-L: 180 to 280V (240V nominal)
Input Frequency Range
45 to 54.9Hz / 55 to 65Hz
AC OUTPUT TO GRID (GRID SUPPORT)
Output Power (Continuous)
@ 25°C
5000W
Grid Feed-In Current Range
0 to 24A (@240V)
Grid Feed-In Voltage Range
L-L: 211 to 264V ± 3.0V
Grid Feed-In
Frequency Range
49.3 to 50.5Hz / 59.3 to 60.5Hz ± 0.05Hz
DC BATTERY CHARGER
20. INVERTER SPECIFICATIONS