Installation Manual
Connecting to the Grid/Utility
Step 1. Check the grid voltage and frequency with an AC multimeter. It should
be within the operation AC voltage range of the product’s specifications.
Step 2. Make sure the circuit breaker is off.
Step 3. For each AC wire, strip 15mm(0.6in) of insulation.
Step 4. Connect the AC wires to the inverter according to the labels indicated
on the terminal block or your grid utility type.
Note: The PE protective conductor (Ground) should be the first to be
connected.
Grid (Utility) Connection
AC WIRE FOR GRID CONNECTION
CONNECTING TO AC UTILITY TERMINAL