SPECIFICATIONS

Item

Standard type

Multifunction type

Low pressure type

High pressure type

Low pressure type

High pressure type

Pressure type

Gauge pressure

Rated pressure range

-100 to + 100kPa

-0.1 to +1.0MPa

-100 to + 100kPa

-0.1 to +1.0MPa

Set pressure range

-100 to + 100kPa

-0.1 to +1.0MPa

-100 to + 100kPa

-0.1 to +1.0MPa

Pressure resistance

500kPa

1.5MPa

500kPa

1.5MPa

Applicable fluid

Non-corrosive gas

Supply voltage

12 to 24V DC 

10%, Ripple P-P 10% or less

Power consumption

• Normal operation: 840mW or less (current consumption 35mA or less at 24V supply voltage)
• ECO mode (STD): 600mW or less (current consumption 25mA or less at 24V supply voltage)
• ECO mode (FULL): 480mW or less (current consumption 20mA or less at 24V supply voltage)

Comparative output

NPN output type

• NPN open-collector transistor
• Maximum sink current: 100mA
• Applied voltage: 30V DC or less (between

comparative output and 0V)

• Residual voltage: 2V or less (at 100mA sink current)

PNP output type

• PNP open-collector transistor
• Maximum source current: 100mA
• Applied voltage: 30V DC or less (between

comparative output and +V)

• Residual voltage: 2V or less (at 100mA source

current)

Output operation

Either N.O. or N.C., selectable

Hysteresis

Min. 1 digit (variable). When using psi units, 2 digits.

Repeatability

0.1% F.S.

 within 2 digits

0.2% F.S.

 within 2 digits

0.1% F.S.

 within 2 digits

0.2% F.S.

 within 2 digits

Response time (ms)

2.5, 5, 10, 25, 50, 100, 250, 500, 1000, 5000ms, selectable

Analog voltage output

_

• Output voltage: 1 to 5V
• Zero point: within 3V 

5% F.S.

• Span: within 4V 

5% F.S.

• Linearity: within 

1% F.S.

• Output impedance: approx. 

1k

• Output voltage: 0.6 to 5V
• Zero point: within 1V 

5% F.S.

• Span: within 4.4V 

5% F.S.

• Linearity: within 

1% F.S.

• Output impedance: approx. 

1k

External input

_

• ON voltage: 

NPN type

: 0.4V DC or less, 

PNP type

: 5V to 

+V DC 

• OFF voltage: 

NPN type

: 5 to 30V DC or open, 

PNP type

0.6V DC or less or open

• Input impedance: approx. 10k

• Input time: 1ms or more

Ambient temperature

-10 to +50°C (No dew condensation or ice formation allowed). Storage: -10 to +60°C.

Ambient humidity

35 to 85% RH. Storage: 35 to 85% RH.

Temperature characteristics

0.5% F.S.

(20°C reference)

1% F.S.

(20°C reference)

0.5% F.S.

(20°C reference)

1% F.S.

(20°C reference)

Material

Enclosure: PBT (with glass fiber); LCD display: acrylic; Pressure port: stainless steel (SUS 303); Mounting screws: 
brass (nickel-plated); O-ring: H-NBR; Switch: silicon rubber

Weight

40g approx. (DP-100-E type: 45g approx., DP-100-M type: 30g approx.) (Main body only)

Accessories

CN-14A-C2 (Cable with a connector, 2m long; optional for J type). Unit switching label: 1 pc.

Rugghölzli 2

CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for DP-100 series

Page 1: ...ightening a commercial coupler to the pressure port The tightening torque should be 9 8N m or less M5 female connector 1N m or less The commercial coupler or pressure port section will be damaged if the tightening torque is excessive Wrap sealing tape around the coupler when connecting to prevent leaks INSTRUCTION MANUAL WARNING Never use this product as a sensing device for personnel protection I...

Page 2: ...OUNTING No Part Description 1 M3 length 6mm screws with washers Accessory with MS DP1 1 2 Sensor mounting bracket MS DP1 1 Optional 5 WIRING Pin no Terminal name 1 V 2 Comparative output 1 3 Standard type Comparative output 2 Multifunction type Analog voltage output or external input 4 0V 6 I O CIRCUIT DIAGRAMS 1 2 CN 14A C غ Recommended product Contact SPHD 001T P0 5 Housing PAP 04V S JST Mfg Co ...

Page 3: ...when psi is selected as the pressure unit Hi 1 or Lo 1 is displayed for comparative output 1 and Hi 2 or Lo 2 for comparative output 2 on the sub display Notes Hysteresis can be fixed in 8 levels For details see page 6 section 11 PRO MODE Hi 1 or Lo 1 is displayed for comparative output 1 and Hi 2 or Lo 2 for comparative output 2 on the sub display 8 SELECTING MODES 9 RUN MODE Setting condition 1 ...

Page 4: ...put AREF Auto reference input 1 or ZERO Remote zero adjustment input 2 1For details see page 7 section 13 AUTO REFERENCE FUNCTION 2 For details see page 8 section 14 REMOTE ZERO ADJUSTMENT FUNCTION MULTIFUNCTION TYPE Setting condition 3 Comparative output 1 set to HYS Hysteresis mode or WCMP Window comparator mode Analog voltage output external input Analog voltage output Setting condition 4 Compa...

Page 5: ... Selects color of main display Pressure unit selection Selects desired pressure unit 1If for the standard type DP 100 comparative output 2 is set to OFF the N O N C selection normally open normally closed selection is the same as for the multifunction type i e you will only set N O or N C for comparative output 1 not for both comparative outputs 2The default setting of the high pressure type is N ...

Page 6: ... carried out for approx 5s in RUN mode the display is turned off Press any key to temporarily show the normal display Setting check code Current settings for DP 100 are stored in code which you can display See Code table on page 7 Setting copy mode Settings can be copied from master sensors to slave sensors For details see page 7 section 12 SETTING COPY FUNCTION ON settings are copied ON L setting...

Page 7: ...digit 7th digit 8th digit Analog voltage output Compara tive output 1 Compara tive output 1 Compara tive output 1 Compara tive output 1 Compara tive output 2 Compara tive output 2 Compara tive output 2 Compara tive output 2 Remote zero adjustment Auto reference N O OFF OFF N C N O N O N C N C N O N O N C N C N C N O EASY Hysteresis Window comparator EASY Hysteresis Window comparator Red when ON Gr...

Page 8: ...ot apply pressure applied at the pressure port pressure should equal atmo spheric pressure Redo zero adjustment External input is carried out outside the rated pressure range Applied pressure range should be adjusted to fall within rated pressure range Communication error e g disconnection faulty con nection etc Check the wiring when using the copy function Communication error incor rect model Mak...

Page 9: ...igits Repeatability 0 1 F S within 2 digits 0 2 F S within 2 digits 0 1 F S within 2 digits 0 2 F S within 2 digits Response time ms 2 5 5 10 25 50 100 250 500 1000 5000ms selectable Analog voltage output _ Output voltage 1 to 5V Zero point within 3V 5 F S Span within 4V 5 F S Linearity within 1 F S Output impedance approx 1k Output voltage 0 6 to 5V Zero point within 1V 5 F S Span within 4 4V 5 F...

Reviews: