3
Hysteresis mode
The comparative output is turned ON or OFF (depending on the N.O./N.C.
setting) when the upper or lower threshold is reached and remains ON or
OFF until the other threshold is reached.
Window comparator mode
The comparative output is turned ON or OFF (depending on the N.O./N.C.
setting) when the pressure lies between the upper or lower threshold. The
tolerance of the threshold is specified by the hysteresis setting. For details,
see page 6, section 11, PRO MODE.
DP-100 has 3 different modes:
RUN mode. For details, see page 3, section 9, RUN MODE.
Menu setting mode. For details, see page 5, section 10, MENU
SETTING MODE.
Pro mode. For details, see page 6, section 11, PRO MODE.
Switching modes
Press
to switch between modes.
From RUN mode, press
for 2s to select the menu setting mode.
From RUN mode, press
for 4s to select pro mode.
To return to RUN mode, press
for 2s.
In RUN mode, you can lock the keys and adjust the threshold for the param-
eters set in menu setting mode while the sensor is operating. For details,
see page 5, section 10, MENU SETTING MODE.
Threshold settings are displayed in the sub-display.
If you attempt to set threshold values that exceed the pressure range
allowed, DP-100 will alert you.
UP
(exceeds the upper limit) or
DOWN
(exceeds
the lower limit) will appear on the sub-display.
DOWN
will also appear if the
Hi
threshold value exceeds the
Lo
threshold value for the hysteresis mode or
window comparator mode.
Standard type
Notes:
• H (Hysteresis): 1 digit or more, 2 digits or more when psi is
selected as the pressure unit.
•
Hi-1
or
Lo-1
is displayed for comparative output 1 and
Hi-2
or
Lo-
2
for comparative output 2 on the sub-display.
Notes:
• Hysteresis can be fixed in 8 levels.
For details, see page 6, section 11, PRO MODE.
•
Hi-1
or
Lo-1
is displayed for comparative output 1 and
Hi-2
or
Lo-
2
for comparative output 2 on the sub-display.
8
SELECTING MODES
9
RUN MODE
Setting condition 1
Comparative output 1 set to:
EASY
(EASY mode)
Comparative output 2 set to:
OFF
(OFF)
0
Lo
Hi
ON
OFF
H (Hysteresis)
Pressure
Comparative
output
0
H (Hysteresis)
H (Hysteresis)
Pressure
Lo
Hi
ON
OFF
Comparative
output
MODE
MODE
MODE
MODE
Setting condition 2
Comparative output 1 set to:
EASY
(EASY mode)
Comparative output 2 set to:
EASY
(EASY mode)
Setting condition 3
Comparative output 1 set to:
EASY
(EASY mode)
Comparative output 2 set to:
HYS
(Hysteresis mode), or
WCMP
(Window comparator mode)
Setting condition 4
Comparative output 1 set to:
HYS
(Hysteresis mode), or
WCMP
(Window comparator mode)
Comparative output 2 set to:
OFF
(OFF)
Setting condition 5
Comparative output 1 set to:
HYS
(Hysteresis mode), or
WCMP
(Window comparator mode)
Comparative output 2 set to:
EASY
(EASY mode)
Setting condition 6
Comparative output 1 set to:
HYS
(Hysteresis mode), or
WCMP
(Window comparator mode)
Comparative output 2 set to:
HYS
(Hysteresis mode), or
WCMP
(Window comparator mode)
MODE
Automatic
Automatic
MODE
MODE
MODE
Automatic
Automatic
Automatic
MODE
Automatic
Automatic
MODE
MODE
MODE
Automatic
Automatic
Automatic
MODE
MODE
MODE
MODE
Automatic
Automatic
Automatic
Automatic