Vertical Airflow Direction Auto-Control
•
•
•
•
When set an Airflow Direction Auto-Control with remote
control, the louver swings up and down as shown in the
diagram.
•
•
•
•
The louver does not swing when the Indoor Fan Motor
stops during operation at the upper limit.
•
•
•
•
When stopped with remote control, the discharge vent is
reset, and stopped at the closing position.
•
•
•
•
During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 36° to 12° - 28° under
Cooling and Soft Dry operation mode.
Vertical Airflow Direction manual Control
•
•
•
•
When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in
the diagram.
The louver can be adjusted by pressing the button to the
desired louver position.
•
•
•
•
When the remote control is used to stop the operation, the
discharge vent is reset, and stopped at the closing position.
•
•
•
•
During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 14°, 19°, 24°, 30°, 36° to
16°, 18°, 20°, 22°, 24° under Cooling and Soft Dry operation
mode.
8.6. Random Auto Restart Control
•
•
•
•
If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the
power is resumed.
It will start with previous operation mode and airflow direction.
•
•
•
•
Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
•
•
•
•
Auto Restart Control is not available when Timer is set.
•
•
•
•
This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
8.7. Airflow Direction Control
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation.
2. In Heating operation, when the piping air temperature reaches 38°C, the louver is changed from upper to lower limit position. When the
piping air temperature falls to 35°C, the louver is changed from lower to upper limit position.
28
CS-W18CKE CU-W18CKE / CS-W24CKE CU-W24CKE
Summary of Contents for CS-W18CKE
Page 10: ...4 Dimensions 10 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 11: ...11 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 12: ...5 Refrigeration Cycle Diagram 12 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 13: ...6 Block Diagram 13 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 14: ...7 Wiring Diagram CS W18CKE CU W18CKE CS W24CKE CU W24CKE 14 ...
Page 34: ...34 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 36: ...39 40 41 38 36 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 37: ...39 37 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 38: ...35 37 38 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 39: ...38 39 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 40: ...39 40 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 41: ...41 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 70: ...14 Technical Data 70 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 72: ...72 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 73: ...73 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 82: ...SCHEMATIC DIAGRAM 5 5 82 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...
Page 84: ...19 1 REMOTE CONTROL 84 CS W18CKE CU W18CKE CS W24CKE CU W24CKE ...