13.5 Compressor Overheating Prevention Control (For S18, S24, 28PK only)
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 112°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. “F97” is indicated.
Compressor=OFF
Compressor Frequency
Reduced
Compressor Frequency
Maintain
Free
Comp Discharge temperature
112°C
96°C
110°C
100°C
97°C
90°C
13.6 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
13.7 Compressor Tank Temperature Rise Protection Control
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
Control
contents
o
Compressor stops (and restart after 3 minutes)
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
13.8 Low Frequency Protection Control 1
When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
13.9 Low Frequency Protection Control 2
When all below conditions comply, the compressor frequency will changed to lower frequency.
Temperature, T, for:
Cooling / Soft Dry
Indoor intake air (°C)
T < 15 or T
≥
30
Outdoor air (°C)
T < 16 or T
≥
38
Indoor heat exchanger (°C)
T < 30
Summary of Contents for cs-s9pkv
Page 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9PKV CS S12PKV...
Page 13: ...13 4 1 2 CS S18PKV CS S24PKV CS S28PKV...
Page 14: ...14 4 2 Outdoor Unit 4 2 1 CU S9PKV 4 2 2 CU S12PKV 542...
Page 15: ...15 4 2 3 CU S18PKV CU S24PKV...
Page 16: ...16 4 2 4 CU S28PKV...
Page 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9PKV CU S9PKV CS S12PKV CU S12PKV...
Page 18: ...18 5 2 CS S18PKV CU S18PKV CS S24PKV CU S24PKV...
Page 19: ...19 5 3 CS S28PKV CU S28PKV...
Page 20: ...20 6 Block Diagram 6 1 CS S9PKV CU S9PKV...
Page 21: ...21 6 2 CS S12PKV CU S12PKV...
Page 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9PKV CS S18PKV CS S24PKV...
Page 26: ...26 7 1 3 CS S28PKV...
Page 31: ...31 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9PKV CS S18PKV CS S24PKV...
Page 32: ...32 8 1 2 CS S12PKV...
Page 33: ...33 8 1 3 CS S28PKV...
Page 35: ...35 8 2 2 CU S12PKV...
Page 39: ...39 9 1 1 2 CS S12PKV...
Page 41: ...41 9 1 5 Human Activity Sensor Printed Circuit Board...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9PK...
Page 43: ...43 9 2 1 2 CU S12PK...
Page 44: ...44 9 2 1 3 CU S18PK CU S24PK...
Page 45: ...45 9 2 1 4 CU S28PK...
Page 46: ...46 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9PKV...
Page 47: ...47 9 2 2 2 CU S28PKV...
Page 51: ...51...
Page 60: ...60...
Page 121: ...121 Figure 3 Figure 4 16 1 1 3 To Remove Discharge Grille Figure 5...
Page 123: ...123 Figure 9 Figure 10...
Page 125: ...125 16 2 1 3 To Remove Power Electronic Controller Figure 13 Figure 14 Figure 15...
Page 127: ...127 Figure 19 Figure 20 Figure 21...