11.2.3 Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND
PIPES in the following procedure.
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o
Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o
Be sure to check for gas leakage.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step
3
above take the following measure:
-
If the leak stops when the piping connections are tightened further, continue working from step
3
.
-
If the leak does not stop when the connections are retightened, repair location of leak.
-
Do not release refrigerant during piping work for installation and reinstallation.
-
Take care of the liquid refrigerant, it may cause frostbite.
Summary of Contents for cs-s9pkv
Page 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9PKV CS S12PKV...
Page 13: ...13 4 1 2 CS S18PKV CS S24PKV CS S28PKV...
Page 14: ...14 4 2 Outdoor Unit 4 2 1 CU S9PKV 4 2 2 CU S12PKV 542...
Page 15: ...15 4 2 3 CU S18PKV CU S24PKV...
Page 16: ...16 4 2 4 CU S28PKV...
Page 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9PKV CU S9PKV CS S12PKV CU S12PKV...
Page 18: ...18 5 2 CS S18PKV CU S18PKV CS S24PKV CU S24PKV...
Page 19: ...19 5 3 CS S28PKV CU S28PKV...
Page 20: ...20 6 Block Diagram 6 1 CS S9PKV CU S9PKV...
Page 21: ...21 6 2 CS S12PKV CU S12PKV...
Page 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9PKV CS S18PKV CS S24PKV...
Page 26: ...26 7 1 3 CS S28PKV...
Page 31: ...31 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9PKV CS S18PKV CS S24PKV...
Page 32: ...32 8 1 2 CS S12PKV...
Page 33: ...33 8 1 3 CS S28PKV...
Page 35: ...35 8 2 2 CU S12PKV...
Page 39: ...39 9 1 1 2 CS S12PKV...
Page 41: ...41 9 1 5 Human Activity Sensor Printed Circuit Board...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9PK...
Page 43: ...43 9 2 1 2 CU S12PK...
Page 44: ...44 9 2 1 3 CU S18PK CU S24PK...
Page 45: ...45 9 2 1 4 CU S28PK...
Page 46: ...46 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9PKV...
Page 47: ...47 9 2 2 2 CU S28PKV...
Page 51: ...51...
Page 60: ...60...
Page 121: ...121 Figure 3 Figure 4 16 1 1 3 To Remove Discharge Grille Figure 5...
Page 123: ...123 Figure 9 Figure 10...
Page 125: ...125 16 2 1 3 To Remove Power Electronic Controller Figure 13 Figure 14 Figure 15...
Page 127: ...127 Figure 19 Figure 20 Figure 21...