65
11.2.4 Connect the Cable to the Outdoor Unit
1 Remove the control board cover from the
unit by loosening the screw.
2 Cable connection to the power supply through
Isolating Devices (Disconnecting means).
o
Connect approved type polychloroprene
sheathed
power supply cord
3 x
4.0 mm
2
type designation 60245 IEC 57
or heavier cord to the terminal board, and
connect the others end of the cord to
Isolating Devices (Disconnecting means).
o
Do not use joint power supply cord.
Replace the wire if the existing wire (from
concealed wiring, or otherwise) is too
short.
o
In unavoidable case, joining of power
supply cord between isolating devices
and terminal board of air conditioner shall
be done by using approved socket and
plug rated 25A. Wiring work to both
socket and plug must follow to national
wiring standard.
3
Connection cable
between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 60245 IEC 57 or
heavier cord. Do not use joint connection
cable. Replace the wire if the existing wire
(from concealed wiring, or otherwise) is too
short.
4 Connect the power supply cord and
connection cable between indoor unit and
outdoor unit according to the diagram below.
5 Secure the power supply cord and connection
cable onto the control board with the holder.
6 Attach the control board cover back to the
original position with screw.
7 For wire stripping and connection requirement,
refer to instruction 11.1.7 of indoor unit.
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
11.2.5 Piping
Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
Summary of Contents for cs-s9pkv
Page 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9PKV CS S12PKV...
Page 13: ...13 4 1 2 CS S18PKV CS S24PKV CS S28PKV...
Page 14: ...14 4 2 Outdoor Unit 4 2 1 CU S9PKV 4 2 2 CU S12PKV 542...
Page 15: ...15 4 2 3 CU S18PKV CU S24PKV...
Page 16: ...16 4 2 4 CU S28PKV...
Page 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9PKV CU S9PKV CS S12PKV CU S12PKV...
Page 18: ...18 5 2 CS S18PKV CU S18PKV CS S24PKV CU S24PKV...
Page 19: ...19 5 3 CS S28PKV CU S28PKV...
Page 20: ...20 6 Block Diagram 6 1 CS S9PKV CU S9PKV...
Page 21: ...21 6 2 CS S12PKV CU S12PKV...
Page 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9PKV CS S18PKV CS S24PKV...
Page 26: ...26 7 1 3 CS S28PKV...
Page 31: ...31 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9PKV CS S18PKV CS S24PKV...
Page 32: ...32 8 1 2 CS S12PKV...
Page 33: ...33 8 1 3 CS S28PKV...
Page 35: ...35 8 2 2 CU S12PKV...
Page 39: ...39 9 1 1 2 CS S12PKV...
Page 41: ...41 9 1 5 Human Activity Sensor Printed Circuit Board...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9PK...
Page 43: ...43 9 2 1 2 CU S12PK...
Page 44: ...44 9 2 1 3 CU S18PK CU S24PK...
Page 45: ...45 9 2 1 4 CU S28PK...
Page 46: ...46 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9PKV...
Page 47: ...47 9 2 2 2 CU S28PKV...
Page 51: ...51...
Page 60: ...60...
Page 121: ...121 Figure 3 Figure 4 16 1 1 3 To Remove Discharge Grille Figure 5...
Page 123: ...123 Figure 9 Figure 10...
Page 125: ...125 16 2 1 3 To Remove Power Electronic Controller Figure 13 Figure 14 Figure 15...
Page 127: ...127 Figure 19 Figure 20 Figure 21...