49
11.1.3.2 Automatic
Operation
•
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
•
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
•
Every 10 minutes, the indoor temperature is judged.
•
For the 1st judgment
o
If indoor intake temperature - remote control setting temperature
≥
2°C, COOL mode is decided.
o
If
-2°C
≤
indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
•
For the 2nd judgment onwards
o
If indoor intake temperature - remote control setting temperature
≥
3°C, if previous operate in DRY mode,
then continue in DRY mode. Otherwise COOL mode is decided.
o
If
-2°C
≤
indoor intake temperature - remote control setting temperature < 3°C, maintain with previous mode.
11.1.3.3 Fan
Operation
•
Fan operation is used to circulate air in the room.
•
During operation, indoor fan run continuously but outdoor fan and compressor stop.
•
Temperature setting is not applicable.
11.2 Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
•
Manual
Fan
Speed
[Cooling, Dry]
o
Fan motor’s number of rotation is determined according to remote control setting.
Remote control
○
○
○
○
○
Tab Hi
Me+
Me
Me-
Lo
•
Auto Fan Speed
[Cooling, Dry]
o
According to room temperature and setting temperature, indoor fan speed is determined automatically.
o
The indoor fan will operate according to pattern below.
Summary of Contents for CS-S9NKR
Page 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9NKR CS S12NKR...
Page 13: ...13 4 1 2 CS S18NKR CS S24NKR CS S28NKR...
Page 14: ...14 4 2 Outdoor Unit 4 2 1 CU S9NKR CU S12NKR 4 2 2 CU S18NKR CU S24NKR CU S28NKR...
Page 15: ...15 5 Refrigeration Cycle Diagram 5 1 CS S9NKR CU S9NKR CS S12NKR CU S12NKR...
Page 16: ...16 5 2 CS S18NKR CU S18NKR CS S24NKR CU S24NKR CS S28NKR CU S28NKR...
Page 17: ...17 6 Block Diagram 6 1 CS S9NKR CU S9NKR CS S12NKR CU S12NKR...
Page 18: ...18 6 2 CS S18NKR CU S18NKR...
Page 19: ...19 6 3 CS S24NKR CU S24NKR...
Page 20: ...20 6 4 CS S28NKR CU S28NKR...
Page 21: ...21 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9NKR CS S12NKR...
Page 22: ...22 7 1 2 CS S18NKR CS S24NKR CS S28NKR...
Page 25: ...25 7 2 3 CU S24NKR...
Page 26: ...26 7 2 4 CU S28NKR...
Page 27: ...27 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9NKR CS S12NKR...
Page 28: ...28 8 1 2 CS S18NKR CS S24NKR CS S28NKR...
Page 29: ...29 8 2 Outdoor Unit 8 2 1 CU S9NKR CU S12NKR...
Page 30: ...30 8 2 2 CU S18NKR...
Page 31: ...31 8 2 3 CU S24NKR...
Page 32: ...32 8 2 4 CU S28NKR...
Page 34: ...34 9 1 1 2 CS S18NKR CS S24NKR CS S28NKR 9 1 2 Indicator Printed Circuit Board...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9NKR CU S12NKR...
Page 36: ...36 CN DEMAND AC GND CN PWR...
Page 37: ...37 9 2 2 CU S18NKR...
Page 38: ...38 9 2 3 CU S24NKR CU S28NKR...
Page 42: ...42...
Page 90: ...90 Figure 3 Figure 4 15 1 1 3 To remove discharge grille Figure 5...
Page 92: ...92 Figure 9 Figure 10...
Page 96: ...96 Figure 20 Figure 21...
Page 124: ...124 Printed in Malaysia SB0712 0...