26
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point +0.5K.
11.1.4 Heating operation
11.1.4.1
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0
℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature<
Compressor OFF point +0.5K.
11.1.5 Automatic Operation
• Once AUTO mode is selected, operation mode is determined by set temperature of remote control and indoor
intake temperature.
1st judgment
JUDGE CONDITION
REFERANCE MODE
If indoor intake temp – Remote control
temp setting
≥
+2
Cool mode
If -2
≤
indoor intake temp. – Remote
control Temp. setting
≤
+2
Dry mode
If indoor intake temp. – Remote control
temp. setting < -2
Heat mode
Intake temp.- setting temp.
DRY
COOL
HEAT
-6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6
Summary of Contents for CS-RE9PKE-3
Page 11: ...11 5 Dimensions 5 1 Indoor Unit Unit mm...
Page 12: ...12 5 2 Outdoor Unit Unit mm...
Page 14: ...14 7 Block Diagram...
Page 15: ...15 8 Wiring Diagram...
Page 18: ...18 9 2 3 Indoor Unit Installation...
Page 42: ...42 Cooling Characteristic at Different Piping Length...
Page 43: ...43 Heating Characteristic at Different Outdoor Air Temperature...
Page 44: ...44 Heating Characteristic at Different Piping Length...
Page 46: ...46 Cooling Characteristic at Different Piping Length...
Page 47: ...47 Heating Characteristic at Different Outdoor Air Temperature...
Page 48: ...48 Heating Characteristic at Different Piping Length...
Page 50: ...50 Cooling Characteristic at Different Piping Length...
Page 51: ...51 Heating Characteristic at Different Outdoor Air Temperature...
Page 52: ...52 Heating Characteristic at Different Piping Length...
Page 55: ...55 16 2 Outdoor Unit CU RE9PKE 3 CU RE12PKE 3 CU RE15PKE 3...