37
14.2.3 Error Codes Table
Code
Abnormality/Protection
Judgment
Check
Emergency
Operation
H00
Normal
H11
Indoor/Outdoor abnormal
communication
>1 minute after starting
operation
Connecting cable,
Indoor/outdoor PCB
○
H14
Indoor intake air temp sensor
abnormality
-
Intake air temperature
sensor(defected or
disconnected)
×
H15
Outdoor compressor
tempearture sensor abnormality
Continue for 5 sec.
Compressor tempeature
sensor(defected or
disconnected)
×
H16
Outdoor Current Transformer
open circuit
-
Outdoor PCB, IPM module
×
H19
Indoor fan motor mechanism
lock
-
Indoor PCB, fan motor
×
H23
Indoor heat exchanger
temperature A sensor
abnormality
Continue for 5 sec.
Heat exchanger
temperature
sensor(defected or
disconnected)
○
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
Outdoor temperature
sensor(defected or
disconnected)
○
H28
Outdoor heat exchanger
temperature sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger
sensor(defected
disconnected)
○
H30
Discharge temperature sensor
abnormality
Continue for 5 sec.
Discharge temperature
sensor(defected or
disconnected)
×
H33
Incorrect connection of
Indoor/Outdoor cable
-
Indoor/outdoor supply
voltage
×
H97
Outdoor fan motor lock
Twice within 30 minutes Outdoor fan motor
×
H98
Indoor high pressure protection -
Air filter dirty
Air circulation short circuit
-
H99
Indoor heat exchanger anti-
freezing protection
Indoor heat exchanger
freezing
Insufficient refrigerant
Air filter dirty
-
F11
Cooling/Heating cycle
changeover abnormality
4 times occurrence
within 30 minutes
4-way valve
V-coil
×
F90
PFC control
4 times occurrence
within 20 minutes
Voltage at PFC
×
F91
Refrigeration cycle abnormality
2 times occurrence
within 20 minutes
No refrigerant(3-way valve is
closed)
×
F93
Compressor abnormality
4 times occurrence
within 20 minutes
Compressor
×
F95
Cool high pressure protection
4 times occurrence
within 20 minutes
Outdoor refrigeration cycle
×
F96
IPM overheating protection
-
Excessive refrigerant
Improper heat radiation
IPM
×
F97
Outdoor compressor
overheating protection
4 times occurrence
within 20 minutes
Insufficient refrigerant
Compressor
×
F98
Total running current protection
3 times occurrence
within 20 minutes
Excess refrigerant
Improper radiation
×
F99
Outdoor Peak Current
Protection Control
4 times occurrcnce
continuously within 30
minutes
Outdoor PCB
IPM
Compressor
×
Summary of Contents for CS-RE12NKR
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Unit mm ...
Page 10: ...10 5 2 Outdoor Unit Unit mm ...
Page 11: ...11 6 Refrigeration Cycle Diagram COOLIN HEATING ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Diagram CS RE9NKR CU RE9NKR ...
Page 14: ...14 CS RE12NKR CU RE12NKR ...
Page 15: ...15 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 18: ...18 10 2 3 Indoor Unit Installation ...
Page 44: ...44 Cooling Characteristic at Different Piping Length ...
Page 45: ...45 Heating Characteristic at Different Outdoor Air Temperature ...
Page 46: ...46 Heating Characteristic at Different Piping Length ...
Page 47: ...47 16 1 2 CS RE12NKR CU RE12NKR Cooling Characteristic at Different Outdoor Air Temperature ...
Page 48: ...48 Cooling Characteristic at Different Piping Length ...
Page 49: ...49 Heating Characteristic at Different Outdoor Air Temperature ...
Page 50: ...50 Heating Characteristic at Different Piping Length ...
Page 51: ...51 17 Exploded View and Replacement Pars List 17 1 Indoor Unit CS RE9NKR CS RE12NKR ...