28
12.3 Outdoor Fan Motor Operation
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30
seconds after compressor stops operation.
30 s
Compressor
Outdoor Fan
ON
ON
OFF
OFF
ON
12.3.1 Vertical Airflow
Airflow Direction
1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature. When the air
conditioner is stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control. The angels of the vane are as stated above. When the air
conditioner is stopped using remote control, the vane will shift to close position.
* Above angle data is for reference only.
12.3.2 Horizontal Airflow
The horizontal airflow direction louvers can be adjusted manually by hand.
12.3.3 Quiet operation
●
To provide quiet operation comparing to normal operation. The Quiet operation can be active or stop by pressing
QUIET button on remote control.
●
Once Quiet mode is active, the unit will continuously operate in QUIET Mode until cancel the mode by pressing
QUIET button on remote control.
12.3.4 Powerful operation
●
To cooling or heating the room faster comparing to normal operation. The POWERFUL operation can be active or
stop by pressing POWERFUL button
on
remote control.
●
When powerful operation is active, the unit will continuously operate in POWERFUL mode until cancel the mode
by pressing POWERFUL button on remote control. Operation details are as the fig. below.
1. For cooling, soft Dry mode
1
2
3
4
5
10°
21°
31°
40°
50°
Normal
Powerful
10°
21°
31°
40°
50°
Normal
Powerful
Normal
7°
22°
35°
50°
60°
Powerful
31°
40°
48°
58°
68°
Normal
Powerful
7°,8°,36°
Manual
7°,8°,33°,45°(Beginning of POWERFUL mode)
10°-50°
6°,35°(Beginning of POWERFUL mode)
12°
Operating Mode
Cooling
Soft dry
12°
Heating
Manual
Auto
Manual
Auto
Auto
Summary of Contents for CS-RE12NKR
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Unit mm ...
Page 10: ...10 5 2 Outdoor Unit Unit mm ...
Page 11: ...11 6 Refrigeration Cycle Diagram COOLIN HEATING ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Diagram CS RE9NKR CU RE9NKR ...
Page 14: ...14 CS RE12NKR CU RE12NKR ...
Page 15: ...15 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 18: ...18 10 2 3 Indoor Unit Installation ...
Page 44: ...44 Cooling Characteristic at Different Piping Length ...
Page 45: ...45 Heating Characteristic at Different Outdoor Air Temperature ...
Page 46: ...46 Heating Characteristic at Different Piping Length ...
Page 47: ...47 16 1 2 CS RE12NKR CU RE12NKR Cooling Characteristic at Different Outdoor Air Temperature ...
Page 48: ...48 Cooling Characteristic at Different Piping Length ...
Page 49: ...49 Heating Characteristic at Different Outdoor Air Temperature ...
Page 50: ...50 Heating Characteristic at Different Piping Length ...
Page 51: ...51 17 Exploded View and Replacement Pars List 17 1 Indoor Unit CS RE9NKR CS RE12NKR ...