27

Safety Precautions

3. Repairs to sealed components

• During repairs to sealed components, all 

electrical supplies shall be disconnected from 
the equipment being worked upon prior to any 
removal of sealed covers, etc.

• If it is absolutely necessary to have an 

electrical supply to equipment during 
servicing, then a permanently operating 
form of leak detection shall be located at the 
most critical point to warn of a potentially 
hazardous situation.

• Particular attention shall be paid to the 

following to ensure that by working on 
electrical components, the casing is not 
altered in such a way that the level of 
protection is affected. This shall include 
damage to cables, excessive number of 
connections, terminals not made to original 
speci

fi

 cation, damage to seals, incorrect 

fi

 tting 

of glands, etc.

• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have 

not degraded such that they no longer serve 
the purpose of preventing the ingress of 

fl

 ammable atmospheres.

• Replacement parts shall be in accordance 

with the manufacturer’s speci

fi

 cations.

NOTE: The use of silicon sealant may inhibit 
the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a 

fl

 ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts speci

fi

 ed 

by the manufacturer. Unspeci

fi

 ed parts by 

manufacturer may result ignition of refrigerant 
in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching or 
detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked 

fl

 ame) shall not be used.

7. The following leak detection methods 

are deemed acceptable for all refrigerant 
systems

• No leaks shall be detected when using 

detection equipment with a sensitivity of 
5 grams per year of refrigerant or better 
under a pressure of at least 0.25 times the 
maximum allowable pressure (>1.04 MPa, 
max 4.15 MPa), for example, a universal 
sniffer.

• Electronic leak detectors may be used 

to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need 
re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed 
and the appropriate percentage of gas (25 % 
maximum) is con

fi

 rmed.

• Leak detection 

fl

uids are also suitable for use 

with most refrigerants, for example, bubble 
method and 

fl

uorescent method agents. The 

use of detergents containing chlorine shall 
be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

• If a leak is suspected, all naked 

fl

 ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. The precautions 
in #8 must be followed to remove the 
refrigerant.

English

Summary of Contents for CS-PU9XKH-8M

Page 1: ...i d n l nh Operating Instructions Air Conditioner 20 37 Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the install...

Page 2: ...K o n p y l ng c a i u khi n 2 L p pin AAA ho c R03 3 y n p A i u ch nh ng h 1 Nh n sau nh n c i t th i gian Nh n v gi n t trong kho ng 5 gi y hi n th th i gian theo d ng 12 gi am pm ho c 24 gi 2 Nh...

Page 3: ...kh c so v i m y th c Nh s n xu t c th thay i m kh ng b o tr c C m n b n l a ch n M y i u h a kh ng kh Panasonic B C c t nh n ng c b n 2 Nh n MODE ch n ch mong mu n DRY AUTO COOL 1 Nh n OFF ON OFF ON...

Page 4: ...n ng ch u tr ch nhi m v an to n cho h Kh ng n n tr em ngh ch ch i v i m y Vui l ng li n h v i i l y quy n ho c chuy n gia v sinh c c b ph n b n trong s a ch a l p t th o v l p l i m y L p t v x l kh n...

Page 5: ...ng i u khi n t xa Th o pin kh i i u khi n t xa n u kh ng s d ng trong th i gian d i Pin m i c ng lo i ph i c l p ng c c nh ch d n Ngu n c p i n Kh ng k o d y ngu n ra kh i c m tr nh b gi t i n Ngu n...

Page 6: ...c n b c k n u h b ng k p d y bu c b o qu n R32 gi ng nh b o qu n R410A Vi c v n h nh b o d ng s a ch a v n p l i m i ch t l m l nh ph i c ti n h nh b i c c nh n vi n c o t o v ch ng nh n v ph i c gi...

Page 7: ...x l theo ng quy nh 2 B o tr 2 1 Nh n vi n b o tr H th ng c ki m tra th ng xuy n gi m s t v s a ch a b i nh n vi n b o h nh c o t o v ch ng nh n c thu b i ng i s d ng hay m t t ch c c tr ch nhi m C n...

Page 8: ...g gi ph i m b o ph n t n m i ch t l m l nh c th i ra m t c ch an to n v t t h n l n n th i ra ngo i kh ng kh 2 7 Ki m tra thi t b l m l nh Khi ph i thay i c c thi t b i n ph i s d ng c c thi t b m i p...

Page 9: ...m n c ph i ch u p l c ph c b rung c c c m p s c hay ch u c c t c ng kh c c a m i tr ng hay kh ng Vi c ki m tra c ng c n t nh n nh h ng c a th i gian s d ng c a thi t b hay s rung li n t c t c c ngu n...

Page 10: ...ch h p theo h ng d n m b o r ng h th ng l m l nh c ti p t tr c khi n p m i ch t l m l nh cho h th ng D n nh n l n h th ng khi qu tr nh n p li u ho n t t n u ch a c l m C n ph i h t s c c n tr ng kh n...

Page 11: ...qu tr nh n p m i ch t cho to n h th ng M i b nh ch a c s d ng ph i c quy nh r cho c c m i ch t c thu h i v ph i c d n nh n c n th n cho m i ch t c ngh a l c c b nh ch a c bi t thu h i m i ch t B nh c...

Page 12: ...T Khi ch n ch AUTO FAN QU T T NG t c qu t s c t ng i u ch nh theo ch ho t ng QUIET Y N T NH Gi m ti ng n c a lu ng gi th i POWERFUL t c nhi t mong mu n nhanh ch ng M y s t ng ng ng ho t ng sau 4 ti ng...

Page 13: ...OFF SET TIMER CANCEL CANCEL 1 2 3 1 Ch n ch TIMER ON B T hay TIMER OFF T T V d OFF T T l c 22 00 gi M i l n b m OFF 7KL W O S FK WKRiW 2 Ch n th i gian 3 X c nh n c i t SET h y ch h n gi nh n n t ON...

Page 14: ...c c nh v tr gi a Khi t nhi t c nh o gi ngang s t ng di chuy n l n xu ng ch COOL DRY L M L NH H T M C nh o gi ngang s t ng di chuy n l n xu ng i u khi n ch t kh i ng Khi i n c kh i ph c sau khi m t i n...

Page 15: ...trong khi m y ang ho t ng L i l c kh 2 tu n m t l n R a tr ng l i l c nh nh ng v i n c tr nh l m h b m t l i l c Ph i kh l i l c trong b ng r m tr nh xa l a ho c ph i tr c ti p d i n ng Thay l i l c k...

Page 16: ...x i theo d ng n c hay h i B c m u m t s linh ki n b ng nh a S b c m u t y thu c v o v t li u c s d ng trong c c linh ki n b ng nh a Qu tr nh n y s di n ra nhanh h n khi ti p x c v i nhi t nh s ng m t...

Page 17: ...c i u khi n t xa b m t ho c c l i x y ra tr n bi t th m chi ti t Sau 15 ph t ho t ng n u ch nh l ch nhi t gi a c a gi v o v c a gi ra nh d i y c ngh a l m y ho t ng b nh th ng COOL L M L NH 8 C 14 4 F...

Page 18: ...1 C m bi n h b i c v n H 32 C m bi n nhi t d n trao i nhi t s 2 c a kh i ngo i b t th ng H 33 Kh i trong kh i ngo i m t k t n i v i nhau H 34 C m bi n nhi t b l m m t kh i ngo i b t th ng H 35 N c ng...

Page 19: ...ng nhau K hi u n y c th d ng k t h p v i m t k hi u h a h c Trong tr ng h p n y n tu n th c c quy nh c li n quan v h a ch t B O NG Bi u t ng n y cho bi t thi t b d ng m i ch t l m l nh c th g y ch y...

Page 20: ...back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm or...

Page 21: ...s only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the ope...

Page 22: ...e supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit I...

Page 23: ...long period of time New batteries of the same type must be inserted following the polarity stated Power supply Do not disconnect the plug by pulling the cord to prevent electric shock nanoe G generat...

Page 24: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use o...

Page 25: ...the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised...

Page 26: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 27: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also...

Page 28: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 29: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 30: ...cording to the operation mode QUIET This operation reduces airflow noise POWERFUL To reach the desired temperature quickly This operation is automatically stop after 4 hours ECO To reduce power consum...

Page 31: ...AN SPEED QUIET POWERFUL ECO Can be selected at the same time Can be activated in all modes POWERFUL QUIET and FAN SPEED cannot be selected at the same time To set the timer ON OFF SET TIMER CANCEL CAN...

Page 32: ...zontal flap is fixed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Auto...

Page 33: ...Air filters Once every 2 weeks Wash rinse the filters gently with water to avoid damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged fi...

Page 34: ...unit during deice cycle melts and is discharged as water or steam Discoloration of some plastic parts Discoloration is subjected to the types of materials used in plastic parts It is accelerated when...

Page 35: ...g or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units will be n...

Page 36: ...heat sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnorma...

Page 37: ...ght be used in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flam...

Page 38: ...Memo...

Page 39: ...Memo...

Page 40: ...Printed in Malaysia ACXF55 29820 FZ0421 0 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021...

Reviews: