58
12.10 Cooling Overload Control
•
Pipe temperature limitation / restriction.
o
Detects the outdoor pipe temperature and carry out restriction / limitation below (Limit the compressor
operation frequency)
o
The compressor stops if outdoor pipe temperature exceeds 61°C.
o
If the compressor stops 4 times in 20 minutes, Timer LED blinks (“F95” indicated: Outdoor high pressure rise
protection)
12.11 Freeze Prevention Control
•
When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stops
operation.
•
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 13°C.
•
At the same time, indoor fan speed will be higher than during its normal operation.
•
If the indoor heat exchanger temperature is higher than 13°C for 5 minutes, the fan speed will return to its normal
operation.
12.12 Freeze Prevention Control 2
•
Control start conditions
o
During Cooling operation and soft dry operation
During Thermo OFF condition, Indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
o
Either one of the conditions above occurs 5 times in 60 minutes.
•
Control
contents
o
Operation
stops
o
Timer LED blinks and “H99” indicated
12.13 Dew Prevention Control
•
To prevent dew formation at indoor unit discharge area.
•
This control will be activated if:
o
Cooling mode or Quiet mode is activated.
o
Remote control setting temperature is less than 25°C.
o
Fan Speed is at CLo or QLo.
o
Room temperature is constant (±1°C) for 30 minutes.
o
Compressor is continuously running.
•
Fan speed will be adjusted accordingly in this control.
o
Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
12.14 Odor Cut Control
•
To reduce the odor released from the unit.
o
Start
Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o
Control
content
Depends on compressor conditions:
1. Compressor
OFF
→
Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor
ON
→
Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
Summary of Contents for CS-PS9PKV
Page 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9PKV CS PS12PKV...
Page 11: ...11 4 1 2 CS PS18PKV CS PS24PKV...
Page 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9PKV 4 2 2 CU PS12PKV CU PS18PKV...
Page 13: ...13 4 2 3 CU PS24PKV...
Page 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9PKV CU PS9PKV CS PS12PKV CU PS12PKV...
Page 15: ...15 5 2 CS PS18PKV CU PS18PKV CS PS24PKV CU PS24PKV...
Page 16: ...16 6 Block Diagram 6 1 CS PS9PKV CU PS9PKV...
Page 17: ...17 6 2 CS PS12PKV CU PS12PKV...
Page 18: ...18 6 3 CS PS18PKV CU PS18PKV...
Page 19: ...19 6 4 CS PS24PKV CU PS24PKV...
Page 21: ...21 7 1 2 CS PS18PKV CS PS24PKV...
Page 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9PKV CS PS12PKV...
Page 27: ...27 8 1 2 CS PS18PKV CS PS24PKV...
Page 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9PKV...
Page 29: ...29 8 2 2 CU PS12PKV...
Page 30: ...30 8 2 3 CU PS18PKV...
Page 31: ...31 8 2 4 CU PS24PKV...
Page 33: ...33 9 1 1 2 CS PS18PKV CS PS24PKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Page 34: ...34 9 1 3 Comparator Printed Circuit Board 9 1 4 Human Activity Sensor Printed Circuit Board...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9PKV...
Page 36: ...36 9 2 1 2 CU PS12PKV...
Page 37: ...37 9 2 1 3 CU PS18PKV...
Page 38: ...38 9 2 1 4 CU PS24PKV...
Page 39: ...39 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9PKV...
Page 93: ...93 15 2 5 To remove cross flow fan and indoor fan motor Figure 17 Figure 18 Figure 19...
Page 94: ...94 Figure 20...