61
14. Troubleshooting
Guide
14.1 Refrigeration Cycle System
In order to diagnose malfunctions, ensure the air conditioner is free
from electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan. The normal
outlet air temperature and pressure of the refrigeration cycle
depends on various conditions, the standard values for them are
shown in the table to the right.
Normal Pressure and Outlet Air Temperature (Standard)
Gas Pressure
Mpa
(kg/cm
2
G)
Outlet air
Temperature
(°C)
Cooling Mode
0.9 ~ 1.2 (9 ~ 12)
12 ~ 16
Condition: Indoor fan speed = High
Outdoor temperature = 35°C at cooling mode.
Compressor operate at rated frequency
Different in the intake
and outlet
air temperatures
Normal
Value of electric current
during operation
Dusty condenser
preventing heat radiation
Excessive amount
of refrigerant
Gas side
pressure
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
capillary cube
•
Measuring the air
temperature different
•
Measuring electric current
during operation
•
Measuring gas side
pressure
More than 8
°
C
(15 minutes after an
operation is started) at
cooling mode.
Less than 8
°
C at the cooling mode
Higher than specified
Cooling
Mode
High
Low
Low
Lower than specified
Summary of Contents for CS-PS9PKV
Page 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9PKV CS PS12PKV...
Page 11: ...11 4 1 2 CS PS18PKV CS PS24PKV...
Page 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9PKV 4 2 2 CU PS12PKV CU PS18PKV...
Page 13: ...13 4 2 3 CU PS24PKV...
Page 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9PKV CU PS9PKV CS PS12PKV CU PS12PKV...
Page 15: ...15 5 2 CS PS18PKV CU PS18PKV CS PS24PKV CU PS24PKV...
Page 16: ...16 6 Block Diagram 6 1 CS PS9PKV CU PS9PKV...
Page 17: ...17 6 2 CS PS12PKV CU PS12PKV...
Page 18: ...18 6 3 CS PS18PKV CU PS18PKV...
Page 19: ...19 6 4 CS PS24PKV CU PS24PKV...
Page 21: ...21 7 1 2 CS PS18PKV CS PS24PKV...
Page 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9PKV CS PS12PKV...
Page 27: ...27 8 1 2 CS PS18PKV CS PS24PKV...
Page 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9PKV...
Page 29: ...29 8 2 2 CU PS12PKV...
Page 30: ...30 8 2 3 CU PS18PKV...
Page 31: ...31 8 2 4 CU PS24PKV...
Page 33: ...33 9 1 1 2 CS PS18PKV CS PS24PKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Page 34: ...34 9 1 3 Comparator Printed Circuit Board 9 1 4 Human Activity Sensor Printed Circuit Board...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9PKV...
Page 36: ...36 9 2 1 2 CU PS12PKV...
Page 37: ...37 9 2 1 3 CU PS18PKV...
Page 38: ...38 9 2 1 4 CU PS24PKV...
Page 39: ...39 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9PKV...
Page 93: ...93 15 2 5 To remove cross flow fan and indoor fan motor Figure 17 Figure 18 Figure 19...
Page 94: ...94 Figure 20...