12. Protection
Control
12.1 Restart Control (Time Delay Safety Control)
•
The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
•
This control is not applicable if the power supply is cut off and on again.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
12.2 30 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
•
The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
12.3 Total Running Current Control
•
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
•
If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
•
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3
minutes.
Model PS9*** PS12*** PS18*** PS24***
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling / Soft Dry (A)
5.5
14.5
6.8
15.0
10.4
14.7
12.9
19.0
Cooling / Soft Dry (B)
5.0
14.5
6.2
15.0
9.5
14.7
12.4
19.0
•
The first 30 minutes of cooling operation, (A) will be applied.
12.4 IPM (Power Transistor) Prevention Control
•
Overheating Prevention Control
o
When the IPM temperature rises to 100°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 95°C.
•
DC Peak Current Control
o
When electric current to IPM exceeds set value of 18.5A, the compressor will stop operate. Then, operation
will restart after 3 minutes.
o
If the set value exceeds again more than 30 seconds after the compressor starts, the operation will restart
after 2 minutes.
o
If the set value exceeds again within 30 seconds after the compressor starts, the operation will restart after 1
minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off.
(B)
(A)
Outdoor air temperature
38.5°C
37.5°C
Summary of Contents for CS-PS9PKV
Page 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9PKV CS PS12PKV...
Page 11: ...11 4 1 2 CS PS18PKV CS PS24PKV...
Page 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9PKV 4 2 2 CU PS12PKV CU PS18PKV...
Page 13: ...13 4 2 3 CU PS24PKV...
Page 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9PKV CU PS9PKV CS PS12PKV CU PS12PKV...
Page 15: ...15 5 2 CS PS18PKV CU PS18PKV CS PS24PKV CU PS24PKV...
Page 16: ...16 6 Block Diagram 6 1 CS PS9PKV CU PS9PKV...
Page 17: ...17 6 2 CS PS12PKV CU PS12PKV...
Page 18: ...18 6 3 CS PS18PKV CU PS18PKV...
Page 19: ...19 6 4 CS PS24PKV CU PS24PKV...
Page 21: ...21 7 1 2 CS PS18PKV CS PS24PKV...
Page 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9PKV CS PS12PKV...
Page 27: ...27 8 1 2 CS PS18PKV CS PS24PKV...
Page 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9PKV...
Page 29: ...29 8 2 2 CU PS12PKV...
Page 30: ...30 8 2 3 CU PS18PKV...
Page 31: ...31 8 2 4 CU PS24PKV...
Page 33: ...33 9 1 1 2 CS PS18PKV CS PS24PKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Page 34: ...34 9 1 3 Comparator Printed Circuit Board 9 1 4 Human Activity Sensor Printed Circuit Board...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9PKV...
Page 36: ...36 9 2 1 2 CU PS12PKV...
Page 37: ...37 9 2 1 3 CU PS18PKV...
Page 38: ...38 9 2 1 4 CU PS24PKV...
Page 39: ...39 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9PKV...
Page 93: ...93 15 2 5 To remove cross flow fan and indoor fan motor Figure 17 Figure 18 Figure 19...
Page 94: ...94 Figure 20...