59
14.3 Error Code Table
Diagnosis
display
Abnormality / Protection control
Abnormality Judgment
Emergency
Operation
Primary location to verify
H00
No abnormality detected
-
Normal operation
H11
Indoor / Outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
•
Internal / external cable connection
•
Indoor / outdoor PCB
H12
Connection capability rank abnormality
Continuously for 90 sec
after power supplied
- -
H14
Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
-
•
Intake air temperature sensor
(defective or disconnected)
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
-
•
Compressor temperature sensor
(defective or disconnected)
H16
Outdoor current transformer open circuit
-
-
•
Outdoor
PCB
•
IPM (Power transistor) module
H19
Indoor fan motor mechanism locked
7 occurrences
continuously
-
•
Indoor
PCB
•
Fan
motor
H23
Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
○
•
Heat exchanger temperature sensor
(defective or disconnected)
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
○
•
Outdoor temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
○
•
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
H30
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
○
•
Outdoor discharge pipe temperature
sensor (defective or disconnected)
H33
Indoor / outdoor wrong connection
-
-
•
Indoor / outdoor supply voltage
H38
Indoor / outdoor mismatch (brand code)
-
-
-
H97
Outdoor fan motor mechanism locked
2 occurrences within 30
minutes
-
•
Outdoor
PCB
•
Outdoor Fan Motor
H98
Indoor temperature rise abnormality
-
-
•
Air filter dirty
•
Air circulation short circuit
H99
Indoor heat exchanger freeze prevention
protection
- -
•
Insufficient
refrigerant
•
Air filter dirty
F11
4 way valve switching failure *
4 occurrences within 30
minutes
-
•
4-way
valve
•
v-coil
F90
System and compressor microcomputer
communication error(for S10*** only)
2 occurrences within 5
seconds
-
•
Compressor
•
Outdoor
PCB
F90
Power factor correction abnormality
4 occurrences within 20
minutes
-
•
Outdoor
PCB
F91
Refrigerant cycle abnormal
2 occurrences within 20
minutes
-
•
No refrigerant ( 3-way valve is
closed)
F93
Outdoor compressor abnormal revolution 4 occurrences within 20
minutes
-
•
Outdoor
compressor
F95
Cooling high pressure protection
4 occurrences within 20
minutes
-
•
Outdoor refrigerant circuit
F96
Intelligent power transistor overheating
protection
-
•
Excess
refrigerant
•
Improper heat radiation
•
IPM (Power transistor)
F97
Compressor temperature rise protection
control
4 times occurrence within
20 minutes
-
•
Insufficient
refrigerant
•
Compressor
F98
Total running current protection
3 times occurrence within
20 minutes
-
•
Excess
refrigerant
•
Improper heat radiation
F99
Outdoor direct current (DC) peak
detection
7 times occurrence
continuously
-
•
Outdoor
PCB
•
IPM (Power transistor)
•
Compressor
Note:
“
○
” – Frequency measured and fan speed fixed
“ * ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one “beep” to four “beep” sounds.
Summary of Contents for CS-PS9NKV
Page 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9NKV CS PS12NKV...
Page 11: ...11 4 1 2 CS PS18NKV CS PS24NKV...
Page 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9NKV 4 2 2 CU PS12NKV CU PS18NKV...
Page 13: ...13 4 2 3 CU PS24NKV...
Page 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9NKV CU PS9NKV CS PS12NKV CU PS12NKV...
Page 15: ...15 5 2 CS PS18NKV CU PS18NKV CS PS24NKV CU PS24NKV...
Page 16: ...16 6 Block Diagram 6 1 CS PS9NKV CU PS9NKV...
Page 17: ...17 6 2 CS PS12NKV CU PS12NKV...
Page 18: ...18 6 3 CS PS18NKV CU PS18NKV...
Page 19: ...19 6 4 CS PS24NKV CU PS24NKV...
Page 20: ...20 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS PS9NKV CS PS12NKV...
Page 21: ...21 7 1 2 CS PS18NKV CS PS24NKV...
Page 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9NKV CS PS12NKV...
Page 27: ...27 8 1 2 CS PS18NKV CS PS24NKV...
Page 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9NKV...
Page 29: ...29 8 2 2 CU PS12NKV...
Page 30: ...30 8 2 3 CU PS18NKV...
Page 31: ...31 8 2 4 CU PS24NKV...
Page 33: ...33 9 1 1 2 CS PS18NKV CS PS24NKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Page 34: ...34 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9NKV...
Page 35: ...35 9 2 1 2 CU PS12NKV...
Page 36: ...36 9 2 1 3 CU PS18NKV...
Page 37: ...37 9 2 1 4 CU PS24NKV...
Page 38: ...38 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9NKV...
Page 86: ...86 Figure 13 Figure 14 15 2 3 To remove discharge grille Figure 15...
Page 88: ...88 Figure 19 Figure 20...