52
12.5 Low Pressure Prevention Control (Gas Leakage Detection)
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
•
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
12.6 Compressor Tank Temperature Rise Protection Control
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
•
Control
contents
o
Compressor stops (and restart after 3 minutes)
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
12.7 Low Frequency Protection Control 1
•
When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
12.8 Low Frequency Protection Control 2
•
When all below conditions comply, the compressor frequency will changed to lower frequency.
Temperature, T, for:
Cooling / Soft Dry
Indoor intake air (°C)
T < 15 or T
≥
30
Outdoor air (°C)
T < 16 or T
≥
38
Indoor heat exchanger (°C)
T < 30
12.9 Outdoor Air Temperature Control
•
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
•
This control will begin 1 minute after the compressor starts.
•
Compressor
frequency will adjust based on outdoor air temperature.
Free
Limited Frequency
Outdoor air temperature
38°C
37°C
Summary of Contents for CS-PS9NKV
Page 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9NKV CS PS12NKV...
Page 11: ...11 4 1 2 CS PS18NKV CS PS24NKV...
Page 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9NKV 4 2 2 CU PS12NKV CU PS18NKV...
Page 13: ...13 4 2 3 CU PS24NKV...
Page 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9NKV CU PS9NKV CS PS12NKV CU PS12NKV...
Page 15: ...15 5 2 CS PS18NKV CU PS18NKV CS PS24NKV CU PS24NKV...
Page 16: ...16 6 Block Diagram 6 1 CS PS9NKV CU PS9NKV...
Page 17: ...17 6 2 CS PS12NKV CU PS12NKV...
Page 18: ...18 6 3 CS PS18NKV CU PS18NKV...
Page 19: ...19 6 4 CS PS24NKV CU PS24NKV...
Page 20: ...20 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS PS9NKV CS PS12NKV...
Page 21: ...21 7 1 2 CS PS18NKV CS PS24NKV...
Page 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9NKV CS PS12NKV...
Page 27: ...27 8 1 2 CS PS18NKV CS PS24NKV...
Page 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9NKV...
Page 29: ...29 8 2 2 CU PS12NKV...
Page 30: ...30 8 2 3 CU PS18NKV...
Page 31: ...31 8 2 4 CU PS24NKV...
Page 33: ...33 9 1 1 2 CS PS18NKV CS PS24NKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Page 34: ...34 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9NKV...
Page 35: ...35 9 2 1 2 CU PS12NKV...
Page 36: ...36 9 2 1 3 CU PS18NKV...
Page 37: ...37 9 2 1 4 CU PS24NKV...
Page 38: ...38 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9NKV...
Page 86: ...86 Figure 13 Figure 14 15 2 3 To remove discharge grille Figure 15...
Page 88: ...88 Figure 19 Figure 20...