Delay ON Timer ca be set using remote controller, the unit with timer set will start operate earlier than
the setting time. This is to provide a comfortable environment when reaching the set On time.
Seventy minutes before the set time for ON Timer or ON-OFF Timer setting, indoor ( at fan speed of
Lo-) and outdoor fan motor start operate for 20 seconds to determine the indoor intake air
temperature and outdoor air temperature in order to judge the operation mode.
From the above judgment, the decided operation will start operate earlier than the set time as shown
below.
Indoor intake air
temperature (
)
30
25
30
25
10 Min
5 Min
Outdoor air
temperature (
)
Indoor intake air
temperature (
)
15
5
0
5
45 Min
50 Min
Outdoor air
temperature (
)
Cooling/Soft Dry
Heating
Timer Signal Receiving Sound During Operation
Operation
Sound
Timer LED Timer Setting
ON Timer Set
OFF
Beep-
ON
Valid
OFF Timer Set
ON
Beep
ON
Valid
ON-OFF Timer Set
OFF
Beep-
ON
Valid
OFF-ON Timer Set
ON
Beep
ON
Valid
Operation
Sound
Timer LED Timer Setting
ON Timer Set
OFF
Beep
ON
Valid
OFF Timer Set
OFF
None
OFF
Invalid
ON-OFF Timer Set
OFF
Beep
ON
Valid
OFF-ON Timer Set
OFF
None
OFF
Invalid
Timer Signal Receiving Sound When the Air Conditioner Stops
15 Min
40 Min
8.8
Auto Restart Control
If there is a power failure, operation will be automatically restarted after 3-4 minutes when the power is
resumed. It will start with previous operation mode and airflow direction.
8.7 Delayed ON-Timer Control
37
CS-PE9DKE / CU-PE9DKE / CS-PE12DKE / CU-PE12DKE