Anti-Fog Protection
Outdoor Air Temp
PE9DKE
PE12DKE
0-30
a
45
58
30-90
b
40
54
90-420
c
40
54
0-30
a
45
58
30-90
b
40
54
90-420
c
35
46
0-30
a
35
46
30-90
b
35
46
90-420
c
35
46
0-30
a
35
46
30-90
b
35
46
90-420
c
35
46
800
850
960
1020
Indoor Fan Speed B
2
>30
<30
Indoor Fan Speed A
Operation Time(S)
1
>30
<30
1
The indoor fan speed is higher than A but less than B.
The indoor fan speed is less than A
Overload Protection For Cooling Operation
56
53
61
58
55
55
Off
>40Hz
8Hz/45s Down
Fixed
40-51Hz(*1)
40-64Hz(*2)
The frequency for the compressor will change according
to the outdoor piping temperature.
*1 PE9DKE
*2 PE12DKE
2
31
CS-PE9DKE / CU-PE9DKE / CS-PE12DKE / CU-PE12DKE