3. Deodorizing Control
This type of control is applicable on Cooling Mode and Soft Dry Mode operating only.
During cooling or soft dry operation with automatic fan speed, the unit will operate as state below for deodorizing purpose.
Deodorising Status
Compressor status
Period(sec)
Indoor fan speed
1
2
3
4
5
ON
OFF
40
50
20
90
40
OFF
OFF
Slo
…
Note*
Slo
OFF
ON
OFF
OFF
ON
Note*:Fan speed is automatic for cooling mode and Slo for soft dry mode.
4
5
4.5.4....
20
90
OFF
Slo
COMP
FM
1
ON
Outdoor Fan Motor Control
1. Specification of outdoor fan motor
Model
Fan Motor
Speed(rpm)
CU-PE9DKE
CU-PE12DKE
Induction Motor(6 Poles 1 speed)
Induction Motor(6 Poles 1 speed)
670
770
2. Operation of the fan motor
The outdoor fan runs during the operation of the compressor or within 30 seconds after the compressor stops.
30 seconds
ON
OFF
OFF
ON
ON
ON
Compressor
Outdoor Fan
CS-PE9DKE / CU-PE9DKE / CS-PE12DKE / CU-PE12DKE