11.2. Pumping down
1.
Confirm that both the 3-way valves are set to the open
position.
•
Remove the valve stem caps and confirm that the valve
stems are in the raised position.
•
Be sure to use a hexagonal wrench to operate the valve
stems.
2.
Operate the unit for 10 to 15 minutes.
3.
Stop operation and wait for 3 minutes, then connect the
charge set to the service port of the 3-way valves.
•
Connect the charge hose with the push pin to the gas
side service port.
4.
Air purging of the charge hose.
•
Open the low-pressure valve on the charge set slightly
to purge air from the charge hose.
5.
Set the Liquid side 3-way valve to the closed position.
6.
Operate the air conditioner at the cooling cycle and
stop it when the gauge indicates 0 kg/cm
2
G.
•
If the unit cannot be operated at the cooling (weather is
rather cool), press the Pump Down switch on the Indoor
unit.
•
So that the unit can be operated.
7.
Immediately set the 3-way valve to the closed position.
•
Do this quickly so that the gauge ends up indicating 1 to
3 kg/cm
2
G.
8.
Disconnect the charge set, and mount both the 3-way
valve’s stem nuts and the service port caps.
•
Use torque wrench CWHAD-9211 to tighten the service
port nut to a torque of 1.8 N.m.
•
Be sure to check for gas leakage.
Procedure:
45
CS-MC12DKV CU-2C24DKV
Summary of Contents for CS-MC12DKV
Page 3: ...2 Functions 3 CS MC12DKV CU 2C24DKV ...
Page 4: ...4 CS MC12DKV CU 2C24DKV ...
Page 8: ...4 Dimensions 4 1 Indoor Unit Remote Control 8 CS MC12DKV CU 2C24DKV ...
Page 9: ...4 2 Outdoor Unit 9 CS MC12DKV CU 2C24DKV ...
Page 10: ...5 Refrigeration Cycle Diagram 10 CS MC12DKV CU 2C24DKV ...
Page 11: ...6 Block Diagram 11 CS MC12DKV CU 2C24DKV ...
Page 12: ...7 Wiring Diagram 12 CS MC12DKV CU 2C24DKV ...
Page 26: ...9 Operating Instructions 26 CS MC12DKV CU 2C24DKV ...
Page 27: ...27 CS MC12DKV CU 2C24DKV ...
Page 28: ...28 CS MC12DKV CU 2C24DKV ...
Page 29: ...29 CS MC12DKV CU 2C24DKV ...
Page 30: ...30 CS MC12DKV CU 2C24DKV ...
Page 31: ...31 CS MC12DKV CU 2C24DKV ...
Page 57: ...14 3 Piping Length Characteristic Cooling 57 CS MC12DKV CU 2C24DKV ...
Page 67: ...67 CS MC12DKV CU 2C24DKV ...
Page 69: ...19 1 Remote Control 69 CS MC12DKV CU 2C24DKV ...
Page 70: ...19 2 Print Pattern Indoor Unit Printed Circuit Board 70 CS MC12DKV CU 2C24DKV ...
Page 71: ...71 CS MC12DKV CU 2C24DKV ...